1) This Section applies to the design and installation of
heating systems, including requirements for combustion air, and
air-conditioning systems serving only one dwelling unit.
2) The design and installation of heating systems,
including requirements for combustion air, and air-conditioning
systems other than those serving individual dwelling units shall conform to Part 6. (See Appendix A and Subsection 9.10.10.)
1) Residential buildings intended for use in the winter months on a continuing basis shall be equipped with heating facilities
conforming to this Section.
1) At the outside winter design temperature, required
heating facilities shall be capable of maintaining an indoor air
temperature of not less than
a)22°C in all living spaces,
b)18°C in unfinished basements, and
c)15°C in heated crawl spaces.
1) The outdoor conditions to be used in designing heating
and air-conditioning systems shall be determined in conformance
with Article 1.1.3.1.
1) Heating and air-conditioning systems, including
ducting, and mechanical heating and refrigeration equipment,
shall be designed, constructed and installed to conform to the
relevant provincial or territorial regulations or municipal
bylaws or, in the absence of such regulations or bylaws, with
good practice such as described in the ASHRAE Handbooks and
Standards, the HRAI Digest, the Hydronics Institute Manuals and
the SMACNA Manuals. (See also Subsection 9.32.3. for the design of systems that also provide
ventilation.)
1) Equipment forming part of a heating or
air-conditioning system, with the exception of embedded pipes or
ducts, shall be installed with provision for access for
inspection, maintenance, repair and cleaning.
1) Equipment forming part of a heating or
air-conditioning system that may be adversely affected by
freezing temperatures and that is located in an unheated area
shall be protected from freezing.
1) Heating and cooling systems shall be designed to allow
for expansion and contraction of the heat transfer fluid and to
maintain the system pressure within the rated working pressure
limits of all components of the system.
1) Mechanical systems and equipment shall be designed and
installed to accommodate the maximum amount of structural
movement provided for in the construction of the building.
2) Where the building is in a location where the spectral response acceleration, Sa(0.2), is greater than 0.55,
heating and air-conditioning equipment with fuel or power
connections shall be secured to the structure to resist
overturning and displacement. (See A-9.31.6.2.(3) in Appendix A.)
1) Asbestos shall not be used in air distribution systems
or equipment in a form or in a location where asbestos fibres
could enter the air supply or return systems.
1) Systems serving garages, and systems serving other
occupied parts of a dwelling unit but located in or running through a garage, shall
be designed and constructed in a manner such that means are not
provided for the transfer of contaminants from the garage into
other spaces in the dwelling unit.
1) The required capacity of heating appliances located in a dwelling unit and serving only that dwelling unit, shall be determined in accordance with CAN/CSA-F280-M, “Determining
the Required Capacity of Residential Space Heating and
Cooling Appliances,” except that the design
temperatures shall conform to Subsection 9.33.3.
1) Except as provided in Articles 9.33.5.3. and 9.33.5.4., the installation of heating and air-conditioning equipment, including mechanical refrigeration equipment, and including provisions for mounting, clearances and air supply, shall conform to
a)CAN/CSA-B139-M, “Installation Code for Oil Burning Equipment,” for the installation of oil burning equipment
b)the BC Safety Standards Act and its following pursuant regulations:
i)the Gas Safety Regulations for the installation of natural gas and propane burning equipment,
ii)the Electrical Safety Regulation,
iii)the Power Engineers, Boiler, Pressure Vessel and Refrigeration Safety Regulation for the installation of boilers, pressure vessels, pressure piping and mechanical refrigeration,
c)CAN/CSA-B365-M, “Installation Code for Solid-Fuel Burning Appliances and Equipment,” or
d)CAN/CSA-C448-M, “Design and Installation of Earth Energy Systems.” (See also Sentence 9.33.5.3.(1).)
1) The design, construction and
installation, including the provision of combustion air, of
solid-fuel-burning appliances and equipment, including stoves, ranges and space heaters, shall conform to CAN/CSA-B365, “Installation Code for Solid-Fuel-Burning Appliances and
Equipment.”
1) Fireplaces shall conform to Section 9.22.
1) The design, construction and installation of air duct
distribution systems serving heating systems in which the rated
heat input does not exceed 120 kW shall conform to this
Subsection.
