A-1.1.2.1.(1) Objectives and Functional Statements Attributed to Acceptable Solutions. The objectives and functional statements attributed to each By-law provision are shown in Tables at the end of each Part in Division B.
Many provisions in Division B serve as modifiers of or pointers to other provisions, or serve other clarification or explanatory purposes. In most cases, no objectives and functional statements have been attributed to such provisions, which therefore do not appear in the above-mentioned tables.
For provisions that serve as modifiers of or pointers to other referenced provisions and that do not have any objectives and functional statements attributed to them, the objectives and functional statements that should be used are those attributed to the provisions they reference.
A-1.1.3.1.(1) Climatic and Seismic Values. Climatic values for municipalities not listed in Appendix C may be obtained by writing to the Meteorological Service of Canada, Environment Canada, 4905 Dufferin Street, Toronto, Ontario M3H 5T4.
Seismic values for municipalities not listed in Appendix C may be obtained through the Natural Resources Canada Web site at www.EarthquakesCanada.ca, or by writing to the Geological Survey of Canada at 7 Observatory Crescent, Ottawa, Ontario K1A 0Y3, or at P.O. Box 6000, Sidney, B.C. V8L 4B2.
A-1.1.3.1.(2) Winter Design Temperatures. The 2.5% values referred to in Sentence 1.1.3.1.(2) are the least restrictive temperatures that can be used. If a designer chooses to use the 1% value given in Table 1.1.3.1.A and Table 1.1.3.1.B, it would be in excess of the By-law minimum and would be considered acceptable.
A-1.3.1.2.(1) Applicable Editions. Where documents are referenced in Appendices A, B and C of this By-law, they shall be the editions designated in Table A-1.3.1.2.(1).
Table A-1.3.1.2.(1) Documents Referenced in Appendices A, B and C of the Vancouver Building By-law |
|||
Issuing Agency | Document Number | Title of Document | By-law Reference |
---|---|---|---|
ANSI/ASCE | 8-02 | Design of Cold Formed Stainless Steel Structural Members | A-4.3.4.2.(1) |
ANSI/ASHRAE | 62-2001 | Ventilation for Acceptable Indoor Air Quality | A-9.25.1.2. |
ANSI/ASME | B18.6.1-1981 | Wood Screws (Inch Series) | A-9.23.3.1.(2) |
ANSI/ASME | B16.3-1998 | Malleable-Iron Threaded Fittings | Table A-7.2.5., 7.2.6. and 7.2.7. |
ANSI/ASME | B16.4-1998 | Gray Iron Threaded Fittings | Table A-7.2.5., 7.2.6. and 7.2.7. |
ANSI/ASME | B16.15-1985 | Cast Bronze Threaded Fittings, Classes 125 and 250 | Table A-7.2.5., 7.2.6. and 7.2.7. |
ANSI | B16.18-2001 | Cast Copper Alloy Solder-Joint Pressure Fittings | Table A-7.2.5., 7.2.6. and 7.2.7. |
ANSI/ASME | B16.22-2001 | Wrought Copper and Copper Alloy Solder-Joint Pressure Fittings | Table A-7.2.5., 7.2.6. and 7.2.7. |
ASME | B16.23-2002 | Cast Copper Alloy Solder Joint Drainage Fittings: DWV | Table A-7.2.5., 7.2.6. and 7.2.7. |
