1) Except as permitted in Sentence (2), covered malls designed for ornamental and pedestrian oriented uses only
shall not be used for merchandising or public
activities.
2) A covered mall referred to in Sentence (1) is permitted to be used for merchandising or public activities on a
temporary basis provided
a)it conforms to Articles 2.12.1.2. to 2.12.1.9., and
b)the fire safety plan required in Section 2.8 includes additional provisions to offset any hazard that may be created by such activity.
1) Merchandising or public activities in a sprinklered covered mall described in Article 2.12.1.1. shall not be permitted where such activity
will create a hazard exceeding the design criteria for which the
sprinkler system was designed.
1) When a covered mall having a width of not less than 9
m has been provided for the purpose of considering each portion
of the building separated by the mall as a separate building, merchandising or public activities are permitted within the required 9 m width
provided alternative protection is installed in conformance with
Article 1.2.1.1. of Division A.
1) Access to exits within a covered mall shall be provided and maintained in conformance with Subsection 2.7.1.
1) Where a covered mall is used for merchandising or
public activities, the activity shall be arranged so that access
to fire protection equipment, including sprinkler control
valves, fire hose stations, portable extinguishers and fire
alarm stations, is not restricted.
1) Decorative materials used for merchandising or public
activities in a covered mall shall conform to Subsection 2.3.2.
1) Flammable liquids, combustible liquids and Class 2.1 flammable gases shall not be used or displayed in a covered mall.
1) Where a covered mall is used for the display of
fuelled equipment, batteries shall be disconnected and caps for
fuel tanks shall be locked or secured against
tampering.
1) A propane fuelled automotive vehicle shall not be
displayed in a covered mall unless
a)the propane fuel tank is permanently installed,
b)the fuel system is equipped with an automatic stop-fill valve,
c)the fuel cut-off valve is closed,
d)fuel tank filling connections are locked or secured against tampering, and
e)batteries are disconnected.