Back6.2.7.1.(1)

ATTRIBUTION:

Functional Statement:

F01

To minimize the risk of accidental ignition.

Objective:

OP1.1

 

APPLICATION:

Minimum clearance between unit heaters that use either steam or hot water as the heating medium and adjacent combustible material, in buildings described in Sentence 1.3.3.2.(1) of Division A.

INTENT:

To limit the probability that radiating heat will reach combustible materials, which could lead to fire, which could lead to damage to the building.

ATTRIBUTION:

Functional Statement:

F01

To minimize the risk of accidental ignition.

Objective:

OS1.1

 

APPLICATION:

Minimum clearance between unit heaters that use either steam or hot water as the heating medium and adjacent combustible material, in buildings described in Sentence 1.3.3.2.(1) of Division A.

INTENT:

To limit the probability that radiating heat will reach combustible materials, which could lead to fire, which could lead to harm to persons.