Division B
Acceptable Solutions
Part 9 — Housing and Small Buildings
Section 9.34. Electrical Facilities
9.34.1. General
9.34.1.1. Standard for Electrical Installations
1) Electrical installations, including the service capacity of the installation and
the number and distribution of circuits and receptacles, shall meet the requirements
of
“the Electrical Safety Regulation.”


2)
In addition to the requirements of Sentence (1), electrical installations in a one-family dwelling required to conform to Article 9.37.3.1. shall also comply with the following:

a) the electrical service size shall be based on the demand load calculated on the total area of the dwelling unit, provided that:
i) for each electrical range additional to the first range, 6 kw demand shall be added for a rating of 12 kw or less, plus 40 per cent of the amount by which the rating of the range exceeds 12 kw, and
ii) except for the first electrical range referred to in (a)(i), for each electrical appliance exceeding 1500 watts additional to those provided for one-family use, 100 per cent of the rating of such
appliance shall be added,
b) general circuit branch wiring may be interconnected between outlets located in the
principal dwelling and the secondary suite, and
c) except as permitted by Sentence 11.4.3.1.(5), a single panel board may supply electrical loads of the principal dwelling and the secondary suite, provided that it is located within the building in a common area accessible to all occupants of the building.

9.34.1.2. Required Facilities
1)
Where electrical services are available, electrical facilities shall be provided for every building in conformance with this Section.

9.34.1.3. Location of Equipment in Public Areas
1)
Entrance switches, meters, panel boxes, splitter boxes, time clocks and other similar equipment shall not be located in any public
area unless adequate precautions are taken to prevent interference
with the equipment.

9.34.1.4. Recessed Lighting Fixtures
1)
Recessed lighting fixtures shall not be located in insulated ceilings unless the fixtures are designed for such installations.

9.34.1.5. Wiring and Cables
1)
Except as required in Sentence (2),
optical fibre cables and
electrical wires and cables installed in buildings permitted to be of combustible construction shall



a)
not convey flame or continue to burn for more than 1 min when tested in conformance with the Vertical
Flame Test in Clause 4.11.1 of CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables,” (FT1 rating), or


b)
be located in


i)
totally enclosed noncombustible raceways (see A-3.1.4.3.(1)(b)(i) in Appendix A),


ii)
masonry walls,


iii)
concrete slabs, or


iv)
totally enclosed non-metallic raceways conforming to Clause 3.1.5.20.(1)(b).


2) 
Except as permitted in Sentence (3),
where a concealed space in a floor or ceiling assembly is used as a plenum,
electrical wires and cables with combustible insulation, jackets or sheathes that are used for the transmission of voice, sound or data and optical fibre cables installed
within the plenum shall conform to Clause 3.6.4.3.(1)(a).





3) 
Wires or cables within plenum spaces that are used for the transmission of signals in fire alarm, security,
radio, and television broadcasting, closed circuit television or community
television systems need not meet the requirements of Sentence (2).



9.34.2. Lighting Outlets
(See Appendix A.)9.34.2.1. Lighting of Entrances
1)
An exterior lighting outlet with fixture controlled by a wall switch located within the building shall be provided at every entrance to buildings of residential occupancy.

9.34.2.2. Outlets in Dwelling Units
1)
Except as provided in Sentence (2), a lighting outlet with fixture controlled by a wall switch shall be provided in kitchens, bedrooms, living rooms, utility rooms, laundry
rooms, dining rooms, bathrooms, water-closet rooms, vestibules and
hallways in dwelling units.

2)
Where a receptacle controlled by a wall switch is provided in bedrooms or living rooms, such rooms need not conform to the requirements
in Sentence (1).

9.34.2.3. Stairways
2) Except as provided in Sentence (3), 3-way wall switches located at the head and foot of every stairway shall be provided
to control at least one lighting outlet with fixture for stairways with 4 or more
risers in dwelling units.
3)
The stairway lighting for basements that do not contain finished space or lead to an outside entrance or built-in garage and which serve not more than one dwelling unit is permitted to be controlled by a single switch located at the head of the stairs.

9.34.2.4. Basements
1)
A lighting outlet with fixture shall be provided for each 30 m2 or fraction thereof of floor area in unfinished basements.

2)
The outlet required in Sentence (1) nearest the stairs shall be controlled by a wall switch located at the head of the stairs.

9.34.2.5. Storage Rooms
9.34.2.6. Garages and Carports
1)
A lighting outlet with fixture shall be provided for an attached, built-in or detached garage or carport.

2)
Except as provided in Sentence (3), outlets required in Sentence (1) shall be controlled by a wall switch near the doorway.

3)
Where the outlet and fixture required in Sentence (1) are ceiling mounted above an area not normally occupied by a parked car, or are wall mounted, a fixture with a built-in switch
accessible to an adult of average height is permitted to be used.

4)
Where a carport is lighted by a light at the entrance to a dwelling unit, additional carport lighting is not required.

9.34.2.7. Public and Service Areas
1)
Every public or service area in buildings shall be provided with lighting outlets with fixtures controlled by a wall switch or panel to illuminate every portion of such areas.

2)
When provided by incandescent lighting, illumination required in Sentence (1) shall conform to Table 9.34.2.7. (See Article 9.9.12.2. for lighting in means of egress.)

3)
When other types of lighting are used, illumination equivalent to that shown in Table 9.34.2.7. shall be provided.

Table 9.34.2.7. Lighting for Public Areas Forming part of Sentences 9.34.2.7.(2) and (3) | ||
Room or Space | Minimum Illumination, lx |
Minimum Lighting Power
Density, |
Storage rooms | 50 | 5 |
Service rooms and laundry areas |
200 | 20 |
Garages | 50 | 5 |
Public water closet rooms | 100 | 10 |
Service hallways and stairways | 50 | 5 |
Recreation rooms | 100 | 10 |
9.34.3. Emergency Lighting
9.34.3.1. Criteria for Emergency Lighting
1)
Emergency lighting shall conform to Subsection 9.9.12.
