1) Sheathing shall be provided beneath stucco applied
over wood-frame walls except as permitted in Article 9.28.4.2.
2) Where applied beneath stucco, sheathing shall conform
to Subsection 9.23.16.
1) Stucco lath or reinforcing shall be used to attach
stucco to any substrate other than masonry.
2) Stucco lath or reinforcing shall be used to attach
stucco to masonry where
a)the masonry is soft-burned tile or brick of less strength than the stucco, or
b)the masonry surface is not sound, clean and sufficiently rough to provide a good key.
3) Stucco applied over masonry chimneys shall be reinforced.
1) Stucco finish shall not be applied over concrete
masonry units less than one month old unless the units have been
cured by the autoclave process.
1) Stucco shall be not less than 200 mm above finished
ground level except when it is applied over concrete or masonry.
1) Flashing and caulking used with stucco shall conform
to Subsections 9.27.3. and , except that if aluminum flashing is used, it shall be separated from the stucco
by an impervious membrane or coating. (See Article 9.7.4.2. for caulking around window frames.)
1) Portland cement shall conform to CSA-A3001,
“Cementitious Materials for Use in Concrete.”
[Rev. 12, B.C. Reg. 336/2010.]
1) Aggregate shall be clean, well-graded natural sand or
sand manufactured from crushed stone, gravel or air-cooled blast
furnace slag and shall contain no significant amounts of
deleterious material.
2) Aggregate grading shall conform to Table 9.28.2.2.
Table 9.28.2.2. Aggregate Grading for Stucco Forming Part of Sentence 9.28.2.2.(2) |
||
Sieve Sizes, mm | % Aggregate Passing Sieve | |
---|---|---|
Maximum | Minimum | |
4 | — | 100 |
2 | — | 90 |
1 | 90 | 60 |
0.5 | 60 | 45 |
0.25 | 30 | 10 |
0.125 | 5 | — |
1) Water shall be clean and free of significant amounts
of deleterious material.
1) Fasteners for stucco lath or reinforcing shall be
corrosion-resistant and of a material other than aluminum.
1) Nails for stucco lath or reinforcing shall be not less
than 3.2 mm diam with a head diameter of not less than 11.1 mm.
2) Staples for stucco lath or reinforcing shall
be not less than 1.5 mm diam or thickness.
3) Staples and nails for attaching stucco lath or
reinforcing to vertical surfaces shall be of sufficient length
to penetrate 25 mm into framing members or to the full depth of
the sheathing where the sheathing is used for attachment.
4) On horizontal surfaces nails for stucco lath or
reinforcing shall be not less than 38 mm long.
1) Rib lath or expanded metal stucco mesh shall be
a)copper-alloy steel coated with rust-inhibitive paint after fabrication, or
b)galvanized.
2) Woven or welded wire mesh shall be galvanized.
1) Sheathing need not be provided beneath stucco where
not less than 1.19 mm diam galvanized wire is applied
horizontally to the framing at vertical intervals of not more
than 150 mm, or where paper-backed welded wire metal lath is
used.
1) Stucco lath shall conform to Table 9.28.4.3.
Table 9.28.4.3. Stucco Lath Forming Part of Sentence 9.28.4.3.(1) |
||||
Location | Type of Lath | Minimum Diam of Wire, mm | Maximum Mesh Opening | Minimum Mass, kg/m2 |
---|---|---|---|---|
Vertical surfaces | Welded or woven wire | 1.15 | 25 mm | — |
1.30 | 38 mm | — | ||
1.50 | 51 mm | — | ||
Stucco mesh reinforcing (expanded metal) | — | 25.8 cm2 | 0.98 | |
Horizontal surfaces(1) | 9.5 mm rib lath | — | — | 1.84 |
Cedar lath | — | — | — |
Notes to Table 9.28.4.3. | |
|
|
(1) | See Appendix A. |
1) Stucco lath shall be held not less than 6 mm away from
the backing by means of suitable self-furring devices.
1) Stucco lath shall be applied with the long dimension
horizontal.
2) Horizontal and vertical joints in stucco lath shall be
lapped not less than 50 mm.
3) End joints of stucco lath shall be staggered and shall
occur over framing members.
4) External corners of stucco lath shall be reinforced
with a vertical strip of lath or reinforcing extending not less
than 150 mm on both sides of the corner, or the lath or
reinforcing shall extend around corners not less than 150 mm.
1) Stucco lath shall be fastened in conformance with
Subsection 9.27.5.
2) Fasteners on vertical surfaces shall be spaced not
more than
a)150 mm o.c. vertically and 400 mm o.c. horizontally, or
b)100 mm o.c. vertically and 600 mm o.c. horizontally.
3) Nailing patterns other than those required in Sentence (2) are permitted to be used provided there are at least 20
fasteners per square metre of wall surface.
4) Fasteners on horizontal surfaces shall be spaced not
more than
a)150 mm o.c. along the framing members when members are spaced not more than 400 mm o.c., and
b)100 mm o.c. along members when members are spaced not more than 600 mm o.c.
1) Stucco mixes shall conform to Table 9.28.5.1.
Table 9.28.5.1. Stucco Mixes Forming Part of Sentence 9.28.5.1.(1) |
|||
Materials, volume | |||
---|---|---|---|
Portland Cement | Masonry Cement | Lime | Aggregate |
1 | — | 0.25 to 1 | 3.25 to 4 parts per part of cementitious material |
1 | 1 | — |
1) Pigment if used shall consist of pure mineral oxides
inert to the action of sun, lime and cement.
2) Pigment shall not exceed 6% of the Portland cement by
weight.
1) Materials shall be thoroughly mixed before and after
water is added.
2) Stucco shall be applied not later than 3 h after the
initial mixing.
1) The base for stucco shall be maintained above
freezing.
2) Stucco shall be maintained at a temperature of not
less than 10°C during application, and for not less
than 48 h afterwards.
1) Stucco shall be applied with at least 2 base coats and
one finish coat, providing a total thickness of not less than
15 mm, measured from the face of the lath or the face of the
masonry where no lath is used.
1) The first coat shall be not less than 6 mm thick,
measured from the face of the lath or masonry, fully embedding
the lath.
2) The surface of the first coat shall be scored to
provide a key with the second coat.
1) The second coat shall be not less than 6 mm thick.
2) The surface of the second coat shall be lightly
roughened to provide a key with the finish coat if the finish
coat is other than stone dash.
1) When the finish coat is other than stone dash, the
base shall be dampened but not saturated before the finish coat
is applied.
2) The thickness of the finish coat shall be not less
than 3 mm.
3) When a stone dash finish is used, the stone shall be
partially embedded in the second coat before the second coat
starts to set or stiffen.