2) Air duct distribution systems in which the rated heat
input exceeds 120 kW shall conform to Part 6. and Subsection 3.6.5.
1) Except as provided in Sentences (2) to (6) and in Article 3.6.4.3., all ducts, duct connectors, associated
fittings and plenums used in air duct systems shall be constructed of steel, aluminum
alloy, copper, clay, asbestos-cement or similar noncombustible material.
2) Ducts, associated fittings and plenums are permitted to contain combustible material provided they
a)conform to the appropriate requirements for Class 1 duct materials in CAN/ULC-S110-M, “Tests for Air Ducts,”
b)conform to Article 3.1.5.15. and Subsection 3.1.9.,
c)are not used in vertical runs serving more than 2 storeys, and
d)are not used in air duct systems in which the air temperature may exceed 120°C.
3) Duct sealants shall have a flame-spread rating of not more than 25 and a smoke developed classification of not more
than 50.
4) Duct connectors that contain combustible materials and that are used between ducts and air outlet units shall
a)conform to the appropriate requirements for Class 1 air duct materials in CAN/ULC-S110-M, “Test for Air Ducts,”
b)be limited to 4 m in length,
c)be used only in horizontal runs, and
d)not penetrate required fire separations.
5) Combustible ducts that are part of a duct system carrying only ventilation air and that
are contained entirely within a dwelling unit need not comply with the requirements of Sentences (1) to (4).
6) Except as provided in Sentences 9.33.6.14.(2) and (3), ducts that are part of a return-air duct system and that are
contained entirely within a dwelling unit need not comply with the requirements of Sentences (1) to (4).
7) Materials referred to in Sentences (1) to (6), when used in a location where they may be subjected to excessive moisture,
shall
a)have no appreciable loss of strength when wet, and
b)be corrosion-resistant.
1) Tape used for sealing duct joints in air ducts, plenums and other parts of air duct systems shall meet the flame-resistance requirements
for fabric in CAN/ULC-S109, “Flame Tests of Flame-Resistant Fabrics and Films.”
1) Coverings, linings and associated adhesives and
insulation of air ducts, plenums and other parts of air duct systems shall be of noncombustible material when exposed to heated air or radiation from heat
sources that would result in the exposed surface exceeding a
temperature of 120°C.
2) Except as provided in Sentence (3), when combustible coverings and linings, including associated adhesives and
insulation, are used, they shall have
a)a flame-spread rating of not more than 25 on any exposed surface or any surface that would be exposed by cutting through the material in any direction, and
b)a smoke developed classification of not more than 50.
3) The outer covering of ducts, plenums and other parts of air duct systems used within an assembly of combustible construction are permitted to have
a)an exposed surface flame-spread rating of not more than 75, and
b)a smoke developed classification greater than 50.
4) Combustible coverings and linings described in Sentences (2) and (3) shall not flame, glow, smoulder or smoke when tested in
accordance with the method of test in ASTM C 411, “Hot-Surface
Performance of High-Temperature Thermal Insulation,”
at the maximum temperature to which the coverings and linings
are to be exposed in service.
5) Except as provided in Sentence (6), foamed plastic insulation shall not be used as part of an air
duct or for insulating an air duct.
6) Foamed plastic insulation is permitted to be used in a
ceiling space that acts as a return air plenum provided the foamed plastic insulation is protected from exposure to the plenum in accordance with Sentence 3.1.5.12.(2).
7) Combustible coverings and linings of ducts, including associated adhesives and
insulation, shall be interrupted
a)at the immediate area of operation of heat sources in a duct system, such as electric resistance heaters or fuel-burning heaters or furnaces, and
b)where the duct penetrates a fire separation.
8) Linings of ducts shall be installed so that they will
not interfere with the operation of volume or balancing dampers
or of fire dampers, fire stop flaps and other closures.
1) Galvanized steel or aluminum supply ducts shall conform to Table 9.33.6.5.
2) The design of fittings for ducts shall conform to
SMACNA, “HVAC Duct Construction Standards – Metal and Flexible,” except
that metal thicknesses shall conform to Table 9.33.6.5.
