Attribution Tables of Division B 6.4.1.1.
Table 6.4.1.1. Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6 Forming part of Sentence 6.4.1.1.(1) | |
Acceptable Solutions | Functional Statements and Objectives(1) |
6.2.1.1. Good Engineering Practice | |
(1) | (a) to (e) [F31,F51-OP1.1] |
(a) to (c) and (e) to (i) [F40,F50,F51,F52,F54,F63-OH1.1] | |
(a),(b),(c),(e),(f),(g),(h) [F50,F51,F52,F54,F63-OH1.2,OH1.3] | |
[F50,F31,F63,F51,F54,F52-OS3.2,OS3.4] | |
(d) [F01-OS1.1] | |
6.2.1.3. Structural Movement | |
(1) | [F23-OS3.1] |
[F51,F63,F50-OH1.1,OH1.2,OH1.3] | |
6.2.1.4. Installation Standards | |
(1) | [F43-OS1.1] |
[F43-OS3.4] | |
[F43-OP1.1] | |
6.2.1.8. Installation – General | |
(1) | [F82-OS1.1] |
[F82-OS3.4] | |
[F82-OP1.1] | |
(2) | [F31-OS3.1] |
(3) | [F81-OS3.2,OS3.3,OS3.4] |
[F81-OS1.1] | |
6.2.1.9. Expansion, Contraction and System Pressure | |
(1) | [F20-OS3.2] |
6.2.1.10. Asbestos | |
(1) | [F43-OH1.1] |
6.2.1.11. Access Openings | |
(1) | [F36-OS3.6] |
6.2.2.1. Required Ventilation | |
(1) | [F50,F31,F63,F51,F54,F52-OS1.1] |
[F50,F31,F63,F51,F54,F52-OP1.1] | |
(2) | [F50-OH1.1] |
![]() |
[F50-OH1.1]![]() |
6.2.2.2. Natural Ventilation | |
(1) | [F50-OH1.1] |
(2) | [F50-OH1.1] |
6.2.2.3. Ventilation of Storage Garages | |
(1) | [F50,F44-OS3.4] |
(2) | [F44-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F50,F44-OS3.4] |
(5) | [F50,F44-OH1.1] |
[F50,F44-OS3.4] | |
6.2.2.4. Cleaning Devices | |
(1) | [F40,F43,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.2.5. Air Contaminants | |
(1) | [F44-OS3.4] |
[F44-OH1.1] | |
(2) | [F44-OH1.1] |
(3) | [F52-OH1.1] |
6.2.2.6. Hazardous Gases, Dusts or Liquids | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.2.7. Commercial Cooking Equipment | |
(1) | [F01,F44-OS1.1] |
[F01,F44-OP1.1] | |
(2) | [F02,F81-OS1.2] |
[F02,F81-OP1.2] | |
![]() |
[F40, F50-OH5] |
(4) | [F40, F50-OH5]![]() |
6.2.2.8. Crawl Spaces and Attic or Roof Spaces | |
(1) | [F61,F63,F41-OH1.1,OH1.3] |
6.2.3.2. Materials in Air Duct Systems | |
(2) | [F20,F80-OH1.1,OH1.2] |
(3) | [F81,F44-OS3.4] |
[F81-OH1.1] | |
(4) | [F20,F80-OH1.1,OH1.2] |
6.2.3.3. Connections and Openings in Air Duct Systems | |
(1) | [F81-OH1.1,OH1.2] |
[F81,F44-OS3.4] | |
(2) | [F82-OS1.1] |
6.2.3.4. Duct Coverings and Linings | |
(3) | [F81-OH1.1,OH1.2] |
[F81-OS1.1] | |
[F81-OP1.1] | |
6.2.3.5. Underground Ducts | |
(1) | (a) [F44,F81-OH1.2,OH1.3] |
(b) [F44,F81-OH1.1] | |
(c) [F44,F81-OH1.1] | |
(2) | [F81-OH1.1,OH1.2,OH1.3] |
6.2.3.8. Exhaust Ducts and Outlets | |
(1) | [F44-OH1.1] |
(2) | [F44-OH1.1] |
(3) | [F81-OH1.1] |
[F81-OH1.2] | |
(4) | [F81-OH1.1] |
[F81-OH1.2] | |
(5) | [F81-OH1.1] |
(6) | [F81-OH1.1] |
(7) | [F81-OS1.1] |
(8) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(9) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(10) | [F81-OH1.1] |
(11) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
(12) | [F81,F44-OH1.1] |
(13) | [F81-OH1.2] |
[F81,F44-OH1.1] | |
6.2.3.9. Interconnection of Systems | |
(1) | [F44-OS1.1] |
[F40-OH1.1] | |
(2) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
[F81,F44-OP1.1] | |
(3) | [F81,F44-OH1.1] |
6.2.3.11. Makeup Air | |
(1) | [F50,F81-OH1.1] |
[F44,F81-OS3.4] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.2] |
6.2.3.12. Supply, Return, Intake and Exhaust Air Openings | |
(1) | [F30-OS3.1] |
[F81-OH1.2] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.1] |
(4) | [F82,F81-OH1.1] |
[F82-OS3.4] | |
6.2.3.13. Filters and Odour Removal Equipment | |
(1) | [F80-OS1.1] |
[F80-OP1.1] | |
(2) | [F30-OS3.3] |
[F81,F43-OH1.1] | |
(3) | [F82-OH1.1] |
(4) | [F82-OH1.1] |
6.2.3.14. Air Washers and Evaporative Cooling Sections or Towers | |
(1) | [F80,F81-OS1.1] |
[F80,F81-OP1.1] | |
(2) | [F82-OH1.1] |
(3) | [F01,F81-OS1.1] |
6.2.3.15. Fans and Associated Air-Handling Equipment | |
(1) | [F81,F44-OH1.1] |
[F81,F44-OS3.4] | |
(2) | [F81-OH1.1] |
6.2.3.20. Return-Air System | |
(3) | [F10-OS1.5] |
6.2.4.1. Carbon Monoxide Alarms | |
(2) | (a),(b),(d) [F44-OS3.4] (c) [F81-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F44-OS3.4] |
(5) | [F44-OS3.4] |
6.2.5.2. Appliances Installed Outside the Building | |
(1) | [F81-OP1.1] |
[F81-OH1.1] | |
[F81-OS1.1] | |
6.2.6.1. Applicable Standard | |
(1) | [F81-OS1.1] |
6.2.7.1. Clearances | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
6.2.8.1. Lining or Backing | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
6.2.9.1. Piping Materials and Installation | |
(1) | [F20-OS3.2,OS3.4] |
(2) | [F21-OH1.1] |
(3) | [F20-OS2.2] |
6.2.9.2. Insulation and Coverings | |
(1) | [F20,F30-OS3.2,OS3.4] |
(2) | [F31-OS3.2] |
6.2.9.3. Clearances | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.9.4. Surface Temperature | |
(1) | [F31-OS3.2] |
6.2.9.5. Protection | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.10.1. Cooling Units | |
(1) | [F43,F81-OS3.4] |
6.2.11.1. Storage Bins | |
(1) | [F30,F31,F43-OS3.2,OS3.4] |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
(3) | [F30-OH2.1] |
(4) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.11.2. Ash Storage Bins | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.12.2. General Ventilation | |
(1) | (a),(b),(d),(e) [F01-OS1.1] |
(c) [F02-OP1.2] | |
(c) [F02-OS1.2] [F81,F82-OS1.1] | |
(2) | [F81,F11-OS1.1] |
6.2.12.3. Enclosure Exhaust Ventilation | |
(1) | (a),(c),(d) [F01-OS1.1] |
(b) [F02-OP1.2] | |
(e) [F12-OP1.1,OP1.2] | |
(a) [F02-OP1.2] | |
(b) [F02-OS1.2] [F81-OS1.1] | |
(e) [F12-OS1.1,OS1.2] | |
(a) [F02-OS1.2] | |
(a) [F01-OS1.1] | |
6.2.12.4. Enclosure Construction | |
(1) | (a) [F02-OS1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” |
(b) [F02-OP1.2] | |
