1) Except as specifically prescribed in this Part, all
tests specified in this Section and Section 7.3. shall be carried out at intervals not greater than 3 months, except that
longer intervals between tests are permitted in conformance with
Clause 1.2.1.1.(1)(b) of Division A. (See Appendix A.)
1) Emergency service features of elevators shall be
tested to ensure that they operate in conformance with
appropriate provincial, territorial or municipal requirements
or, in the absence of such requirements, as provided in Sentence (2).
2) Tests to ensure operation in conformance with
the British Columbia Safety Standards Act
and pursuant regulations, shall be
performed on
a)in-car emergency service switches,
b)manual key-operated recall switches located outside an elevator shaft, and
c)automatic emergency recall systems.
3) At intervals not greater than 12 months, the building emergency power systems shall be operated and all elevators supplied with emergency power shall
be tested as provided in Sentence (1) with no other source of electrical power.
1) The closures in vent openings into smoke shafts from each floor area shall be tested in conformance with Article 7.2.1.1. to ensure that they will open as required in Chapter 3, Sentence (5) of Commentary
C of the User's Guide – NBC 1995 (Part
3).
2) A closure in an opening to the outdoors at the top of a smoke shaft shall be tested to ensure
that it will open
a)manually from outside the building,
b)on a signal from the smoke detector in the smoke shaft, and
c)when a closure in an opening between a floor area and the smoke shaft opens.
1) In addition to the procedures described in Article 7.2.3.1., all elevators in an elevator shaft that is designed for use as a
smoke shaft shall be tested to ensure that on activation of the
fire alarm system they will return to the street floor level and remain inoperative.
1) Controls for air-handling systems used for venting in
the event of a fire shall be tested to ensure that air is
exhausted from each floor area to the outdoors as required in Chapter 3, Sentence (8) of Commentary C
of the User's Guide – BCBC 1995 (Part 3).
1) Air moving fans in a system serving more than 2 storeys shall be tested to ensure that they will stop on activation of a switch at the central alarm and
control facility.
1) Doors to vestibules that are normally held open by a
hold-open device connected to the building fire alarm system shall be tested to ensure that they will close on a signal from the central alarm and control
facility.