Table 9.33.6.5. Minimum Metal Thickness of Ducts Forming Part of Article 9.33.6.5. |
||||
Type of Duct | Maximum Diameter, mm | Maximum Width or Depth, mm | Minimum metal thickness, mm | |
---|---|---|---|---|
Duct Material | ||||
Galvanized Steel | Aluminum | |||
Round ducts serving single dwelling units | 125 or less | — | 0.254 | 0.30 |
Round | 350 | — | 0.33 | 0.30 |
Over 350 | — | 0.41 | 0.41 | |
Rectangular, enclosed | — | 350 | 0.33 | 0.30 |
— | Over 350 | 0.41 | 0.41 | |
Rectangular, not enclosed, for single dwelling units, with required clearance up to 12 mm | — | 350 | 0.33 | 0.41 |
— | Over 350 | 0.41 | 0.48 | |
Rectangular, not enclosed, with required clearance of more than 12 mm | — | 350 | 0.41 | 0.41 |
— | Over 350 | 0.48 | 0.48 |
1) Where the installation of heating supply ducts in walls and floors creates a space between the duct and construction
material, the space shall be fire stopped with noncombustible material at each end.
2) Ducts shall be securely supported by metal hangers,
straps, lugs or brackets, except that, where zero clearance is
permitted, wooden brackets are permitted to be used.
3) All round duct joints shall be tight-fitting and
lapped not less than 25 mm.
4) Rectangular duct connections shall be made with S and
drive cleats or equivalent mechanical connections.
5) Duct systems shall have no openings other than those
required for the proper operation and maintenance of the system.
1) Air duct systems serving garages shall not be
interconnected with other parts of the dwelling unit.
2) Trunk supply ducts shall not be nailed directly to wood members.
3) Branch ducts shall be supported at suitable spacings
to maintain alignment and prevent sagging.
4) Ducts passing through unheated spaces shall have all
joints taped or otherwise sealed to ensure that the ducts are
airtight throughout their length.
5) Combustible ducts in concrete slabs-on-ground that are connected to a furnace supply plenum shall be located not closer than 600 mm to that plenum and not less than 600 mm from its connection to a riser or register.
6) Ducts in or beneath concrete slabs-on-ground shall be
watertight and corrosion-, decay-, and mildew-resistant.
a)be constructed to provide interior drainage from and access to all low points, and
b)not be connected directly to a sewer.
1) The clearance of furnace plenums from combustible material shall conform to the appropriate standards in Sentence 9.33.5.2.(1).
2) Where the plenum clearance required in Sentence (1) is 75 mm or less, the clearance between a supply duct and combustible material shall
a)be equal to the required plenum clearance within 450 mm of the plenum, and
b)be not less than 12 mm at a distance of 450 mm or more from the plenum, except that this clearance may be reduced to zero beyond a bend or offset in the duct sufficiently large to shield the remainder of the supply duct from direct radiation from the furnace heat exchanger. (See A-3.6.5.6.(2) in Appendix A.)
3) Where the plenum clearance required in Sentence (1) is more than 75 mm but not more than 150 mm, the clearance
between a supply duct and combustible material shall be
a)equal to the required plenum clearance within a horizontal distance of 1.8 m of the plenum, and
b)not less than 12 mm at a horizontal distance of 1.8 m or more from the plenum, except that this distance may be reduced to zero beyond a bend or offset in the duct sufficiently large to shield the remainder of the duct from direct radiation from the furnace heat exchanger. (See A-3.6.5.6.(3) in Appendix A.)
4) Where the plenum clearance required in Sentence (1) is more than 150 mm, the clearance between a supply duct and combustible material shall be
a)equal to the required plenum clearance within a horizontal distance of 1 m of the plenum,
b)not less than 150 mm within a horizontal distance between 1 m and 1.8 m from the plenum, and
c)not less than 25 mm at a horizontal distance of 1.8 m or more from the plenum, except that this distance may be reduced to 8 mm beyond a bend or offset in the duct sufficiently large to shield the remainder of the supply duct from direct radiation from the furnace heat exchanger. (See A-3.6.5.6.(4) in Appendix A.)