(a) [F02-OP1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” | |
(a) [F80-OS3.4] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(b) [F02-OS1.2] [F82-OS1.1] | |
(a) [F80-OS1.1] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(a) [F01-OS1.1] Applies to portion of Code text: “… be constructed of … materials compatible with … the dangerous goods vapours and particles being exhausted …” | |
(3) | [F02-OS1.2] |
[F02-OP1.2] | |
6.3.1.2. Masonry or Concrete Chimneys | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.3. Metal Smoke Stacks | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.4. Lightning Protection Systems | |
(1) | [F01,F81-OS1.1] |
[F01,F81-OP1.1] | |
6.3.1.5. Access Ladders | |
(1) | [F20,F80-OS3.1] |
(2) | [F30-OS3.1] |
VC2014 2017-05-01 R7VC2014 2015-01-01 R1BC2012 2017-04-07 R11BC2012 2014-12-19 R7BC2012 2014-12-19 R6NC2010 2010-01-01 R1
Table 6.4.1.1. Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6 Forming part of Sentence 6.4.1.1.(1) |
|
Acceptable Solutions | Functional Statements and Objectives(1) |
6.2.1.1. Good Engineering Practice | |
(1) | (a) to (e) [F31,F51-OP1.1] |
(a) to (c) and (e) to (i) [F40,F50,F51,F52,F54,F63-OH1.1] | |
(a),(b),(c),(e),(f),(g),(h) [F50,F51,F52,F54,F63-OH1.2,OH1.3] | |
[F50,F31,F63,F51,F54,F52-OS3.2,OS3.4] | |
(d) [F01-OS1.1] | |
6.2.1.3. Structural Movement | |
(1) | [F23-OS3.1] |
[F51,F63,F50-OH1.1,OH1.2,OH1.3] | |
6.2.1.4. Installation Standards | |
(1) | [F43-OS1.1] |
[F43-OS3.4] | |
[F43-OP1.1] | |
6.2.1.8. Installation – General | |
(1) | [F82-OS1.1] |
[F82-OS3.4] | |
[F82-OP1.1] | |
(2) | [F31-OS3.1] |
(3) | [F81-OS3.2,OS3.3,OS3.4] |
[F81-OS1.1] | |
6.2.1.9. Expansion, Contraction and System Pressure | |
(1) | [F20-OS3.2] |
6.2.1.10. Asbestos | |
(1) | [F43-OH1.1] |
6.2.1.11. Access Openings | |
(1) | [F36-OS3.6] |
6.2.2.1. Required Ventilation | |
(1) | [F50,F31,F63,F51,F54,F52-OS1.1] |
[F50,F31,F63,F51,F54,F52-OP1.1] | |
(2) | [F50-OH1.1] |
(4) | [F50-OH1.1] |
6.2.2.2. Natural Ventilation | |
(1) | [F50-OH1.1] |
(2) | [F50-OH1.1] |
6.2.2.3. Ventilation of Storage Garages | |
(1) | [F50,F44-OS3.4] |
(2) | [F44-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F50,F44-OS3.4] |
(5) | [F50,F44-OH1.1] |
[F50,F44-OS3.4] | |
6.2.2.4. Cleaning Devices | |
(1) | [F40,F43,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.2.5. Air Contaminants | |
(1) | [F44-OS3.4] |
[F44-OH1.1] | |
(2) | [F44-OH1.1] |
(3) | [F52-OH1.1] |
6.2.2.6. Hazardous Gases, Dusts or Liquids | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.2.7. Commercial Cooking Equipment | |
(1) | [F01,F44-OS1.1] |
[F01,F44-OP1.1] | |
(2) | [F02,F81-OS1.2] |
[F02,F81-OP1.2] | |
(3) | [F40, F50-OH5] |
(4) | [F40, F50-OH5] |
6.2.2.8. Crawl Spaces and Attic or Roof Spaces | |
(1) | [F61,F63,F41-OH1.1,OH1.3] |
6.2.3.2. Materials in Air Duct Systems | |
(2) | [F20,F80-OH1.1,OH1.2] |
(3) | [F81,F44-OS3.4] |
[F81-OH1.1] | |
(4) | [F20,F80-OH1.1,OH1.2] |
6.2.3.3. Connections and Openings in Air Duct Systems | |
(1) | [F81-OH1.1,OH1.2] |
[F81,F44-OS3.4] | |
(2) | [F82-OS1.1] |
6.2.3.4. Duct Coverings and Linings | |
(3) | [F81-OH1.1,OH1.2] |
[F81-OS1.1] | |
[F81-OP1.1] | |
6.2.3.5. Underground Ducts | |
(1) | (a) [F44,F81-OH1.2,OH1.3] |
(b) [F44,F81-OH1.1] | |
(c) [F44,F81-OH1.1] | |
(2) | [F81-OH1.1,OH1.2,OH1.3] |
6.2.3.8. Exhaust Ducts and Outlets | |
(1) | [F44-OH1.1] |
(2) | [F44-OH1.1] |
(3) | [F81-OH1.1] |
[F81-OH1.2] | |
(4) | [F81-OH1.1] |
[F81-OH1.2] | |
(5) | [F81-OH1.1] |
(6) | [F81-OH1.1] |
(7) | [F81-OS1.1] |
(8) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(9) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(10) | [F81-OH1.1] |
(11) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
(12) | [F81,F44-OH1.1] |
(13) | [F81-OH1.2] |
[F81,F44-OH1.1] | |
6.2.3.9. Interconnection of Systems | |
(1) | [F44-OS1.1] |
[F40-OH1.1] | |
(2) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
[F81,F44-OP1.1] | |
(3) | [F81,F44-OH1.1] |
6.2.3.11. Makeup Air | |
(1) | [F50,F81-OH1.1] |
[F44,F81-OS3.4] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.2] |
6.2.3.12. Supply, Return, Intake and Exhaust Air Openings | |
(1) | [F30-OS3.1] |
[F81-OH1.2] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.1] |
(4) | [F82,F81-OH1.1] |
[F82-OS3.4] | |
6.2.3.13. Filters and Odour Removal Equipment | |
(1) | [F80-OS1.1] |
[F80-OP1.1] | |
(2) | [F30-OS3.3] |
[F81,F43-OH1.1] | |
(3) | [F82-OH1.1] |
(4) | [F82-OH1.1] |
6.2.3.14. Air Washers and Evaporative Cooling Sections or Towers | |
(1) | [F80,F81-OS1.1] |
[F80,F81-OP1.1] | |
(2) | [F82-OH1.1] |
(3) | [F01,F81-OS1.1] |
6.2.3.15. Fans and Associated Air-Handling Equipment | |
(1) | [F81,F44-OH1.1] |
[F81,F44-OS3.4] | |
(2) | [F81-OH1.1] |
6.2.3.20. Return-Air System | |
(3) | [F10-OS1.5] |
6.2.4.1. Carbon Monoxide Alarms | |
(2) | (a),(b),(d) [F44-OS3.4] (c) [F81-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F44-OS3.4] |
(5) | [F44-OS3.4] |
6.2.5.2. Appliances Installed Outside the Building | |
(1) | [F81-OP1.1] |
[F81-OH1.1] | |
[F81-OS1.1] | |
6.2.6.1. Applicable Standard | |
(1) | [F81-OS1.1] |
6.2.7.1. Clearances | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
6.2.8.1. Lining or Backing | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
6.2.9.1. Piping Materials and Installation | |
(1) | [F20-OS3.2,OS3.4] |
(2) | [F21-OH1.1] |
(3) | [F20-OS2.2] |
6.2.9.2. Insulation and Coverings | |
(1) | [F20,F30-OS3.2,OS3.4] |
(2) | [F31-OS3.2] |
6.2.9.3. Clearances | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.9.4. Surface Temperature | |
(1) | [F31-OS3.2] |
6.2.9.5. Protection | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.10.1. Cooling Units | |
