1) Fire alarm and voice communication systems shall be
maintained in operable condition at all times.
1) Fire alarm systems shall be inspected and tested in
conformance with CAN/ULC-S536, “Inspection and Testing of Fire
Alarm Systems.”
2) Fire alarm and detection system components shall be
accessible for purposes of inspection or
maintenance.
1) Central stations, including their fire protection
signalling systems, shall be maintained in conformance with
CAN/ULC-S561, “Installation and Services for Fire Signal
Receiving Centres and Systems.”
(See Appendix A.)
1) Voice communication systems that are integrated with a
required fire alarm system shall be tested in conformance with
Article 6.3.1.2.
2) Voice communication or public address systems that are
part of the building evacuation plan and are not electrically supervised shall be tested at intervals not
greater than one month in conformance with Sentences (3) and (4). (See Appendix A.)
3) Loudspeakers operated from the central alarm and
control facility shall be tested to ensure they can be heard in
all parts of the building.
4) The 2-way communication system from each floor area to the central alarm and control facility shall be tested to ensure proper
operation.