1) This Section shall apply to hot works involving open
flames or producing heat or sparks, including, without being
limited to, cutting, welding, soldering, brazing, grinding,
adhesive bonding, thermal spraying and thawing
pipes.
2) Except as provided in this Section, hot works
described in Sentence (1) shall conform to CAN/CSA-W117.2, “Safety in
Welding, Cutting and Allied Processes.”
1) Hot works shall be performed only by personnel trained
in the safe use of equipment in conformance with this
Section.
1) Hot work equipment shall be maintained in good
operating condition.
1) Hot work equipment shall be examined for leakage or
defects prior to each use.
2) Leaks or defects found in hot work equipment shall be
repaired prior to use.
1) All valves shall be closed and gas lines bled when
Class 2 gas hot work equipment is not in use.
2) Electric hot work equipment shall be de-energized when
not in use.
1) The design and installation of oxygen-fuel gas
equipment shall conform to NFPA 51, “Design and Installation of
Oxygen-Fuel Gas Systems for Welding, Cutting and Allied
Processes.”
2) Unalloyed copper piping shall not be used for
acetylene gas.
3) Oil or grease shall not be used with equipment for
oxygen.
4) Cylinders of Class 2 gases shall conform to Part 3.
1) Except as provided in Sentence (2), hot work shall be carried out in an area free of combustible and
flammable contents, with walls, ceilings and floors of noncombustible construction or lined with noncombustible materials.
2) When it is not practicable to undertake hot work in an
area described in Sentence (1),
a)combustible and flammable materials within a 15 m distance from the hot work shall be protected against ignition in conformance with Article 5.2.3.2.,
b)a fire watch shall be provided during the hot work and for a period of not less than 60 min after its completion in conformance with Article 5.2.3.3., and
c)a final inspection of the hot work area shall be conducted 4 h after completion of work.
3) When there is a possibility of sparks leaking onto
combustible materials in areas adjacent to the area where hot
work is carried out,
a)openings in walls, floors or ceilings shall be covered or closed to prevent the passage of sparks to such adjacent areas, or
b) Sentence (2) shall apply to such adjacent areas.
1) Any combustible and flammable material, dust or
residue shall be
a)removed from the area where hot work is carried out, or
b)protected against ignition by the use of noncombustible materials.
2) Combustible materials or building surfaces that cannot be removed or protected against ignition as required in Sentence (1) shall be thoroughly wetted where hot work is carried out.
3) Any process or activity that produces flammable gases
or vapours, combustible dusts or combustible fibres in quantities sufficient to create a fire or explosion hazard shall be
interrupted and the hazardous conditions shall be
removed before any hot work is carried
out.
1) The exposed areas described in Sentences 5.2.3.1.(2) and (3) shall be examined for ignition of combustible materials by personnel
equipped with and trained in the use of fire extinguishing
equipment.
1) Hot work shall not be performed on containers,
equipment, or piping containing flammable liquids, combustible liquids or Class 2.1 flammable gases unless
a)they have been cleaned and tested with a gas detector to ascertain that they are free of explosive vapours, or
b) safety measures are taken in conformance with good engineering practice (see Appendix A).
2) Hot work shall not be performed on a totally enclosed
container.
3) Hot work shall not be performed on metal objects that
are in contact with combustible materials unless safety
precautions are taken to prevent their ignition by
conduction.
1) When hot work is to be carried out near piping
containing a Class 2.1 flammable gas, the piping shall
a)conform to Sentence 5.2.3.4.(1), or
b)be protected by a thermal barrier against the passage of heat.
1) At least one portable fire extinguisher shall be
provided in the hot work area.
1) In buildings or areas described in Article 2.8.1.1., the required fire safety plan shall include the safety measures
described in this Subsection for the safe conducting of hot
works.