(1) | [F43,F81-OS3.4] |
6.2.11.1. Storage Bins | |
(1) | [F30,F31,F43-OS3.2,OS3.4] |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
(3) | [F30-OH2.1] |
(4) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.11.2. Ash Storage Bins | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.12.2. General Ventilation | |
(1) | (a),(b),(d),(e) [F01-OS1.1] |
(c) [F02-OP1.2] | |
(c) [F02-OS1.2] [F81,F82-OS1.1] | |
(2) | [F81,F11-OS1.1] |
6.2.12.3. Enclosure Exhaust Ventilation | |
(1) | (a),(c),(d) [F01-OS1.1] |
(b) [F02-OP1.2] | |
(e) [F12-OP1.1,OP1.2] | |
(a) [F02-OP1.2] | |
(b) [F02-OS1.2] [F81-OS1.1] | |
(e) [F12-OS1.1,OS1.2] | |
(a) [F02-OS1.2] | |
(a) [F01-OS1.1] | |
6.2.12.4. Enclosure Construction | |
(1) | (a) [F02-OS1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” |
(b) [F02-OP1.2] | |
(a) [F02-OP1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” | |
(a) [F80-OS3.4] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(b) [F02-OS1.2] [F82-OS1.1] | |
(a) [F80-OS1.1] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(a) [F01-OS1.1] Applies to portion of Code text: “… be constructed of … materials compatible with … the dangerous goods vapours and particles being exhausted …” | |
(3) | [F02-OS1.2] |
[F02-OP1.2] | |
6.3.1.2. Masonry or Concrete Chimneys | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.3. Metal Smoke Stacks | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.4. Lightning Protection Systems | |
(1) | [F01,F81-OS1.1] |
[F01,F81-OP1.1] | |
6.3.1.5. Access Ladders | |
(1) | [F20,F80-OS3.1] |
(2) | [F30-OS3.1] |
Table 6.4.1.1. Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6 Forming part of Sentence 6.4.1.1.(1) |
|
Acceptable Solutions | Functional Statements and Objectives(1) |
6.2.1.1. Good Engineering Practice | |
(1) | (a) to (e) [F31,F51-OP1.1] |
(a) to (c) and (e) to (i) [F40,F50,F51,F52,F54,F63-OH1.1] | |
(a),(b),(c),(e),(f),(g),(h) [F50,F51,F52,F54,F63-OH1.2,OH1.3] | |
[F50,F31,F63,F51,F54,F52-OS3.2,OS3.4] | |
(d) [F01-OS1.1] | |
6.2.1.3. Structural Movement | |
(1) | [F23-OS3.1] |
[F51,F63,F50-OH1.1,OH1.2,OH1.3] | |
6.2.1.4. Installation Standards | |
(1) | [F43-OS1.1] |
[F43-OS3.4] | |
[F43-OP1.1] | |
6.2.1.7. Outdoor Design Conditions | |
(2) | [F40,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.1.8. Installation – General | |
(1) | [F82-OS1.1] |
[F82-OS3.4] | |
[F82-OP1.1] | |
(2) | [F31-OS3.1] |
(3) | [F81-OS3.2,OS3.3,OS3.4] |
[F81-OS1.1] | |
6.2.1.9. Expansion, Contraction and System Pressure | |
(1) | [F20-OS3.2] |
6.2.1.10. Asbestos | |
(1) | [F43-OH1.1] |
6.2.1.11. Access Openings | |
(1) | [F36-OS3.6] |
6.2.2.1. Required Ventilation | |
(1) | [F50,F31,F63,F51,F54,F52-OS1.1] |
[F50,F31,F63,F51,F54,F52-OP1.1] | |
(2) | [F50-OH1.1] |
(4) | [F50-OH1.1] |
6.2.2.2. Natural Ventilation | |
(1) | [F50-OH1.1] |
(2) | [F50-OH1.1] |
6.2.2.3. Ventilation of Storage Garages | |
(1) | [F50,F44-OS3.4] |
(2) | [F44-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F50,F44-OS3.4] |
(5) | [F50,F44-OH1.1] |
[F50,F44-OS3.4] | |
6.2.2.4. Cleaning Devices | |
(1) | [F40,F43,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.2.5. Air Contaminants | |
(1) | [F44-OS3.4] |
[F44-OH1.1] | |
(2) | [F44-OH1.1] |
(3) | [F52-OH1.1] |
6.2.2.6. Hazardous Gases, Dusts or Liquids | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.2.7. Commercial Cooking Equipment | |
(1) | [F01,F44-OS1.1] |
[F01,F44-OP1.1] | |
(2) | [F02,F81-OS1.2] |
[F02,F81-OP1.2] | |
(3) | [F40, F50-OH5] |
(4) | [F40, F50-OH5] |
6.2.2.8. Crawl Spaces and Attic or Roof Spaces | |
(1) | [F61,F63,F41-OH1.1,OH1.3] |
6.2.3.2. Materials in Air Duct Systems | |
(2) | [F20,F80-OH1.1,OH1.2] |
(3) | [F81,F44-OS3.4] |
[F81-OH1.1] | |
(4) | [F20,F80-OH1.1,OH1.2] |
6.2.3.3. Connections and Openings in Air Duct Systems | |
(1) | [F81-OH1.1,OH1.2] |
[F81,F44-OS3.4] | |
(2) | [F82-OS1.1] |
6.2.3.4. Duct Coverings and Linings | |
(3) | [F81-OH1.1,OH1.2] |
[F81-OS1.1] | |
[F81-OP1.1] | |
6.2.3.5. Underground Ducts | |
(1) | (a) [F44,F81-OH1.2,OH1.3] |
(b) [F44,F81-OH1.1] | |
(c) [F44,F81-OH1.1] | |
(2) | [F81-OH1.1,OH1.2,OH1.3] |
6.2.3.8. Exhaust Ducts and Outlets | |
(1) | [F44-OH1.1] |
(2) | [F44-OH1.1] |
(3) | [F81-OH1.1] |
[F81-OH1.2] | |
(4) | [F81-OH1.1] |
[F81-OH1.2] | |
(5) | [F81-OH1.1] |
(6) | [F81-OH1.1] |
(7) | [F81-OS1.1] |
(8) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(9) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(10) | [F81-OH1.1] |
(11) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
(12) | [F81,F44-OH1.1] |
(13) | [F81-OH1.2] |
[F81,F44-OH1.1] | |
6.2.3.9. Interconnection of Systems | |
(1) | [F44-OS1.1] |
[F40-OH1.1] | |
(2) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
[F81,F44-OP1.1] | |
(3) | [F81,F44-OH1.1] |
6.2.3.11. Makeup Air | |
(1) | [F50,F81-OH1.1] |
[F44,F81-OS3.4] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.2] |
6.2.3.12. Supply, Return, Intake and Exhaust Air Openings | |
(1) | [F30-OS3.1] |
[F81-OH1.2] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.1] |
(4) | [F82,F81-OH1.1] |
[F82-OS3.4] | |
6.2.3.13. Filters and Odour Removal Equipment | |
(1) | [F80-OS1.1] |
[F80-OP1.1] | |
(2) | [F30-OS3.3] |
[F81,F43-OH1.1] | |
(3) | [F82-OH1.1] |
(4) | [F82-OH1.1] |
6.2.3.14. Air Washers and Evaporative Cooling Sections or Towers | |
(1) | [F80,F81-OS1.1] |
[F80,F81-OP1.1] | |
(2) | [F82-OH1.1] |
(3) | [F01,F81-OS1.1] |
6.2.3.15. Fans and Associated Air-Handling Equipment | |
(1) | [F81,F44-OH1.1] |
[F81,F44-OS3.4] | |
(2) | [F81-OH1.1] |
6.2.3.20. Return-Air System | |
(3) | [F10-OS1.5] |
6.2.4.1. Carbon Monoxide Alarms | |
(2) | (a),(b),(d) [F44-OS3.4] (c) [F81-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F44-OS3.4] |
