3.4.2.5.(1)
OS3
ATTRIBUTION:
Functional Statement:
F10
To facilitate the timely movement of persons to a safe place in an emergency.
Objective:
OS3.7
APPLICATION:
Location of
exits
with respect to limiting the maximum travel distance to at least one
exit
, where more than one
exit
is required from a
floor area
.
This applies to
floor areas
that are intended for
occupancies
, including
mezzanines
as stated in
Sentence 3.4.2.2.(1)
, in
buildings
described in
Sentence 1.3.3.2.(1) of Division A
.
This also applies to:
travel distances within a room or
suite
to the nearest egress doorway, as stated in
Sentence 3.3.1.6.(1)
,
travel distances from a zone in a
floor area
that is not
sprinklered
and that has a
barrier-free
path of travel, as stated in
SubClause 3.3.1.7.(1)(b)(ii)
,
tents and
air-supported structures
, as stated in Sentences
3.1.6.1.(1)
and
9.10.1.2.(1)
, and
travel distances in
public corridors
referred to in
Clause 3.4.2.5.(1)(d)
, in
buildings
to which Part 9 applies [see
Sentence 1.3.3.3.(1) of Division A
for application of Part 9], as stated in
Sentence 9.9.8.1.(3)
.
INTENT:
To limit the probability of excessive travel distances to an exit in an emergency situation, which could lead to delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons.