Division B
Acceptable Solutions

Part 5 — Environmental Separation

(See Appendix A.)  (See Part 10)

[Rev. 2, B.C. Reg. 73/2008.]

Section 5.1. General

5.1.1. Scope

5.1.1.1. Scope

1) This Part is concerned withI

a)the control of condensation

i)in building components and assemblies, and

ii)on building materials, components and assemblies, and

b)the transfer of heat, air, moisture and sound through

i) building materials, components and assemblies, and

ii)interfaces between building materials, components and assemblies.

(See Appendix A.)

5.1.2. Application

5.1.2.1. Exposure to Exterior Space or the Ground and Separation of Dissimilar Environments

1) This Part applies, as described in Subsection 1.3.3. of Division A, toI

a) building materials, components and assemblies exposed to exterior space or the ground, including those separating interior space from exterior space or separating interior space from the ground,

b) building materials, components and assemblies separating environmentally dissimilar interior spaces (see A-5.9. in Appendix A), and

c)site materials, components, assemblies and grading that may affect environmental loads on building materials, components and assemblies exposed to exterior space or the ground.

(See Appendix A.)

5.1.3. Definitions

5.1.3.1. Defined Words

1) Words that appear in italics are defined in Article 1.4.1.2. of Division A.I

5.1.4. Resistance to Loads and Deterioration

5.1.4.1. Structural and Environmental Loads
(See Appendix A.)

1) Building materials, components and assemblies that separate dissimilar environments or are exposed to the exterior shall have sufficient capacity and integrity to resist or accommodateI

a)all environmental loads, and effects of those loads, that may reasonably be expected having regard to

i)the intended use of the building, and

ii)the environment to which the materials, components and assemblies are subject, and

b) all structural loads, and effects of those loads, that may reasonably be expected.

2) Compliance with Clause 5.1.4.1.(1)(a) shall be demonstrated by design complying with Subsection 5.2.1. and construction conforming to that design.I

3) Compliance with Clause 5.1.4.1.(1)(b) shall be demonstrated by design complying with Subsection 5.2.2., and construction conforming to that design, with regard toI

a)materials, components and assemblies, and associated loads, that are identified in Part 4,

b)air pressure loads imposed on air barrier systems,

c)wind up-lift imposed on roofing, and

d)hydrostatic pressure imposed on the means of protection from moisture in the ground.

4) For materials, components, assemblies and loads to which Sentence (3) does not apply, compliance with Clause 5.1.4.1.(1)(b) shall be demonstratedI

a)by design complying with Subsection 5.2.2. for individual applicable loads and construction conforming to that design, or

b)in the case of common materials, components and assemblies, and their installation, by proven past performance over a period of several years for individual applicable loads.

(See Appendix A.)

5) Materials, components and assemblies separating dissimilar environments and assemblies exposed to the exterior, including their connections, that are subject to structural loads, shallI

a)transfer such loads to the building structure without adverse effects on the performance of other materials, components or assemblies,

b)not deflect to a degree that adversely affects the performance of other materials, components or assemblies, and

c)be designed, and constructed according to that design, to accommodate

i)the maximum relative structural movement that may reasonably be expected, and

ii)construction tolerances that may be reasonably expected.

(See Article 4.1.3.5., Sentence 4.1.3.3.(2) and Subsection 4.1.8. for information on different types of structural movements.) (See A-5.1.4.1. and A-5.1.4.1.(5)(b) and (c) in Appendix A.)
5.1.4.2. Resistance to Deterioration
(See Appendix A.)

1) Except as provided in Sentence (2), materials used in building components and assemblies that separate dissimilar environments, or in assemblies exposed to the exterior, shall beI

a)compatible with adjoining materials, and

b)resistant to any mechanisms of deterioration that may reasonably be expected, given the nature, function and exposure of the materials.

2) Material compatibility and deterioration resistance are not required where it can be shown that incompatibility or uncontrolled deterioration will not adversely affect any ofI

a)the health or safety of building users,

b)the intended use of the building, or

c)the operation of building services.

5.1.5. Other Requirements

5.1.5.1. Requirements in Other Parts of the Code

1) Structural and fire safety requirements of other Parts of the BCBC shall apply.I