1) Except as provided in Articles 6.3.1.2. and 6.3.1.3., the         									products of combustion from oil-, gas- and solid-fuel-burning
         									appliances shall be vented in         									conformance with the requirements in the applicable
         									appliance installation standard or regulation listed in         									Article            										6.2.1.4.
1) Rectangular masonry or concrete               										chimneys not more than 12 m in height shall conform to
         										Part 9. if
         									they serve
a) appliances with a combined total rated heat output of 120 kW or less, or
b)fireplaces.
2)  Masonry or concrete chimneys other         									than those described in Sentence (1) shall be designed and installed in         									conformance with the appropriate requirements in NFPA 211, “Chimneys,
         										Fireplaces, Vents, and Solid Fuel-Burning
         									Appliances.”
1) Single wall metal smoke stacks shall be designed and
         									installed in conformance with NFPA 211, “Chimneys,
         										Fireplaces, Vents, and Solid Fuel-Burning
         									Appliances.”
1) A lightning protection system, when provided, shall
         									conform to CAN/CSA-B72-M,
         										“Installation Code for Lightning Protection
         										Systems.”
1) Access ladders for chimneys,         									when provided, shall consist of steel or bronze rungs, built
         									into the walls of the chimneys.
2) Rungs for external ladders shall begin at not less
         									than 2.5 m from ground level.