Division B
Acceptable Solutions

Part 9 — Housing and Small Buildings

Section 9.32. Ventilation

9.32.1. General

9.32.1.1. Application
1) This Section applies to the ventilation of rooms and spaces in residential occupancies change beginby natural ventilation and to self-contained mechanical ventilation systems serving only one dwelling unit.change end

contentHistory

2) Mechanical ventilation systems other than self-contained systems serving single dwelling units shall conform to Part 6.

contentHistory

3) A storage garage for more than 5 motor vehicles shall be ventilated in accordance with Part 6.

contentHistory

4) change beginSystems used for ventilation shall conform to the energy efficiency requirements of change beginPart 10change end.change end

contentHistory

9.32.1.2. Required Ventilation
1) Intent Statementchange beginEvery dwelling unit shall incorporate
a) provisions for non-heating-season ventilation in accordance with Subsection 9.32.2., and
b) if supplied with electrical power, provisions for heating season ventilation in accordance with Subsection 9.32.3.change end

contentHistory

9.32.2. Non-Heating-Season Ventilation

9.32.2.1. Required Ventilation
1) Rooms or spaces in dwelling units shall be ventilated during the non-heating season by
a) natural ventilation in accordance with Article 9.32.2.2., or
b) a mechanical ventilation system conforming to change beginSubsection 9.32.3.change end

contentHistory

2) Where a habitable room or space is not provided with natural ventilation as described in change beginClause (1)(a), mechanical ventilation shall be provided to exhaust inside air from, or to introduce outside air to,change end that room or space at the rate of
a) one-half air change per hour if the room or space is mechanically cooled during the non-heating season, or
b) one air change per hour if it is not mechanically cooled during the non-heating season.
9.32.2.2. Non-Heating-Season Natural Ventilation
1) Intent StatementThe unobstructed openable ventilation area to the outdoors for rooms and spaces in residential buildings ventilated by natural means shall conform to Table 9.32.2.2.
Table 9.32.2.2.
Natural Ventilation Area
Forming part of Sentence 9.32.2.2.(1)
Location Minimum Unobstructed Area

Within a dwelling unit

Bathrooms or water-closet rooms

0.09 m2

Unfinished basement space

0.2% of the floor area

Dining rooms, living rooms, bedrooms, kitchens, combined rooms, dens, recreation rooms and all other finished rooms

0.28 m2 per room or combination room

Other than within a dwelling unit

Bathrooms or water-closet rooms

0.09 m2 per water closet

Sleeping areas

0.14 m2 per occupant

Laundry rooms, kitchens, recreation rooms

4% of the floor area

Corridors, storage rooms and other similar public rooms or spaces

2% of the floor area

Unfinished basement space not used on a shared basis

0.2% of the floor area

contentHistory

2) Intent StatementWhere a vestibule opens directly off a living or dining room within a dwelling unit, ventilation to the outdoors for such rooms may be through the vestibule.
3) Intent StatementOpenings for natural ventilation other than windows shall provide protection from the weather and insects.
4) Intent StatementScreening shall be of corrosion-resistant material.
9.32.2.3. Reserved

contentHistory

9.32.3. Heating-Season (Mechanical) Ventilation

(See Appendix A.)
9.32.3.1. Required Ventilation
1) Intent StatementEvery dwelling unit that is supplied with electrical power shall be provided with a mechanical ventilation system that change beginconforms tochange end
b) change beginPart 6, orchange end
c) change beginthis Subsection.change end
9.32.3.2. Design and Installation
1) Intent StatementAspects of mechanical ventilation systems not specifically described in this Subsection shall be designed, constructed and installed in accordance with good practice such as that described in the ASHRAE Handbooks and Standards, the HRAI Digest, the HRAI Residential Mechanical Ventilation Manual, the TECA Ventilation Guideline, the Hydronics Institute Manuals and the SMACNA manuals.
9.32.3.3. Required Ventilation Capacity
1) Intent StatementEvery dwelling unit shall be equipped with
a) a principal ventilation exhaust fan or ducted central ventilation system providing a minimum ventilation rate complying with Table 9.32.3.3.A, and
b) an exhaust fan with a minimum ventilation rate change begincomplying with Table 9.32.3.3.B in
i) every kitchen and
ii) every bathroom or water-closet room, unless the bathroom or water-closet room is served by a principle ventilation exhaust fan or ducted central ventilation system providing a minimum ventilation rate complying with Table 9.32.3.3.B.change end
2) Intent StatementWhere make-up air is required by Article 9.32.3.8. for change beginachange end principal ventilation exhaust fan, the maximum ventilation rate shall not exceed 55 l/s (110 cfm).
Table 9.32.3.3.A
Principal Exhaust Fan Ventilation Rate
Forming part of Clause 9.32.3.3.(1)(a)

