1) Smoke alarms shall be inspected, tested and maintained in conformance with CAN/ULC-S552,
“Maintenance and Testing of Smoke Alarms.”
2) A record shall be kept of all testing of smoke alarms installed in hotels and motels and shall be retained in conformance with Article 2.2.1.2. of DivisionC.
3) Carbon monoxide detectors shall be inspected,
tested and maintained in conformance with the manufacturer's
instructions.