Back6.2.9.5.(1)

ATTRIBUTION:

Functional Statement:

F01

To minimize the risk of accidental ignition.

Objective:

OS1.1

 

APPLICATION:

Protection of surrounding building elements from pipes carrying steam or hot water at a temperature above 120°C that pass through combustible floors, ceilings or walls, in buildings described in Sentence 1.3.3.2.(1) of Division A.
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], with respect to heating systems, other than those serving individual dwelling units, as stated in Sentence 9.33.1.1.(2).

INTENT:

To limit the probability that combustible floors, ceilings or walls will be ignited by heat radiating from the pipes, which could lead to harm to persons.

ATTRIBUTION:

Functional Statement:

F01

To minimize the risk of accidental ignition.

Objective:

OP1.1

 

APPLICATION:

Protection of surrounding building elements from pipes carrying steam or hot water at a temperature above 120°,C that pass through combustible floors, ceilings or walls, in buildings described in Sentence 1.3.3.2.(1) of Division A.
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], with respect to heating systems, other than those serving individual dwelling units, as stated in Sentence 9.33.1.1.(2).

INTENT:

To limit the probability that combustible floors, ceilings or walls will be ignited by heat radiating from the pipes, which could lead to damage to the building.