(5) | [F44-OS3.4] |
6.2.5.2. Appliances Installed Outside the Building | |
(1) | [F81-OP1.1] |
[F81-OH1.1] | |
[F81-OS1.1] | |
6.2.6.1. Applicable Standard | |
(1) | [F81-OS1.1] |
6.2.7.1. Clearances | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
6.2.8.1. Lining or Backing | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
6.2.9.1. Piping Materials and Installation | |
(1) | [F20-OS3.2,OS3.4] |
(2) | [F21-OH1.1] |
(3) | [F20-OS2.2] |
6.2.9.2. Insulation and Coverings | |
(1) | [F20,F30-OS3.2,OS3.4] |
(2) | [F31-OS3.2] |
6.2.9.3. Clearances | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.9.4. Surface Temperature | |
(1) | [F31-OS3.2] |
6.2.9.5. Protection | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.10.1. Cooling Units | |
(1) | [F43,F81-OS3.4] |
6.2.11.1. Storage Bins | |
(1) | [F30,F31,F43-OS3.2,OS3.4] |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
(3) | [F30-OH2.1] |
(4) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.11.2. Ash Storage Bins | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.12.2. General Ventilation | |
(1) | (a),(b),(d),(e) [F01-OS1.1] |
(c) [F02-OP1.2] | |
(c) [F02-OS1.2] [F81,F82-OS1.1] | |
(2) | [F81,F11-OS1.1] |
6.2.12.3. Enclosure Exhaust Ventilation | |
(1) | (a),(c),(d) [F01-OS1.1] |
(b) [F02-OP1.2] | |
(e) [F12-OP1.1,OP1.2] | |
(a) [F02-OP1.2] | |
(b) [F02-OS1.2] [F81-OS1.1] | |
(e) [F12-OS1.1,OS1.2] | |
(a) [F02-OS1.2] | |
(a) [F01-OS1.1] | |
6.2.12.4. Enclosure Construction | |
(1) | (a) [F02-OS1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” |
(b) [F02-OP1.2] | |
(a) [F02-OP1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” | |
(a) [F80-OS3.4] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(b) [F02-OS1.2] [F82-OS1.1] | |
(a) [F80-OS1.1] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(a) [F01-OS1.1] Applies to portion of Code text: “… be constructed of … materials compatible with … the dangerous goods vapours and particles being exhausted …” | |
(3) | [F02-OS1.2] |
[F02-OP1.2] | |
6.3.1.2. Masonry or Concrete Chimneys | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.3. Metal Smoke Stacks | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.4. Lightning Protection Systems | |
(1) | [F01,F81-OS1.1] |
[F01,F81-OP1.1] | |
6.3.1.5. Access Ladders | |
(1) | [F20,F80-OS3.1] |
(2) | [F30-OS3.1] |
Table 6.4.1.1. Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6 Forming part of Sentence 6.4.1.1.(1) |
|
Acceptable Solutions | Functional Statements and Objectives(1) |
6.2.1.1. Good Engineering Practice | |
(1) | (a) to (e) [F31,F51-OP1.1] |
(a) to (c) and (e) to (i) [F40,F50,F51,F52,F54,F63-OH1.1] | |
(a),(b),(c),(e),(f),(g),(h) [F50,F51,F52,F54,F63-OH1.2,OH1.3] | |
[F50,F31,F63,F51,F54,F52-OS3.2,OS3.4] | |
(d) [F01-OS1.1] | |
6.2.1.3. Structural Movement | |
(1) | [F23-OS3.1] |
[F51,F63,F50-OH1.1,OH1.2,OH1.3] | |
6.2.1.4. Installation Standards | |
(1) | [F43-OS1.1] |
[F43-OS3.4] | |
[F43-OP1.1] | |
(2) | [F40,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.1.8. Installation – General | |
(1) | [F82-OS1.1] |
[F82-OS3.4] | |
[F82-OP1.1] | |
(2) | [F31-OS3.1] |
(3) | [F81-OS3.2,OS3.3,OS3.4] |
[F81-OS1.1] | |
6.2.1.9. Expansion, Contraction and System Pressure | |
(1) | [F20-OS3.2] |
6.2.1.10. Asbestos | |
(1) | [F43-OH1.1] |
6.2.1.11. Access Openings | |
(1) | [F36-OS3.6] |
6.2.2.1. Required Ventilation | |
(1) | [F50,F31,F63,F51,F54,F52-OS1.1] |
[F50,F31,F63,F51,F54,F52-OP1.1] | |
(2) | [F50-OH1.1] |
(4) | [F50-OH1.1] |
6.2.2.2. Natural Ventilation | |
(1) | [F50-OH1.1] |
(2) | [F50-OH1.1] |
6.2.2.3. Ventilation of Storage Garages | |
(1) | [F50,F44-OS3.4] |
(2) | [F44-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F50,F44-OS3.4] |
(5) | [F50,F44-OH1.1] |
[F50,F44-OS3.4] | |
6.2.2.4. Cleaning Devices | |
(1) | [F40,F43,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.2.5. Air Contaminants | |
(1) | [F44-OS3.4] |
[F44-OH1.1] | |
(2) | [F44-OH1.1] |
(3) | [F52-OH1.1] |
6.2.2.6. Hazardous Gases, Dusts or Liquids | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.2.7. Commercial Cooking Equipment | |
(1) | [F01,F44-OS1.1] |
[F01,F44-OP1.1] | |
(2) | [F02,F81-OS1.2] |
[F02,F81-OP1.2] | |
(3) | [F40, F50-OH5] |
(4) | [F40, F50-OH5] |
6.2.2.8. Crawl Spaces and Attic or Roof Spaces | |
(1) | [F61,F63,F41-OH1.1,OH1.3] |
6.2.3.2. Materials in Air Duct Systems | |
(2) | [F20,F80-OH1.1,OH1.2] |
(3) | [F81,F44-OS3.4] |
[F81-OH1.1] | |
(4) | [F20,F80-OH1.1,OH1.2] |
6.2.3.3. Connections and Openings in Air Duct Systems | |
(1) | [F81-OH1.1,OH1.2] |
[F81,F44-OS3.4] | |
(2) | [F82-OS1.1] |
6.2.3.4. Duct Coverings and Linings | |
(3) | [F81-OH1.1,OH1.2] |
[F81-OS1.1] | |
[F81-OP1.1] | |
6.2.3.5. Underground Ducts | |
(1) | (a) [F44,F81-OH1.2,OH1.3] |
(b) [F44,F81-OH1.1] | |
(c) [F44,F81-OH1.1] | |
(2) | [F81-OH1.1,OH1.2,OH1.3] |
6.2.3.8. Exhaust Ducts and Outlets | |
(1) | [F44-OH1.1] |
(2) | [F44-OH1.1] |
(3) | [F81-OH1.1] |
[F81-OH1.2] | |
(4) | [F81-OH1.1] |
[F81-OH1.2] | |
(5) | [F81-OH1.1] |
(6) | [F81-OH1.1] |
(7) | [F81-OS1.1] |
(8) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(9) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(10) | [F81-OH1.1] |
(11) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
(12) | [F81,F44-OH1.1] |
(13) | [F81-OH1.2] |
[F81,F44-OH1.1] | |
6.2.3.9. Interconnection of Systems | |
(1) | [F44-OS1.1] |
[F40-OH1.1] | |
(2) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
[F81,F44-OP1.1] | |
(3) | [F81,F44-OH1.1] |
6.2.3.11. Makeup Air | |
(1) | [F50,F81-OH1.1] |
[F44,F81-OS3.4] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.2] |