ANSI/ASME | B16.29-2001 | Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings – DWV | Table A-7.2.5., 7.2.6. and 7.2.7. |
ANSI/AWWA | C151/A21.51-2002 | Ductile-Iron Pipe, Centrifugally Cast, for Water | Table A-7.2.5., 7.2.6. and 7.2.7. |
ASHRAE | 2003 | ASHRAE Handbook of HVAC Applications, Chapter 45, Control of Gaseous Indoor Air Contaminants | A-7.6.1.1.(1) |
ASPE | 1999 | Data Book – Volume 2, Chapter 5, Cold Water Systems | A-7.6.1.1.(1) |
ASPE | 1999 | Data Book – Volume 2, Chapter 6, Domestic Water Heating Systems Fundamentals | A-7.6.1.1.(1) |
ASPE | 2003 | Data Book – Volume 4, Chapter 8, Grease Interceptors | A-7.4.4.3.(1) |
ASTM | A 53/A 53M-02 | Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless | Table A-7.2.5., 7.2.6. and 7.2.7. |
ASTM | B 42-02e1 | Seamless Copper Pipe, Standard Sizes | Table A-7.2.5., 7.2.6. and 7.2.7. |
ASTM | B 43-98e1 | Seamless Red Brass Pipe, Standard Sizes | Table A-7.2.5., 7.2.6. and 7.2.7. |
ASTM | B 88-03 | Seamless Copper Water Tube | Table A-7.2.5., 7.2.6. and 7.2.7. |
ASTM | B 306-02 | Copper Drainage Tube (DWV) | Table A-7.2.5., 7.2.6. and 7.2.7. |
ASTM | D 2466-02 | Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40 | Table A-7.2.5., 7.2.6. and 7.2.7. |
ASTM | D 2467-02 | Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80 | Table A-7.2.5., 7.2.6. and 7.2.7. |
ASTM | D 3138-02 | Solvent Cements for Transition Joints Between Acrylonitrile-Butadiene-Styrene (ABS) and Poly(Vinyl Chloride) (PVC) Non-Pressure Piping Components | A-7.2.5.10. to 7.2.5.12. |
ASTM | F 628-01 | Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, Waste, and Vent Pipe With a Cellular Core | Table A-7.2.5., 7.2.6. and 7.2.7. |
ASTM | F 714-03 | Polyethylene (PE) Plastic Pipe (SDR-PR) Based on Outside Diameter | Table A-7.2.5., 7.2.6. and 7.2.7. |
ASTM | C 516-02 | Vermiculite Loose Fill Thermal Insulation | A-9.25.2.4.(5) |
ASTM | D 1037-99 | Evaluating Properties of Wood-Base Fiber and Particle Panel Materials | A-9.23.14.2.(4) |
ASTM | D 1143-81e1 | Piles Under Static Axial Compressive Load | A-4.2.7.2.(2) |
ASTM | E 336-97e1 | Measurement of Airborne Sound Insulation in Buildings | A-9.11.1.1.(1) |
ASTM | E 492-90e1 | Laboratory Measurement of Impact Sound Transmission Through Floor-Ceiling Assemblies Using The Tapping Machine | A-9.11.1.1.(1) |
ASTM | E 597-95 | Determining a Single Number Rating of Airborne Sound Insulation for Use in Multi-Unit Building Specifications | A-9.11.1.1.(1) |
ASTM | E 1007-97 | Field Measurement of Tapping Machine Impact Sound Transmission Through Floor-Ceiling Assemblies and Associated Support Structures | A-9.11.1.1.(1) |
ASTM | F 476-84 | Security of Swinging Door Assemblies | A-9.6.8.10.(1) |
AWWA | 2004 | Manual M14, Recommended Practice for Backflow Prevention and Cross-Connection Control | A-7.6.2.4.(2) |
CCBFC | NRCC 30629 | Supplement to the National Building Code of Canada 1990 | Appendix C |
