Division B
Acceptable Solutions
Part 5 — Environmental Separation
Section 5.5. Vapour Diffusion
(See Appendix A and Part 10.)5.5.1. Vapour Barriers
5.5.1.1. Required Resistance to Vapour Diffusion
(See Appendix A.)1)
Where a building component or assembly is subjected to differentials in temperature and water vapour pressure,
the properties and position of the materials and components in those
components or assemblies shall be such that they control vapour diffusion
or permit venting to the exterior so as to minimize the accumulation
of condensation in the building component or assembly.

2)
Except as provided in Sentence (3), a vapour barrier shall be installed to provide the principal resistance to water vapour diffusion.

3)
A vapour barrier is not required where it can be shown that uncontrolled vapour diffusion will not adversely affect any of

a) the health or safety of building users,
b) the intended use of the building, or
c) the operation of building services.
5.5.1.2. Vapour Barrier Properties and Installation
(See A-5.3.1.2. in Appendix A.)1)
The vapour barrier shall have sufficiently low permeance and shall be positioned in the building component or assembly so as to

a) minimize moisture transfer by diffusion, to surfaces within the assembly that would be cold enough to cause condensation at the
design temperature and humidity conditions, or
b) reduce moisture transfer by diffusion, to surfaces within the
assembly that would be cold enough to cause condensation at the design
temperature and humidity conditions, to a rate that will not allow
sufficient accumulation of moisture to cause deterioration or otherwise
adversely affect any of
(See Appendix A.)i) the health or safety of building users,
ii) the intended use of the building, or
iii) the operation of building services.
2)
Coatings applied to gypsum wallboard to provide required resistance to vapour diffusion shall conform to the requirements of Sentence (1) when tested in accordance with CAN/CGSB-1.501-M, “Method for Permeance of Coated Wallboard.”

3)
Coatings applied to materials other than gypsum wallboard to provide required resistance to vapour diffusion shall conform to the
requirements of Sentence (1) when tested in accordance with ASTM E 96/E 96M, “Water Vapor Transmission of Materials,” by the desiccant
method (dry cup).