6.2.3.12. Supply, Return, Intake and Exhaust Air Openings | |
(1) | [F30-OS3.1] |
[F81-OH1.2] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.1] |
(4) | [F82,F81-OH1.1] |
[F82-OS3.4] | |
6.2.3.13. Filters and Odour Removal Equipment | |
(1) | [F80-OS1.1] |
[F80-OP1.1] | |
(2) | [F30-OS3.3] |
[F81,F43-OH1.1] | |
(3) | [F82-OH1.1] |
(4) | [F82-OH1.1] |
6.2.3.14. Air Washers and Evaporative Cooling Sections or Towers | |
(1) | [F80,F81-OS1.1] |
[F80,F81-OP1.1] | |
(2) | [F82-OH1.1] |
(3) | [F01,F81-OS1.1] |
6.2.3.15. Fans and Associated Air-Handling Equipment | |
(1) | [F81,F44-OH1.1] |
[F81,F44-OS3.4] | |
(2) | [F81-OH1.1] |
6.2.3.20. Return-Air System | |
(3) | [F10-OS1.5] |
6.2.4.1. Carbon Monoxide Alarms | |
(2) | (a),(b),(d) [F44-OS3.4] (c) [F81-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F44-OS3.4] |
(5) | [F44-OS3.4] |
6.2.5.2. Appliances Installed Outside the Building | |
(1) | [F81-OP1.1] |
[F81-OH1.1] | |
[F81-OS1.1] | |
6.2.6.1. Applicable Standard | |
(1) | [F81-OS1.1] |
6.2.7.1. Clearances | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
6.2.8.1. Lining or Backing | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
6.2.9.1. Piping Materials and Installation | |
(1) | [F20-OS3.2,OS3.4] |
(2) | [F21-OH1.1] |
(3) | [F20-OS2.2] |
6.2.9.2. Insulation and Coverings | |
(1) | [F20,F30-OS3.2,OS3.4] |
(2) | [F31-OS3.2] |
6.2.9.3. Clearances | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.9.4. Surface Temperature | |
(1) | [F31-OS3.2] |
6.2.9.5. Protection | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.10.1. Cooling Units | |
(1) | [F43,F81-OS3.4] |
6.2.11.1. Storage Bins | |
(1) | [F30,F31,F43-OS3.2,OS3.4] |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
(3) | [F30-OH2.1] |
(4) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.11.2. Ash Storage Bins | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.12.2. General Ventilation | |
(1) | (a),(b),(d),(e) [F01-OS1.1] |
(c) [F02-OP1.2] | |
(c) [F02-OS1.2] [F81,F82-OS1.1] | |
(2) | [F81,F11-OS1.1] |
6.2.12.3. Enclosure Exhaust Ventilation | |
(1) | (a),(c),(d) [F01-OS1.1] |
(b) [F02-OP1.2] | |
(e) [F12-OP1.1,OP1.2] | |
(a) [F02-OP1.2] | |
(b) [F02-OS1.2] [F81-OS1.1] | |
(e) [F12-OS1.1,OS1.2] | |
(a) [F02-OS1.2] | |
(a) [F01-OS1.1] | |
6.2.12.4. Enclosure Construction | |
(1) | (a) [F02-OS1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” |
(b) [F02-OP1.2] | |
(a) [F02-OP1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” | |
(a) [F80-OS3.4] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(b) [F02-OS1.2] [F82-OS1.1] | |
(a) [F80-OS1.1] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(a) [F01-OS1.1] Applies to portion of Code text: “… be constructed of … materials compatible with … the dangerous goods vapours and particles being exhausted …” | |
(3) | [F02-OS1.2] |
[F02-OP1.2] | |
6.3.1.2. Masonry or Concrete Chimneys | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.3. Metal Smoke Stacks | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.4. Lightning Protection Systems | |
(1) | [F01,F81-OS1.1] |
[F01,F81-OP1.1] | |
6.3.1.5. Access Ladders | |
(1) | [F20,F80-OS3.1] |
(2) | [F30-OS3.1] |
Table 6.4.1.1. Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6 Forming part of Sentence 6.4.1.1.(1) |
|
Acceptable Solutions | Functional Statements and Objectives(1) |
6.2.1.1. Good Engineering Practice | |
(1) | (a) to (e) [F31,F51-OP1.1] |
(a) to (c) and (e) to (i) [F40,F50,F51,F52,F54,F63-OH1.1] | |
(a),(b),(c),(e),(f),(g),(h) [F50,F51,F52,F54,F63-OH1.2,OH1.3] | |
[F50,F31,F63,F51,F54,F52-OS3.2,OS3.4] | |
(d) [F01-OS1.1] | |
6.2.1.3. Structural Movement | |
(1) | [F23-OS3.1] |
[F51,F63,F50-OH1.1,OH1.2,OH1.3] | |
6.2.1.4. Installation Standards | |
(1) | [F43-OS1.1] |
[F43-OS3.4] | |
[F43-OP1.1] | |
(2) | [F40,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.1.8. Installation – General | |
(1) | [F82-OS1.1] |
[F82-OS3.4] | |
[F82-OP1.1] | |
(2) | [F31-OS3.1] |
(3) | [F81-OS3.2,OS3.3,OS3.4] |
[F81-OS1.1] | |
6.2.1.9. Expansion, Contraction and System Pressure | |
(1) | [F20-OS3.2] |
6.2.1.10. Asbestos | |
(1) | [F43-OH1.1] |
6.2.1.11. Access Openings | |
(1) | [F36-OS3.6] |
6.2.2.1. Required Ventilation | |
(1) | [F50,F31,F63,F51,F54,F52-OS1.1] |
[F50,F31,F63,F51,F54,F52-OP1.1] | |
(2) | [F50-OH1.1] |
(4) | [F50-OH1.1] |
6.2.2.2. Natural Ventilation | |
(1) | [F50-OH1.1] |
(2) | [F50-OH1.1] |
6.2.2.3. Ventilation of Storage Garages | |
(1) | [F50,F44-OS3.4] |
(2) | [F44-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F50,F44-OS3.4] |
(5) | [F50,F44-OH1.1] |
[F50,F44-OS3.4] | |
6.2.2.4. Cleaning Devices | |
(1) | [F40,F43,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.2.5. Air Contaminants | |
(1) | [F44-OS3.4] |
[F44-OH1.1] | |
(2) | [F44-OH1.1] |
(3) | [F52-OH1.1] |
6.2.2.6. Hazardous Gases, Dusts or Liquids | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.2.7. Commercial Cooking Equipment | |
(1) | [F01,F44-OS1.1] |
[F01,F44-OP1.1] | |
(2) | [F02,F81-OS1.2] |
[F02,F81-OP1.2] | |
(3) | [F40, F50-OH5] |
(4) | [F40, F50-OH5] |
6.2.2.8. Crawl Spaces and Attic or Roof Spaces | |
(1) | [F61,F63,F41-OH1.1,OH1.3] |
6.2.3.2. Materials in Air Duct Systems | |
(2) | [F20,F80-OH1.1,OH1.2] |
(3) | [F81,F44-OS3.4] |
[F81-OH1.1] | |
(4) | [F20,F80-OH1.1,OH1.2] |
6.2.3.3. Connections and Openings in Air Duct Systems | |
(1) | [F81-OH1.1,OH1.2] |
[F81,F44-OS3.4] | |
(2) | [F82-OS1.1] |
6.2.3.4. Duct Coverings and Linings | |
(3) | [F81-OH1.1,OH1.2] |
[F81-OS1.1] | |
[F81-OP1.1] | |
6.2.3.5. Underground Ducts | |
(1) | (a) [F44,F81-OH1.2,OH1.3] |
(b) [F44,F81-OH1.1] | |
(c) [F44,F81-OH1.1] | |
(2) | [F81-OH1.1,OH1.2,OH1.3] |