CCBFC | NRCC 35951 | Guidelines for Application of Part 3 of the National Building Code of Canada to Existing Buildings | A-1.1.1.1.(1) (1) |
CCBFC | NRCC 47667 | National Fire Code of Canada 2005 | A-1.1.1.1.(1) (1) A-3.1.2.3.(1) A-3.2.4.6.(2) A-3.2.7.8.(3) A-3.3. A-3.3.1.2.(1) A-3.3.1.7.(1) A-3.3.3.1.(1) B-3.2.6. |
CCBFC | NRCC 47668 | National Plumbing Code of Canada 2005 | A-4.1.6.4.(3) Appendix C |
CCBFC | NRCC 38732 | National Farm Building Code of Canada 1995 | A-1.4.1.2.(1) (1) A-Table 4.1.2.1. A-5.1.2.1.(1) |
CCBFC | NRCC 40383 | User's Guide – NBC 1995, Fire Protection, Occupant Safety and Accessibility (Part 3) | A-1.1.1.1.(1) (1) |
CCBFC | NRCC 48192 | User's Guide – NBC 2005, Structural Commentaries (Part 4 of Division B) | A-1.1.1.1.(1) (1) A-4.1.1.3.(1) A-4.1.3.2.(2) A-4.1.3.2.(3) A-4.1.3.4.(1) A-4.1.3.5.(1) A-4.1.3.5.(3) A-Table 4.1.8.5. A-Table 4.1.8.6. A-5.1.4.2. Appendix C |
CCBFC | NRCC 43963 | User's Guide – NBC 1995, Application of Part 9 to Existing Buildings | A-1.1.1.1.(1) (1) |
CGSB | CAN/CGSB-7.2-97 | Adjustable Steel Columns | A-9.17.3.4. |
CGSB | CAN/CGSB-12.20-M89 | Structural Design of Glass for Buildings | A-9.7.3.2.(1) |
CGSB | CAN/CGSB-71.26-M88 | Adhesive for Field-Gluing Plywood to Lumber Framing for Floor Systems | Table A-9.23.4.2.(2)C. |
CGSB | CAN/CGSB-82.6-M86 | Doors, Mirrored Glass, Sliding or Folding, Wardrobe | A-9.6.6.3.(1) |
CGSB | CAN/CGSB-93.1-M85 | Sheet, Aluminum Alloy, Prefinished, Residential | A-9.27.12.1.(3) and (4) |
CGSB | CAN/CGSB-93.2-M91 | Prefinished Aluminum Siding, Soffits, and Fascia, for Residential Use | A-9.27.12.1.(3) and (4) |
CGSB | CAN/CGSB-34.1-94 | Asbestos-Cement Pressure Pipe | Table A-7.2.5., 7.2.6. and 7.2.7. |
CGSB | CAN/CGSB-34.9-94 | Asbestos-Cement Sewer Pipe | Table A-7.2.5., 7.2.6. and 7.2.7. |
CGSB | CAN/CGSB-34.22-94 | Asbestos-Cement Drain Pipe | Table A-7.2.5., 7.2.6. and 7.2.7. |
CGSB | CAN/CGSB-34.23-94 | Asbestos-Cement House Connection Sewer Pipe | Table A-7.2.5., 7.2.6. and 7.2.7. |
CMHC | 1993 | Testing of Fresh Air Mixing Devices | A-9.32.3.4. |
CMHC | 1988 | Air Permeance of Building Materials | A-5.4.1.2.(1) and (2) Table A-9.25.1.2.B. |
CSA | A23.3-04 | Design of Concrete Structures | A-4.1.3.2.(3) A-4.3.3.1.(1) |
CSA | CAN/CSA-A23.4-00 | Precast Concrete – Materials and Construction | A-4.3.3.1.(1) |
CSA | A82.31-M80 | Gypsum Board Application | Table A-9.10.3.1.A. Table A-9.10.3.1.B. |
CSA | CAN/CSA-A277-01 | Procedure for Certification of Factory-Built Houses | A-1.1.1.1.(2) (1) |
CSA | A370-04 | Connectors for Masonry | A-9.21.4.5.(2) |
CSA | CAN/CSA-A440-00 | Windows | A-9.7.2.1.(1) |
CSA | CAN/CSA-A440.1-00 | User Selection Guide to CSA Standard CAN/CSA-A440-00, Windows | A-9.7.2.1.(1) |
CSA | B44-00 | Safety Code for Elevators | A-3.5.2.1.(1) |
CSA | CAN/CSA-B149.1-00 | Natural Gas and Propane Installation Code | A-9.10.22. |
CSA | CAN/CSA-B365-01 | Installation Code for Solid-Fuel-Burning Appliances and Equipment | A-9.33.1.1.(2) A-9.33.5.3. |
CSA | C22.1-02 | Canadian Electrical Code, Part I | A-3.1.4.3.(1)(b)(i) A-9.10.22. |
CSA | CAN/CSA-C282-00 | Emergency Electrical Power Supply for Buildings | A-3.2.7.6.(1) |
CSA | CAN/CSA-F326-M91 | Residential Mechanical Ventilation Systems | A-6.2.2.2.(1) A-9.32.3.1.(1) A-9.32.3.5. A-9.32.3.7. A-9.32.3.8. A-9.33.6.14. |
CSA | CAN/CSA-O86-01 (Including Supplement CAN/CSA-O86S1-05) | Engineering Design in Wood | A-9.15.2.4.(1) A-9.23.4.2. |
CSA | CAN/CSA-O141-05 | Softwood Lumber | A-9.3.2.1.(1) |
CSA | O437.0-93 | OSB and Waferboard | A-9.23.14.4.(2) |
CSA | CAN/CSA-S6-00 | Canadian Highway Bridge Design Code | A-Table 4.1.5.10. |
CSA | CAN/CSA-S16-01 (Including Supplement CAN/CSA-S16S1-05) | Limit States Design of Steel Structures | A-4.1.5.12. A-4.3.4.1.(1) |
CSA | S304.1-04 | Design of Masonry Structures | A-5.1.4.1.(5)(b) and (c) |
CSA | CAN/CSA-S406-92 | Construction of Preserved Wood Foundations | A-9.13.4.1.(4) A-9.15.2.4.(1) |
CSA | CAN/CSA-Z32-04 | Electrical Safety and Essential Electrical Systems in Health Care Facilities | A-3.2.7.6.(1) |
CSA | CAN/CSA-Z240 MH Series-92 | Mobile Homes | A-1.1.1.1.(2) (1) |
CSA | A60.1-M1976 | Vitrified Clay Pipe | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | A257.1-03 | Non-Reinforced Circular Concrete Culvert, Storm Drain, Sewer Pipe, and Fittings | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | A257.2-03 | Reinforced Circular Concrete Culvert, Storm Drain, Sewer Pipe, and Fittings | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | CAN/CSA-B64.4.1-01 | Backflow Preventers, Reduced Pressure Principle Type for Fire Systems (RPF) | Table A-7.6.2.4.(2) |
CSA | CAN/CSA-B64.5.1-01 | Backflow Preventers, Double Check Valve Type for Fire Systems (DCVAF) | Table A-7.6.2.4.(2) |
CSA | CAN/CSA-B64.6.1-01 | Backflow Preventers, Dual Check Valve Type for Fire Systems (DuCF) | Table A-7.6.2.4.(2) |
CSA | CAN/CSA-B64.9-01 | Backflow Preventers, Single Check Valve Type for Fire Systems (SCVAF) | Table A-7.6.2.4.(2) |
CSA | CAN/CSA-B64.10.1-01 | Manual for the Maintenance and Field Testing of Backflow Prevention Devices | A-7.6.2.1.(3) |
CSA | CAN/CSA-B70-02 | Cast Iron Soil Pipe, Fittings, and Means of Joining | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | CAN/CSA-B125-01 | Plumbing Fittings | A-7.6.1.11.(1) |
CSA | B127.1-99 | Asbestos Cement Drain, Waste and Vent Pipe and Pipe Fittings | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | B127.2-M1977 | Components for Use in Asbestos Cement Building Sewer Systems | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | CAN/CSA-B137.1-02 | Polyethylene Pipe, Tubing, and Fittings for Cold-Water Pressure Services | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | CAN/CSA-B137.2-02 | PVC Injection-Moulded Gasketed Fittings for Pressure Applications | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | CAN/CSA-B137.3-02 | Rigid Polyvinyl Chloride (PVC) Pipe for Pressure Applications | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | CAN/CSA-B137.5-02 | Crosslinked Polyethylene (PEX) Tubing Systems for Pressure Applications | Table A-7.2.5., 7.2.6. and 7.2.7. A-7.2.5.7.(1) |