Number of Bedrooms

Minimum Ventilation Rate
l/s
1 15
2 22
3 30
4 or more 35
Table 9.32.3.3.B
Bathroom/Kitchen Exhaust Ventilation Rate
Forming part of Clause 9.32.3.3.(1)(b)
Room Minimum Exhaust Rate change beginl/schange end
Intermittent Continuous
Kitchen 40 N/A
Bathroom 25 10
9.32.3.4. Principal Exhaust Fan Control
1) The principal ventilation exhaust fan shall
a) be controlled by an adjustable time control device capable of providing change beginnot less than 8 total hours of ventilation in not less than 2 periods per 24 hr day,change end and have a separate manual switch when serving both the principle ventilation exhaust function and a bathroom or water-closet room exhaust function, or
b) be designed to run continuously.
9.32.3.5. Principal change beginVentilationchange end Exhaust Fan Capacity Rating
1) Intent StatementThe principal ventilation exhaust fan capacity rating shall be based on air flow performance at 50 pa external static pressure as determined in accordance with
a) HVI 916 “Airflow Test Standard,” or
b) CAN/CSA-C260-M90, “Rating the Performance of Residential Mechanical Ventilating Equipment.”
9.32.3.6. Principal change beginVentilationchange end Exhaust Fan Sound Rating
1) Wall and ceiling fans used as a principal ventilation exhaust fan shall not have a sound rating exceeding
a) 1.5 Sone when controlled by an adjustable time control device, or
b) 1.0 Sone when designed to run continuously.
2) Intent StatementThe principal ventilation exhaust fan sound rating shall be determined change beginin accordance withchange end
a) HVI 915, “Procedure for Loudness Rating of Residential Fan Products,” or
b) CAN/CSA-C260-M90, “Rating the Performance of Residential Mechanical Ventilating Equipment.”
9.32.3.7. Kitchen and Bathroom change beginVentilation Exhaustchange end Fan Capacity Ratings
1) Kitchen and bathroom change beginventilationchange end exhaust fan capacity ratings shall be based on air flow performance at 50 pa external static pressure as determined in accordance with
a) change beginHVI 916, “Airflow Test Procedure,”change end or
9.32.3.8. Required Make-up Air for Principal change beginVentilationchange end Exhaust Fan
1) Make-up ventilation air shall be provided from the outdoors where
a) a dwelling unit contains a naturally aspirating fuel-fired vented appliance that is subject to back drafting (See Appendix A.), or
b) the dwelling unit is located in an area where soil gas is deemed to be a problem and incorporates no soil gas mitigation system
2) Where make-up air is required, change beginthe make-up air supplychange end shall
a) when not connected to a forced air heating duct system be sized in accordance with Table 9.32.3.8. for the rating of the principal exhaust fan installed, or
b) when connected to the return air duct of a forced air heating appliance,
i) have an outdoor air supply duct size of 100 mm diameter for smooth duct or 125 mm diameter for insulated flex duct or equivalent area, and
ii) have the outdoor air supply duct connected not more than 5 m or, unless a flow control device is used, less than 3 m upstream of the return air connection to the furnace cabinet,
iii) have the furnace air circulating fan interconnected with the principal ventilation exhaust fan, and
iv) where the winter design temperature is colder than -10°C, have a duct provided with a motorized damper also interconnected with the principal ventilation exhaust fan.
3) Where make-up ventilation air is provided as required change beginbychange end Clause (1)(a), in geographic areas where the winter design temperature is warmer than -10°C, it shall be delivered by
a) ducting into secondary areas such as a utility or storage room,
b) specially designed inlets in the upper sash or high on a wall, or
c) change beginanother method that avoids creating a cold draft or otherwise prevents occupants from blocking the ventilation.change end
4) Where make-up ventilation air is provided as required by Clause (1)(a) in geographic areas where the winter design temperature is colder than -10°C, it shall be delivered as described in Sentence (3) with the addition of heat.
5) Systems or ducts designed to provide combustion change beginair, dilution air or both for fuel-burningchange end appliances shall not be used to supply make-up air for ventilation systems.
Table 9.32.3.8.
Passive Make-up Air Opening Size
Forming part of Sentence 9.32.3.8.(2)
Maximum Exhaust change beginFanchange end Ventilation Rate Minimum Make-up Air Duct Size
Vent Area Vent change beginDiameterchange end
l/s cm2 mm
8 47 80
12 66 90
15 85 100
17 95 110
20 114 120
25 142 130
30 170 150
35 199 160
40 227 170
45 255 180
50 284 190
55 312 200
60 340 210
6) Reserved.
7) Reserved.
8) The provision of makeup air as described in Sentence (1) is not required for mechanical exhausting devices operating a subfloor depressurization system installed for the purpose of reducing the risk of radon ingress.
9.32.3.9. Exhaust and Make-up Air Ducts
1) Exhaust ducts serving wall or ceiling exhaust fans shall be sized in accordance with Table 9.32.3.9.
2) Exhaust ducts shall discharge directly to the outdoors.
3) Where an exhaust duct passes through or is located adjacent to an unheated space, the duct shall be insulated to not less than RSI 0.75.
4) Where a ventilation air supply duct passes through a heated space the duct shall be insulated to not less than RSI 0.75 and provided with an effective vapour barrier.
5) Where an exhaust duct exceeds 30 m in total equivalent length, using an equivalent length of 10 m for the exterior hood and 3 m for each 90 degree elbow, the duct shall be increased to the next diameter.
6) Ductwork for range hoods and range-top fans shall
a) be of noncombustible, corrosion-resistant material,
b) lead directly to the outdoors with no connections to other exhaust fans or ducts, and
c) be equipped with a grease filter at the intake end.
Table 9.32.3.9.
change beginMinimum Exhaust Duct Size
Forming part of Article 9.32.3.9.
Maximum Exhaust Fan Ventilation Rate, l/s Minimum Exhaust Duct Diameter, mm
Smooth Duct Flexible Duct
10 75 100
25 100 125
45 125 150
70 150 175change end
9.32.3.10. Protection from Weather
1) Outdoor air intakes and exhaust outlets shall be shielded from the weather, birds and rodents with hoods incorporating a screen of corrosion-resistant material with openings of 6 to 12 mm.
9.32.3.11. Exhaust Fan Installation
1) Installation of exhaust fans shall be in accordance with manufacturer's instructions for minimizing noise and vibration transmission and achieving the required sound rating.
9.32.3.12. Accessibility
1) Ventilation equipment shall be accessible for inspection, maintenance, repair and cleaning.
2) Except where the kitchen exhaust grille is located at least 1.2 m horizontally from the range change beginor equipped with an intake filter, kitchen exhaust ducts shall be designed and installed so that the entire duct can be cleaned.change end
9.32.3.13. Ventilation Ducts
1) Except as required by Sentence 9.32.3.9.(6), ventilation air ducts serving general exhaust and supply ventilation air are permitted to be of combustible material.
9.32.3.14. Interior Distribution
1) To facilitate ventilation air transfer, interior doors in dwelling units shall be undercut a minimum of 12 mm or the rooms shall be provided with a grille of equivalent area.

