1) The flow rates of fittings that supply water to plumbing fixtures must not exceed the maximum flow rate at the test pressures listed for that fitting in Table 10.3.1.1.
Table 10.3.1.1.A Maximum Flow Rates for Supply Fittings Forming Part of Sentence 10.3.1.1. (1) | |||
Fittings | Maximum Flow (L/min) | Test Pressure (kPa) | |
---|---|---|---|
Lavatory Faucet | 8.3 | 415 | |
Kitchen Faucet | 8.3 | 415 | |
Shower Head | 9.5 | 550 |
[Rev. 2, B.C. Reg. 73/2008.]
1) Except as required by Sentence (2), the flush cycle for the installation of a water closet or urinal must not exceed the flush cycle listed for that fixture in Table 10.3.1.2.(1)
Table 10.3.1.2. Maximum Flush Cycle Forming Part of Sentence 10.3.1.2. (1) | |
Fixture | Litres |
---|---|
Water Closet (Tank Type) | 6.0 |
Water Closet (Direct Flush) | 6.0 |
Urinal (Tank Type) | 1.9 |
Urinal (Direct Flush) | 1.9 |
2) The flush cycle for the installation of a water closet or urinal in buildings classified as Group C must not exceed the flush cycle listed for that fixture in Table 10.3.1.2.(2).
Table 10.3.1.2. Maximum Flush Cycle Forming Part of Sentence 10.3.1.2. (2) | |
Fixture | Litres |
---|---|
Water Closet (Tank Type) | 4.8(1) |
Water Closet (Direct Flush) | 4.8 |
Urinal (Tank Type) | 1.9 |
Urinal (Direct Flush) | 1.9 |
Notes to Table 10.3.1.2. | |
|
|
(1) | A water closet which provides a dual flush cycle option of both 4.1 L or less and 6.0 L shall be deemed to comply. |
3) The water supply to urinal flush tanks equipped for automatic flushing shall be controlled with a timing device in order to limit operation to the period during which the building is normally occupied.
[Rev. 13, B.C. Reg. 95/2010.]