CSA | CAN/CSA-B137.6-02 | CPVC Pipe, Tubing, and Fittings for Hot- and Cold-Water Distribution Systems | Table A-7.2.5., 7.2.6. and 7.2.7. A-7.2.5.10. to 7.2.5.12. |
CSA | B137.9-99 | Polyethylene/Aluminum/Polyethylene Composite Pressure-Pipe Systems | Table A-7.2.5., 7.2.6. and 7.2.7. A-7.2.5.13.(1) |
CSA | CAN/CSA-B137.10-02 | Crosslinked Polyethylene/Aluminum/Crosslinked Polyethylene Composite Pressure-Pipe Systems | Table A-7.2.5., 7.2.6. and 7.2.7. A-7.2.5.14.(1) |
CSA | CAN/CSA-B137.11-02 | Polypropylene (PP-R) Pipe and Fittings for Pressure Applications | Table A-7.2.5., 7.2.6. and 7.2.7. A-7.2.5.15.(1) |
CSA | CAN/CSA-B181.1-02 | ABS Drain, Waste, and Vent Pipe and Pipe Fittings | Table A-7.2.5., 7.2.6. and 7.2.7. A-7.2.5.10. to 7.2.5.12. |
CSA | CAN/CSA-B181.2-02 | PVC Drain, Waste, and Vent Pipe and Pipe Fittings | Table A-7.2.5., 7.2.6. and 7.2.7. A-7.2.5.10. to 7.2.5.12. |
CSA | CAN/CSA-B181.3-02 | Polyolefin Laboratory Drainage Systems | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | CAN/CSA-B182.1-02 | Plastic Drain and Sewer Pipe and Pipe Fittings | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | CAN/CSA-B182.2-02 | PVC Sewer Pipe and Fittings (PSM Type) | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | CAN/CSA-B182.4-02 | Profile PVC Sewer Pipe and Fittings | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | CAN/CSA-B182.6-02 | Profile Polyethylene Sewer Pipe and Fittings For Leak-Proof Sewer Applications | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | CAN/CSA-B182.7-02 | Multilayer PVC Sewer Pipe (PSM Type) Having Reprocessed-Recycled Content | Table A-7.2.5., 7.2.6. and 7.2.7. |
CSA | G401-01 | Corrugated Steel Pipe Products | Table A-7.2.5., 7.2.6. and 7.2.7. |
CWC | 2004 | The Span Book | A-9.23.4.2. |
CWC | 2004 | Engineering Guide for Wood Frame Construction | A-9.4.1.1. A-9.4.1.1.(3) |
FCC | Project 43-10C-024 (1988) | Deflection Serviceability Criteria for Residential Floors | A-9.23.4.2.(2) |
FM Global | FM 2008 (1996) | Early Suppression – Fast Response Sprinklers | A-3.2.5.13.(7) |
HC | H46-2/90-156E | Exposure Guidelines for Residential Indoor Air Quality | A-9.13.4.6. Table A-9.25.1.2.B. |
HC | 1995 | Fungal Contamination in Public Buildings: A Guide to Recognition and Management | A-5.5.1.1. |
IRC | BPN 61 | Shear Resistance of Wood Frame Walls | A-9.23.10.2. |
IRC | CBD 222 | Airtight Houses and Carbon Monoxide Poisoning | A-9.33.1.1.(2) |
IRC | CBD 230 | Applying Building Codes to Existing Buildings | A-1.1.1.1.(1) (1) |