6.2.3.8. Exhaust Ducts and Outlets | |
(1) | [F44-OH1.1] |
(2) | [F44-OH1.1] |
(3) | [F81-OH1.1] |
[F81-OH1.2] | |
(4) | [F81-OH1.1] |
[F81-OH1.2] | |
(5) | [F81-OH1.1] |
(6) | [F81-OH1.1] |
(7) | [F81-OS1.1] |
(8) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(9) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(10) | [F81-OH1.1] |
(11) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
(12) | [F81,F44-OH1.1] |
(13) | [F81-OH1.2] |
[F81,F44-OH1.1] | |
6.2.3.9. Interconnection of Systems | |
(1) | [F44-OS1.1] |
[F40-OH1.1] | |
(2) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
[F81,F44-OP1.1] | |
(3) | [F81,F44-OH1.1] |
6.2.3.11. Makeup Air | |
(1) | [F50,F81-OH1.1] |
[F44,F81-OS3.4] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.2] |
6.2.3.12. Supply, Return, Intake and Exhaust Air Openings | |
(1) | [F30-OS3.1] |
[F81-OH1.2] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.1] |
(4) | [F82,F81-OH1.1] |
[F82-OS3.4] | |
6.2.3.13. Filters and Odour Removal Equipment | |
(1) | [F80-OS1.1] |
[F80-OP1.1] | |
(2) | [F30-OS3.3] |
[F81,F43-OH1.1] | |
(3) | [F82-OH1.1] |
(4) | [F82-OH1.1] |
6.2.3.14. Air Washers and Evaporative Cooling Sections or Towers | |
(1) | [F80,F81-OS1.1] |
[F80,F81-OP1.1] | |
(2) | [F82-OH1.1] |
(3) | [F01,F81-OS1.1] |
6.2.3.15. Fans and Associated Air-Handling Equipment | |
(1) | [F81,F44-OH1.1] |
[F81,F44-OS3.4] | |
(2) | [F81-OH1.1] |
6.2.3.20. Return-Air System | |
(3) | [F10-OS1.5] |
6.2.4.1. Carbon Monoxide Alarms | |
(2) | (a),(b),(d) [F44-OS3.4] (c) [F81-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F44-OS3.4] |
(5) | [F44-OS3.4] |
6.2.5.2. Appliances Installed Outside the Building | |
(1) | [F81-OP1.1] |
[F81-OH1.1] | |
[F81-OS1.1] | |
6.2.6.1. Applicable Standard | |
(1) | [F81-OS1.1] |
6.2.7.1. Clearances | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
6.2.8.1. Lining or Backing | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
6.2.9.1. Piping Materials and Installation | |
(1) | [F20-OS3.2,OS3.4] |
(2) | [F21-OH1.1] |
(3) | [F20-OS2.2] |
6.2.9.2. Insulation and Coverings | |
(1) | [F20,F30-OS3.2,OS3.4] |
(2) | [F31-OS3.2] |
6.2.9.3. Clearances | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.9.4. Surface Temperature | |
(1) | [F31-OS3.2] |
6.2.9.5. Protection | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.10.1. Cooling Units | |
(1) | [F43,F81-OS3.4] |
6.2.11.1. Storage Bins | |
(1) | [F30,F31,F43-OS3.2,OS3.4] |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
(3) | [F30-OH2.1] |
(4) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.11.2. Ash Storage Bins | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.12.2. General Ventilation | |
(1) | (a),(b),(d),(e) [F01-OS1.1] |
(c) [F02-OP1.2] | |
(c) [F02-OS1.2] [F81,F82-OS1.1] | |
(2) | [F81,F11-OS1.1] |
6.2.12.3. Enclosure Exhaust Ventilation | |
(1) | (a),(c),(d) [F01-OS1.1] |
(b) [F02-OP1.2] | |
(e) [F12-OP1.1,OP1.2] | |
(a) [F02-OP1.2] | |
(b) [F02-OS1.2] [F81-OS1.1] | |
(e) [F12-OS1.1,OS1.2] | |
(a) [F02-OS1.2] | |
(a) [F01-OS1.1] | |
6.2.12.4. Enclosure Construction | |
(1) | (a) [F02-OS1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” |
(b) [F02-OP1.2] | |
(a) [F02-OP1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” | |
(a) [F80-OS3.4] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(b) [F02-OS1.2] [F82-OS1.1] | |
(a) [F80-OS1.1] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(a) [F01-OS1.1] Applies to portion of Code text: “… be constructed of … materials compatible with … the dangerous goods vapours and particles being exhausted …” | |
(3) | [F02-OS1.2] |
[F02-OP1.2] | |
6.3.1.2. Masonry or Concrete Chimneys | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.3. Metal Smoke Stacks | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.4. Lightning Protection Systems | |
(1) | [F01,F81-OS1.1] |
[F01,F81-OP1.1] | |
6.3.1.5. Access Ladders | |
(1) | [F20,F80-OS3.1] |
(2) | [F30-OS3.1] |
Table 6.4.1.1. Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6 Forming part of Sentence 6.4.1.1.(1) |
|
Acceptable Solutions | Functional Statements and Objectives(1) |
6.2.1.1. Good Engineering Practice | |
(1) | (a) to (e) [F31,F51-OP1.1] |
(a) to (c) and (e) to (i) [F40,F50,F51,F52,F54,F63-OH1.1] | |
(a),(b),(c),(e),(f),(g),(h) [F50,F51,F52,F54,F63-OH1.2,OH1.3] | |
[F50,F31,F63,F51,F54,F52-OS3.2,OS3.4] | |
(d) [F01-OS1.1] | |
6.2.1.3. Structural Movement | |
(1) | [F23-OS3.1] |
[F51,F63,F50-OH1.1,OH1.2,OH1.3] | |
6.2.1.4. Installation Standards | |
(1) | [F43-OS1.1] |
[F43-OS3.4] | |
[F43-OP1.1] | |
6.2.1.7. Outdoor Design Conditions | |
(2) | [F40,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.1.8. Installation – General | |
(1) | [F82-OS1.1] |
[F82-OS3.4] | |
[F82-OP1.1] | |
(2) | [F31-OS3.1] |
(3) | [F81-OS3.2,OS3.3,OS3.4] |
[F81-OS1.1] | |
6.2.1.9. Expansion, Contraction and System Pressure | |
(1) | [F20-OS3.2] |
6.2.1.10. Asbestos | |
(1) | [F43-OH1.1] |
6.2.1.11. Access Openings | |
(1) | [F36-OS3.6] |
6.2.2.1. Required Ventilation | |
(1) | [F50,F31,F63,F51,F54,F52-OS1.1] |
[F50,F31,F63,F51,F54,F52-OP1.1] | |
(2) | [F50-OH1.1] |
(4) | [F50-OH1.1] |
6.2.2.2. Natural Ventilation | |
(1) | [F50-OH1.1] |
(2) | [F50-OH1.1] |
6.2.2.3. Ventilation of Storage Garages | |
(1) | [F50,F44-OS3.4] |
(2) | [F44-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F50,F44-OS3.4] |
(5) | [F50,F44-OH1.1] |
[F50,F44-OS3.4] | |
6.2.2.4. Cleaning Devices | |
(1) | [F40,F43,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.2.5. Air Contaminants | |
(1) | [F44-OS3.4] |
[F44-OH1.1] | |
(2) | [F44-OH1.1] |
(3) | [F52-OH1.1] |
6.2.2.6. Hazardous Gases, Dusts or Liquids | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.2.7. Commercial Cooking Equipment | |