5) Where a register is installed in a floor directly over
a pipeless furnace, a double-walled register box with not less than 100 mm between
walls, or a register box with the warm-air passage completely
surrounded by the cold-air passage, shall be permitted in lieu
of the clearances listed in Sentences (2), (3) and (4).
1) Warm-air supply systems for residential buildings built on concrete slabs-on-ground shall be installed in or beneath the slab and
shall be of the perimeter loop type or radial perimeter type.
1) All branch supply ducts that are not fitted with diffusers with
adjustable balance stops shall be supplied with adjustable
dampers and fitted with devices to indicate the positions of the
dampers.
1) Supply outlets and return openings in the dwelling unit, when located less than 2 m above the floor, shall be protected by grilles
having openings of a size that will not allow the passage of a
15 mm diam sphere.
2) Combustible grilles, diffusers and other devices for the supply and return air
openings installed in walls and ceilings shall have a flame-spread rating of
a)not more than 200 in bathrooms, and
b)not more than 150 in rooms or spaces other than bathrooms.
1) In a dwelling unit, a warm-air supply outlet shall be provided in each
finished room that is located adjacent to unheated space.
2) Except as provided in Sentence (3), when a room described in Sentence (1) is located adjacent to exterior walls, such outlet shall be
located so as to bathe at least one exterior wall or window with
warm air, except in bathrooms, utility rooms or kitchens, where
this may not be practical.
3) Where the heating system is also designed to provide
ventilation air, ceiling outlets or outlets located high on
interior walls are permitted to be installed, provided the
outlets are designed for this purpose and are installed with
diffusers.
4) At least one warm-air supply outlet shall be provided
for each 40 m2 of floor surface area in unfinished
basements serving dwelling units, and it shall be located so as to provide adequate distribution of warm
air throughout the basement.
5) At least one warm-air supply outlet shall be provided
for each 80 m2 of floor surface area in heated crawl
spaces serving dwelling units, and it shall be located so as to provide adequate
distribution of warm air throughout the crawl space.
6) Except for pipeless furnaces, the capacity of warm-air supply outlets serving dwelling units shall be not less than the design heat loss from the area served
and shall not exceed 3 kW per outlet.
7) In basements and heated crawl spaces, the calculated heat gain from the supply ducts and plenum surfaces is permitted to be considered in calculating the design heat loss.
8) The temperature of supply air at warm-air supply
outlets shall not exceed 70°C.
9) Warm-air supply outlets located in finished areas
shall be provided with diffusers and adjustable openings and
shall not be located on a furnace plenum.
1) Return-air inlets shall not be installed in an
enclosed room or crawl space that provides combustion air to a
furnace.
2) Except for unfinished areas and floor levels which are
less than 900 mm above or below an adjacent floor level which is
provided with a return-air inlet, at least one return-air inlet
shall be provided in each floor level in a dwelling unit.
3) Provision shall be made for the return of air from all
rooms by leaving gaps beneath doors, using louvred doors or
installing return duct inlets.
1) The return-air system shall be designed to handle the
entire air supply.
2) Where any part of a return duct will be exposed to radiation from the furnace heat exchanger or other radiating part within the furnace, such part of a return duct directly above or within 600 mm of the outside furnace casing shall be noncombustible.
3) Return ducts serving solid-fuel-burning furnaces shall be constructed of noncombustible material.
4) Combustible return ducts shall be lined with noncombustible material
a)below floor registers,
b)at the bottom of vertical ducts, and
c)under furnaces having a bottom return.
5) Spaces between studs or joists used
as return ducts shall be separated from the unused portions of such spaces by
tight-fitting metal stops or wood blocking.
6) A vertical return duct shall have openings to return air on not more
than one floor.
7) The return-air system shall be designed so that the
negative pressure from the circulating fan cannot
a)affect the furnace combustion air supply, nor
b)draw combustion products from joints or openings in the furnace or flue pipe.
1) Air filters for air duct systems shall conform to the
requirements for Class 2 air filter units as described in ULC-S111, “Fire
Tests for Air
Filter Units.”
2) When electrostatic-type filters are used, they shall
be installed so as to ensure that the electric circuit is
automatically de-energized when filter access doors are opened
or, in dwelling units, when the furnace circulation fan is not operating.