IRC | CBD 231 | Moisture Problems in Houses | A-9.25.3.1.(1) |
IRC | 1988 | Performance and Acceptability of Wood Floors – Forintek Studies | A-9.23.4.2.(2) |
ISO | 7731:2003 (E) | Ergonomics – Danger signals for public and work areas – Auditory danger signals | A-3.2.4.21.(1)(b) |
ISO | 8201:1987 (E) | Acoustics – Audible emergency evacuation signal | A-3.2.4.18.(2) |
McGraw-Hill | 1998 | National Plumbing Code Handbook, R. Dodge Woodson, Second Edition | A-7.6.3. |
NFPA | 2001 | Fire Protection Guide to Hazardous Materials | A-6.2.2.5.(1) |
NFPA | 2003 | Fire Protection Handbook, Nineteenth Edition | A-3.2.2.2.(1) A-3.6.2.7.(5) |
NFPA | 13-1999 | Installation of Sprinkler Systems | A-3.2.4.9.(2)(f) A-3.2.5.13.(1) A-3.2.5.13.(6) A-3.2.5.13.(7) A-3.2.5.14.(1) A-3.2.8.2.(3) |
NFPA | 13D-2002 | Installation of Sprinkler Systems in One-and Two-Family Dwellings and Manufactured Homes | A-3.2.5.13.(6) A-3.2.5.13.(7) A-3.2.5.14.(1) |
NFPA | 13R-2002 | Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height | A-3.2.5.13.(6) A-3.2.5.13.(7) A-3.2.5.14.(1) |
NFPA | 20-2003 | Installation of Stationary Pumps for Fire Protection | A-3.2.4.9.(2)(f) A-3.2.5.19.(1) |
NFPA | 30-2003 | Flammable and Combustible Liquids Code | A-6.2.2.5.(1) |
NFPA | 30A-2003 | Motor Fuel Dispensing Facilities and Repair Garages | A-6.2.2.5.(1) |
NFPA | 32-2003 | Drycleaning Plants | A-6.2.2.5.(1) |
NFPA | 33-2003 | Spray Application Using Flammable or Combustible Materials | A-6.2.2.5.(1) |
NFPA | 34-2003 | Dipping and Coating Processes Using Flammable or Combustible Liquids | A-6.2.2.5.(1) |
NFPA | 35-1999 | Manufacture of Organic Coatings | A-6.2.2.5.(1) |
NFPA | 36-2004 | Solvent Extraction Plants | A-6.2.2.5.(1) |
NFPA | 40-2001 | Storage and Handling of Cellulose Nitrate Film | A-6.2.2.5.(1) |
NFPA | 50A-1999 | Gaseous Hydrogen Systems at Consumer Sites | A-6.2.2.5.(1) |
NFPA | 50B-1999 | Liquefied Hydrogen Systems at Consumer Sites | A-6.2.2.5.(1) |
NFPA | 51-2002 | Design and Installation of Oxygen-Fuel Gas Systems for Welding, Cutting, and Allied Processes | A-6.2.2.5.(1) |
NFPA | 51A-2001 | Acetylene Cylinder Charging Plants | A-6.2.2.5.(1) |
NFPA | 61-2002 | Prevention of Fires and Dust Explosions in Agricultural and Food Products Facilities | A-6.2.2.5.(1) |
NFPA | 68-2002 | Venting of Deflagrations | A-3.6.2.7.(5) A-6.2.2.5.(1) |
NFPA | 69-2002 | Explosion Prevention Systems | A-3.6.2.7.(5) A-6.2.2.5.(1) |
NFPA | 80-1999 | Fire Doors and Fire Windows | A-3.1.8.1.(2) A-3.2.8.2.(3) |
NFPA | 80A-2001 | Protection of Buildings from Exterior Fire Exposures | A-3 |
NFPA | 81-1986 | Fur Storage, Fumigation and Cleaning | A-6.2.2.5.(1) |
NFPA | 85-2004 | Boiler and Combustion Systems Hazards Code | A-6.2.2.5.(1) |
NFPA | 86-2003 | Ovens and Furnaces | A-6.2.2.5.(1) |
NFPA | 88A-2002 | Parking Structures | A-6.2.2.5.(1) |
NFPA | 91-1999 | Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids | A-6.2.2.5.(1) |
