Back6.2.3.11.(2)

ATTRIBUTION:

Functional Statement:

F81

To minimize the risk of malfunction, interference, damage, tampering, lack of use or misuse.

Objective:

OH1.1

 

APPLICATION:

Interlocking of make-up air facilities with the exhaust devices they serve, for ventilating systems that exhaust air to the outdoors, in buildings described in Sentence 1.3.3.2.(1) of Division A.
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], with respect to:

INTENT:

To limit the probability that exhaust systems will operate without the introduction of make-up air, which could lead to the depressurization of occupied space from which air is being exhausted, which could lead to:
  • a reduction in exhaust air volume, which could lead to inadequate ventilation, or
  • the entry of combustion products from fuel-fired appliances into the building.
This is to limit the probability of negative effects on the air quality of indoor spaces, which could lead to harm to persons.

ATTRIBUTION:

Functional Statement:

F81

To minimize the risk of malfunction, interference, damage, tampering, lack of use or misuse.

F44

To limit the spread of hazardous substances beyond their point of release.

Objective:

OS3.4

 

APPLICATION:

Interlocking of make-up air facilities with the exhaust devices they serve, for ventilating systems that exhaust air to the outdoors, in buildings described in Sentence 1.3.3.2.(1) of Division A.
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], with respect to:

INTENT:

To limit the probability that exhaust systems will operate without the introduction of make-up air, which could lead to the depressurization of occupied space from which air is being exhausted, which could lead to the entry of carbon monoxide gas from fuel-fired appliances into the building, which could lead to harm to persons.