3) When odour removal equipment of the adsorption type is
used it shall be
a)installed to provide access so that adsorption material can be reactivated or renewed, and
b)protected from dust accumulation by air filters installed on the inlet side.
1) Every steam or hot water radiator and convector
located in a recess or concealed space or attached to the face
of a wall of combustible construction shall be provided with a noncombustible lining or backing.
1) The exposed surface temperature of a steam or hot
water radiator shall not exceed 70°C unless precautions
are taken to prevent human contact.
1) Piping shall be made from materials designed to
withstand the effects of temperatures and pressures that may
occur in the system. (See Articles 3.1.5.16., 3.1.9.1. and 9.10.9.6. for fire safety requirements.)
2) Every pipe used in a heating or air-conditioning
system shall be installed to allow for expansion and contraction
due to temperature changes.
3) Supports and anchors for piping in a heating or
air-conditioning system shall be designed and installed to
ensure that undue stress is not placed on the supporting
structure.
1) Insulation and coverings on pipes shall be composed of
material suitable for the operating temperature of the system to
withstand deterioration from softening, melting, mildew and
mould.
2) Insulation and coverings on pipes in which the
temperature of the fluid exceeds 120°C
a)shall be made of noncombustible material, or
b)shall not flame, glow, smoulder or smoke when tested in accordance with ASTM C 411, “Hot-Surface Performance of High-Temperature Thermal Insulation,” at the maximum temperature to which such insulation or covering is to be exposed in service.
3) Except as provided in Sentence (6), where combustible insulation is used on piping in a horizontal or vertical service space, the insulation and coverings on such pipes shall have a flame-spread rating throughout the material of not more than
a)25 in buildings of noncombustible construction, and
b)75 in buildings of combustible construction.
4) Except as provided in Sentence (6), insulation and coverings on piping located in rooms and spaces
other than the service spaces described in Sentence (3) shall have a flame-spread rating not more than that required for the interior finish
for the ceiling of the room or space.
5) Pipes that are exposed to human contact shall be
insulated so that the exposed surface does not exceed
70°C. (See A-6.2.9.2.(2) in Appendix A.)
6) No flame-spread rating or smoke developed classification limitations are
required where combustible insulation and coverings are used on piping when such piping is
a)located within a concealed space in a wall,
b)located in a floor slab, or
c)enclosed in a noncombustible raceway or conduit.
1) Clearances between combustible material and bare pipes carrying steam or hot water shall conform to Table 9.33.8.3.
Table 9.33.8.3. Clearance between Steam or Hot Water Pipes and Combustible Material Forming Part of Sentence 9.33.8.3.(1) |
|
Steam or Water Temperature (T), °C | Minimum Clearance, mm |
---|---|
T ≤ 95 | no clearance required |
95 < T ≤ 120 | 15 |
T > 120 | 25 |
1) Where a pipe carrying steam or hot water at a
temperature above 120°C passes through a combustible floor, ceiling or wall, the construction shall be protected by a sleeve
of metal or other noncombustible material not less than 50 mm larger in diameter than the pipe.
2) Unprotected steam or hot water pipes that pass through
a storage space shall be covered with not less than 25 mm
thickness of noncombustible insulation to prevent direct contact with the material stored.
1) Where a cooling unit is combined with a fuel-fired
furnace in the same duct system, the cooling unit shall be installed
a)in parallel with the heating furnace,
b)upstream of the furnace, provided the furnace is designed for such application, or
c)downstream of the furnace, provided the cooling unit is designed to prevent excessive temperature or pressure in the refrigeration system.
1) Except as provided in Articles 9.33.10.2. and 9.33.10.3., the products of combustion from oil-, gas- and solid-fuel-burning appliances, including stoves, ranges and space heaters, shall be vented in conformance with the
applicable appliance installation standard and regulations listed in Sentences 9.33.5.2.(1) and 9.33.5.3.(1).
1) Factory-built chimneys serving solid-fuel-burning appliances, and their installation, shall conform to CAN/ULC-S629-M,
“650°C Factory-Built Chimneys.” (See
Appendix A.)
1) Masonry or concrete chimneys shall conform to Section 9.21.