NFPA | 96-2001 | Ventilation Control and Fire Protection of Commercial Cooking Operations | A-3.3.1.2.(2) A-6.2.2.5.(1) A-9.10.1.3.(1) |
NFPA | 204-2002 | Smoke and Heat Venting | A-6.2.2.5.(1) |
NFPA | 303-2000 | Marinas and Boatyards | A-6.2.2.5.(1) |
NFPA | 307-2000 | Construction and Fire Protection of Marine Terminals, Piers, and Wharfs | A-6.2.2.5.(1) |
NFPA | 409-2001 | Aircraft Hangars | A-6.2.2.5.(1) |
NFPA | 415-2002 | Airport Terminal Buildings, Fueling, Ramp Drainage, Loading Walkways | A-6.2.2.5.(1) |
NFPA | 484-2002 | Combustible Metals, Metal Powders, and Metal Dusts | A-6.2.2.5.(1) |
NFPA | 654-2000 | Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids | A-6.2.2.5.(1) |
NFPA | 655-2001 | Prevention of Sulfur Fires and Explosions | A-6.2.2.5.(1) |
NFPA | 664-2002 | Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities | A-6.2.2.5.(1) |
NIST | Building Materials and Structures Report BMS-79, 1941 | Water-Distributing Systems for Buildings, R. B. Hunter | A-7.6.3. |
NLGA | 2004 | Standard Grading Rules for Canadian Lumber (Interpretation Included) | A-9.3.2.1.(1) Table A-9.3.2.1.(1)A. A-9.3.2.8.(1) A-9.23.10.4.(1) |
NLGA | SPS-1-2003 | Fingerjoined Structural Lumber | A-9.23.10.4.(1) |
NLGA | SPS-3-2003 | Fingerjoined “Vertical Stud Use Only” Lumber | A-9.23.10.4.(1) |
NRCA | 5th Edition | Roofing and Waterproofing Manual | A-5.6.2.1. |
OMMAH | Supplementary Guidelines to the 1997 Ontario Building Code | A-9.8.8.2. | |
ONHWP | 1993 | Details of Air Barrier Systems for Houses | Table A-9.25.1.2.B |
ONHWP | 1995 | High-Rise Residential Construction Guide | A-5.6.2.1. |
SMACNA | 6th Edition | Architectural Sheet Metal Manual | A-5.6.2.1. |
TC | Transportation of Dangerous Goods Act and its Regulations | A-3.3.1.2.(1) | |
UL | ANSI/UL-199 (2003) | Automatic Sprinklers for Fire-Protection Service | A-3.2.5.13.(7) |
UL | ANSI/UL-1626 (2003) | Residential Sprinklers for Fire-Protection Service | A-3.2.5.13.(7) |
ULC | CAN/ULC-S101-04 | Fire Endurance Tests of Building Construction and Materials | A-3.1.5.12.(2)(e) B-3.2.6.5.(6)(b) |
ULC | CAN/ULC-S112-M90 | Fire Test of Fire-Damper Assemblies | Table B-3.2.6.5.(6)(b) |
ULC | CAN4-S113-79 | Wood Core Doors Meeting the Performance Required by CAN4-S104-77 for Twenty Minute Fire Rated Closure Assemblies | A-9.10.13.2.(1) |
ULC | CAN4-S124-M85 | Test for the Evaluation of Protective Coverings for Foamed Plastic | A-3.1.5.12.(2)(e) |
ULC | ULC-S332-93 | Burglary Resisting Glazing Material | A-9.6.8.1. |
ULC | CAN/ULC-S524-01 | Installation of Fire Alarm Systems | A-3.2.4.18.(10) |
ULC | CAN/ULC-S526-02 | Visible Signal Devices for Fire Alarm Systems | A-3.2.4.19.(1) |
ULC | CAN/ULC-S702-97 | Mineral Fibre Thermal Insulation for Buildings | A-5.10.1.1.(1) |
WCLIB | No. 17 (2004) | Standard Grading Rules | A-Table 9.3.2.1. |
WWPA | 1998 | Western Lumber Grading Rules | A-Table 9.3.2.1. |