contentHistory

9.32.4. Additional Protection Against Depressurization

9.32.4.1. Protection Requirements
1) change beginAdditional make-up air for the actual appliance exhaust rate shall be provided for any appliance that discharges air to the exterior at an installed rate exceeding 0.5 air change per hour when it is located within a dwelling unit that contains a vented appliance that is subject to back drafting (Naturally Aspirating Fuel-Fired Vented Appliance). (See Appendix A.)change end

contentHistory

2) change beginWhere additional make-up air is required for appliances described in Sentence (1), it shall be provided by a supply fan rated to deliver outdoor air at the rate of the installed exhaust appliance.change end

contentHistory

3) The supply fan as required in change beginSentence (2)change end shall be interconnected with the exhaust fan for which make-up air is required.
4) The outdoor air required by Sentence (3) shall be
a) tempered to at least 1°C before being introduced to a normally unoccupied area of the dwelling unit, or
b) tempered to at least 12°C before being introduced to occupied areas either by passive transfer grille or directly from outside.
9.32.4.2. Carbon Monoxide Alarms
(See Appendix A.)
1) This Article applies to every building that contains a residential occupancy and that also contains
a) a fuel-burning appliance, or
2) Carbon monoxide (CO) alarms required by this Article shall
b) be equipped with an integral alarm that satisfies the audibility requirements of CAN/CSA-6.19, “Residential Carbon Monoxide Alarming Devices,”
c) have no disconnect switch between the overcurrent device and the CO alarm, where the CO alarm is powered by the dwelling unit's electrical system, and
d) be mechanically fixed at a height recommended by the change beginmanufacturer's instructionschange end.
3) change beginWhere a room contains a solid-fuel-burning appliance,change end a CO alarm conforming to CAN/CSA-6.19, “Residential Carbon Monoxide Alarming Devices,” shall be mechanically fixed
a) change beginat a height recommended by the manufacturer’s instructions where those instructions specifically mention solid-fuel-burning appliances, orchange end
b) change beginin the absence of specific instructions related to solid-fuel-burning appliances, on or near the ceiling.change end
4) Where a fuel-burning appliance is installed in a suite of residential occupancy, a CO alarm shall be installed
a) inside each bedroom, or
b) outside each bedroom, within 5 m of each bedroom door, measured following corridors and doorways.
5) Where a fuel-burning appliance is installed in a service room that is not in a suite of residential occupancy, a CO alarm shall be installed
a) in the service room, and
b) for every suite of residential occupancy that shares a wall or floor/ceiling assembly with that service room, either
i) inside each bedroom, or
ii) outside each bedroom, within 5 m of each bedroom door, measured following corridors and doorways.
6) For each suite of residential occupancy that shares a wall or floor/ceiling assembly with a storage garage or that is adjacent to an attic or crawl space to which the storage garage is also adjacent, a CO alarm shall be installed
a) inside each bedroom, or
b) outside each bedroom, within 5 m of each bedroom door, measured following corridors and doorways.