(1) | [F01,F44-OS1.1] |
[F01,F44-OP1.1] | |
(2) | [F02,F81-OS1.2] |
[F02,F81-OP1.2] | |
(3) | [F40, F50-OH5] |
(4) | [F40, F50-OH5] |
6.2.2.8. Crawl Spaces and Attic or Roof Spaces | |
(1) | [F61,F63,F41-OH1.1,OH1.3] |
6.2.3.2. Materials in Air Duct Systems | |
(2) | [F20,F80-OH1.1,OH1.2] |
(3) | [F81,F44-OS3.4] |
[F81-OH1.1] | |
(4) | [F20,F80-OH1.1,OH1.2] |
6.2.3.3. Connections and Openings in Air Duct Systems | |
(1) | [F81-OH1.1,OH1.2] |
[F81,F44-OS3.4] | |
(2) | [F82-OS1.1] |
6.2.3.4. Duct Coverings and Linings | |
(3) | [F81-OH1.1,OH1.2] |
[F81-OS1.1] | |
[F81-OP1.1] | |
6.2.3.5. Underground Ducts | |
(1) | (a) [F44,F81-OH1.2,OH1.3] |
(b) [F44,F81-OH1.1] | |
(c) [F44,F81-OH1.1] | |
(2) | [F81-OH1.1,OH1.2,OH1.3] |
6.2.3.8. Exhaust Ducts and Outlets | |
(1) | [F44-OH1.1] |
(2) | [F44-OH1.1] |
(3) | [F81-OH1.1] |
[F81-OH1.2] | |
(4) | [F81-OH1.1] |
[F81-OH1.2] | |
(5) | [F81-OH1.1] |
(6) | [F81-OH1.1] |
(7) | [F81-OS1.1] |
(8) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(9) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(10) | [F81-OH1.1] |
(11) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
(12) | [F81,F44-OH1.1] |
(13) | [F81-OH1.2] |
[F81,F44-OH1.1] | |
6.2.3.9. Interconnection of Systems | |
(1) | [F44-OS1.1] |
[F40-OH1.1] | |
(2) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
[F81,F44-OP1.1] | |
(3) | [F81,F44-OH1.1] |
6.2.3.11. Makeup Air | |
(1) | [F50,F81-OH1.1] |
[F44,F81-OS3.4] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.2] |
6.2.3.12. Supply, Return, Intake and Exhaust Air Openings | |
(1) | [F30-OS3.1] |
[F81-OH1.2] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.1] |
(4) | [F82,F81-OH1.1] |
[F82-OS3.4] | |
6.2.3.13. Filters and Odour Removal Equipment | |
(1) | [F80-OS1.1] |
[F80-OP1.1] | |
(2) | [F30-OS3.3] |
[F81,F43-OH1.1] | |
(3) | [F82-OH1.1] |
(4) | [F82-OH1.1] |
6.2.3.14. Air Washers and Evaporative Cooling Sections or Towers | |
(1) | [F80,F81-OS1.1] |
[F80,F81-OP1.1] | |
(2) | [F82-OH1.1] |
(3) | [F01,F81-OS1.1] |
6.2.3.15. Fans and Associated Air-Handling Equipment | |
(1) | [F81,F44-OH1.1] |
[F81,F44-OS3.4] | |
(2) | [F81-OH1.1] |
6.2.3.20. Return-Air System | |
(3) | [F10-OS1.5] |
6.2.4.1. Carbon Monoxide Alarms | |
(2) | (a),(b),(d) [F44-OS3.4] (c) [F81-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F44-OS3.4] |
(5) | [F44-OS3.4] |
6.2.5.2. Appliances Installed Outside the Building | |
(1) | [F81-OP1.1] |
[F81-OH1.1] | |
[F81-OS1.1] | |
6.2.6.1. Applicable Standard | |
(1) | [F81-OS1.1] |
6.2.7.1. Clearances | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
6.2.8.1. Lining or Backing | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
6.2.9.1. Piping Materials and Installation | |
(1) | [F20-OS3.2,OS3.4] |
(2) | [F21-OH1.1] |
(3) | [F20-OS2.2] |
6.2.9.2. Insulation and Coverings | |
(1) | [F20,F30-OS3.2,OS3.4] |
(2) | [F31-OS3.2] |
6.2.9.3. Clearances | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.9.4. Surface Temperature | |
(1) | [F31-OS3.2] |
6.2.9.5. Protection | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.10.1. Cooling Units | |
(1) | [F43,F81-OS3.4] |
6.2.11.1. Storage Bins | |
(1) | [F30,F31,F43-OS3.2,OS3.4] |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
(3) | [F30-OH2.1] |
(4) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.11.2. Ash Storage Bins | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.12.2. General Ventilation | |
(1) | (a),(b),(d),(e) [F01-OS1.1] |
(c) [F02-OP1.2] | |
(c) [F02-OS1.2] [F81,F82-OS1.1] | |
(2) | [F81,F11-OS1.1] |
6.2.12.3. Enclosure Exhaust Ventilation | |
(1) | (a),(c),(d) [F01-OS1.1] |
(b) [F02-OP1.2] | |
(e) [F12-OP1.1,OP1.2] | |
(a) [F02-OP1.2] | |
(b) [F02-OS1.2] [F81-OS1.1] | |
(e) [F12-OS1.1,OS1.2] | |
(a) [F02-OS1.2] | |
(a) [F01-OS1.1] | |
6.2.12.4. Enclosure Construction | |
(1) | (a) [F02-OS1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” |
(b) [F02-OP1.2] | |
(a) [F02-OP1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” | |
(a) [F80-OS3.4] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(b) [F02-OS1.2] [F82-OS1.1] | |
(a) [F80-OS1.1] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(a) [F01-OS1.1] Applies to portion of Code text: “… be constructed of … materials compatible with … the dangerous goods vapours and particles being exhausted …” | |
(3) | [F02-OS1.2] |
[F02-OP1.2] | |
6.3.1.2. Masonry or Concrete Chimneys | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.3. Metal Smoke Stacks | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.4. Lightning Protection Systems | |
(1) | [F01,F81-OS1.1] |
[F01,F81-OP1.1] | |
6.3.1.5. Access Ladders | |
(1) | [F20,F80-OS3.1] |
(2) | [F30-OS3.1] |
Table 6.4.1.1. Objectives and Functional Statements Attributed to the Acceptable Solutions in Part 6 Forming part of Sentence 6.4.1.1.(1) |
|
Acceptable Solutions | Functional Statements and Objectives(1) |
6.2.1.1. Good Engineering Practice | |
(1) | (a) to (e) [F31,F51-OP1.1] |
(a) to (c) and (e) to (i) [F40,F50,F51,F52,F54,F63-OH1.1] | |
(a),(b),(c),(e),(f),(g),(h) [F50,F51,F52,F54,F63-OH1.2,OH1.3] | |
[F50,F31,F63,F51,F54,F52-OS3.2,OS3.4] | |
(d) [F01-OS1.1] | |
6.2.1.3. Structural Movement | |
(1) | [F23-OS3.1] |
[F51,F63,F50-OH1.1,OH1.2,OH1.3] | |
6.2.1.4. Installation Standards | |
(1) | [F43-OS1.1] |
[F43-OS3.4] | |
[F43-OP1.1] | |
6.2.1.7. Outdoor Design Conditions | |
(2) | [F40,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.1.8. Installation – General | |
(1) | [F82-OS1.1] |
[F82-OS3.4] | |
[F82-OP1.1] | |
(2) | [F31-OS3.1] |
(3) | [F81-OS3.2,OS3.3,OS3.4] |
[F81-OS1.1] | |
6.2.1.9. Expansion, Contraction and System Pressure | |
(1) | [F20-OS3.2] |
6.2.1.10. Asbestos | |
(1) | [F43-OH1.1] |
6.2.1.11. Access Openings | |
(1) | [F36-OS3.6] |
6.2.2.1. Required Ventilation | |
(1) | [F50,F31,F63,F51,F54,F52-OS1.1] |
[F50,F31,F63,F51,F54,F52-OP1.1] | |
(2) | [F50-OH1.1] |
(4) | [F50-OH1.1] |
6.2.2.2. Natural Ventilation | |
(1) | [F50-OH1.1] |
(2) | [F50-OH1.1] |
6.2.2.3. Ventilation of Storage Garages | |
(1) | [F50,F44-OS3.4] |
(2) | [F44-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F50,F44-OS3.4] |
(5) | [F50,F44-OH1.1] |
[F50,F44-OS3.4] | |
6.2.2.4. Cleaning Devices | |
(1) | [F40,F43,F44,F50-OH1.1] |
[F44-OS3.4] | |
6.2.2.5. Air Contaminants | |
(1) | [F44-OS3.4] |
[F44-OH1.1] | |
(2) | [F44-OH1.1] |
(3) | [F52-OH1.1] |
6.2.2.6. Hazardous Gases, Dusts or Liquids | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.2.7. Commercial Cooking Equipment | |
(1) | [F01,F44-OS1.1] |
[F01,F44-OP1.1] | |
(2) | [F02,F81-OS1.2] |
[F02,F81-OP1.2] | |
(3) | [F40, F50-OH5] |
(4) | [F40, F50-OH5] |
6.2.2.8. Crawl Spaces and Attic or Roof Spaces | |
(1) | [F61,F63,F41-OH1.1,OH1.3] |
6.2.3.2. Materials in Air Duct Systems | |
(2) | [F20,F80-OH1.1,OH1.2] |
(3) | [F81,F44-OS3.4] |
[F81-OH1.1] | |
(4) | [F20,F80-OH1.1,OH1.2] |
6.2.3.3. Connections and Openings in Air Duct Systems | |
(1) | [F81-OH1.1,OH1.2] |
[F81,F44-OS3.4] | |
(2) | [F82-OS1.1] |
6.2.3.4. Duct Coverings and Linings | |
(3) | [F81-OH1.1,OH1.2] |
[F81-OS1.1] | |
[F81-OP1.1] | |
6.2.3.5. Underground Ducts | |
(1) | (a) [F44,F81-OH1.2,OH1.3] |
(b) [F44,F81-OH1.1] | |
(c) [F44,F81-OH1.1] | |
(2) | [F81-OH1.1,OH1.2,OH1.3] |
6.2.3.8. Exhaust Ducts and Outlets | |
(1) | [F44-OH1.1] |
(2) | [F44-OH1.1] |
(3) | [F81-OH1.1] |
[F81-OH1.2] | |
(4) | [F81-OH1.1] |
[F81-OH1.2] | |
(5) | [F81-OH1.1] |
(6) | [F81-OH1.1] |
(7) | [F81-OS1.1] |
(8) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(9) | [F40,F44,F50,F52-OH1.1] |
[F44-OS3.4] | |
[F01-OS1.1] | |
[F01-OP1.1] | |
(10) | [F81-OH1.1] |
(11) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
(12) | [F81,F44-OH1.1] |
(13) | [F81-OH1.2] |
[F81,F44-OH1.1] | |
6.2.3.9. Interconnection of Systems | |
(1) | [F44-OS1.1] |
[F40-OH1.1] | |
(2) | [F81,F44-OH1.1] |
[F81,F44-OS1.1] | |
[F81,F44-OP1.1] | |
(3) | [F81,F44-OH1.1] |
6.2.3.11. Makeup Air | |
(1) | [F50,F81-OH1.1] |
[F44,F81-OS3.4] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.2] |
6.2.3.12. Supply, Return, Intake and Exhaust Air Openings | |
(1) | [F30-OS3.1] |
[F81-OH1.2] | |
(2) | [F81-OH1.1] |
[F81,F44-OS3.4] | |
(3) | [F81-OH1.1] |
(4) | [F82,F81-OH1.1] |
[F82-OS3.4] | |
6.2.3.13. Filters and Odour Removal Equipment | |
(1) | [F80-OS1.1] |
[F80-OP1.1] | |
(2) | [F30-OS3.3] |
[F81,F43-OH1.1] | |
(3) | [F82-OH1.1] |
(4) | [F82-OH1.1] |
6.2.3.14. Air Washers and Evaporative Cooling Sections or Towers | |
(1) | [F80,F81-OS1.1] |
[F80,F81-OP1.1] | |
(2) | [F82-OH1.1] |
(3) | [F01,F81-OS1.1] |
6.2.3.15. Fans and Associated Air-Handling Equipment | |
(1) | [F81,F44-OH1.1] |
[F81,F44-OS3.4] | |
(2) | [F81-OH1.1] |
6.2.3.20. Return-Air System | |
(3) | [F10-OS1.5] |
6.2.4.1. Carbon Monoxide Alarms | |
(2) | (a),(b),(d) [F44-OS3.4] (c) [F81-OS3.4] |
(3) | [F44-OS3.4] |
(4) | [F44-OS3.4] |
(5) | [F44-OS3.4] |
6.2.5.2. Appliances Installed Outside the Building | |
(1) | [F81-OP1.1] |
[F81-OH1.1] | |
[F81-OS1.1] | |
6.2.6.1. Applicable Standard | |
(1) | [F81-OS1.1] |
6.2.7.1. Clearances | |
(1) | [F01-OP1.1] |
[F01-OS1.1] | |
6.2.8.1. Lining or Backing | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
6.2.9.1. Piping Materials and Installation | |
(1) | [F20-OS3.2,OS3.4] |
(2) | [F21-OH1.1] |
(3) | [F20-OS2.2] |
6.2.9.2. Insulation and Coverings | |
(1) | [F20,F30-OS3.2,OS3.4] |
(2) | [F31-OS3.2] |
6.2.9.3. Clearances | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.9.4. Surface Temperature | |
(1) | [F31-OS3.2] |
6.2.9.5. Protection | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.10.1. Cooling Units | |
(1) | [F43,F81-OS3.4] |
6.2.11.1. Storage Bins | |
(1) | [F30,F31,F43-OS3.2,OS3.4] |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
(3) | [F30-OH2.1] |
(4) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.11.2. Ash Storage Bins | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.2.12.2. General Ventilation | |
(1) | (a),(b),(d),(e) [F01-OS1.1] |
(c) [F02-OP1.2] | |
(c) [F02-OS1.2] [F81,F82-OS1.1] | |
(2) | [F81,F11-OS1.1] |
6.2.12.3. Enclosure Exhaust Ventilation | |
(1) | (a),(c),(d) [F01-OS1.1] |
(b) [F02-OP1.2] | |
(e) [F12-OP1.1,OP1.2] | |
(a) [F02-OP1.2] | |
(b) [F02-OS1.2] [F81-OS1.1] | |
(e) [F12-OS1.1,OS1.2] | |
(a) [F02-OS1.2] | |
(a) [F01-OS1.1] | |
6.2.12.4. Enclosure Construction | |
(1) | (a) [F02-OS1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” |
(b) [F02-OP1.2] | |
(a) [F02-OP1.2] Applies to portion of Code text: “… be constructed of noncombustible materials …” | |
(a) [F80-OS3.4] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(b) [F02-OS1.2] [F82-OS1.1] | |
(a) [F80-OS1.1] Applies to portion of Code text: “… be constructed of … materials … chemically resistant to the dangerous goods vapours and particles being exhausted …” | |
(a) [F01-OS1.1] Applies to portion of Code text: “… be constructed of … materials compatible with … the dangerous goods vapours and particles being exhausted …” | |
(3) | [F02-OS1.2] |
[F02-OP1.2] | |
6.3.1.2. Masonry or Concrete Chimneys | |
(2) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.3. Metal Smoke Stacks | |
(1) | [F01-OS1.1] |
[F01-OP1.1] | |
6.3.1.4. Lightning Protection Systems | |
(1) | [F01,F81-OS1.1] |
[F01,F81-OP1.1] | |
6.3.1.5. Access Ladders | |
(1) | [F20,F80-OS3.1] |
(2) | [F30-OS3.1] |