Division B
Acceptable Solutions
Part 2 — Building and Occupant Fire Safety
Section 2.2. Fire Separations
2.2.1. General
2.2.1.1. Fire Separations
1) Where a building contains more than one major occupancy, such occupancies shall be separated from each other in conformance with the British Columbia Building Code.
2) Where rooms or spaces within a building contain a high-hazard industrial occupancy, such occupancy shall be separated from the remainder of the building by fire separations in conformance with this Code and the British Columbia Building Code.
3) Rooms, corridors, shafts and other spaces shall be separated where practicable by
fire separations conforming to the British Columbia Building Code.
2.2.1.2. Damage to Fire Separations
1)
Where fire separations are damaged so as to affect their integrity, they shall be repaired so that the
integrity of the fire separation is maintained.

2.2.2. Closures
2.2.2.1. Openings in Fire Separations
1) Openings in fire separations shall be protected with closures in conformance with the British Columbia Building Code.
2) Where closures in fire separations are replaced, the replacements shall be in conformance with
the British Columbia Building Code.
2.2.2.2. Damage to Closures
1)
Where closures are damaged so as to affect the integrity of their fire-protection rating, they shall be repaired so that their integrity is maintained
in conformance with Article 2.2.2.1.

2.2.2.3. Protective Guarding Devices
1)
Protective guarding devices shall be

a) provided where necessary to prevent damage to the mechanical components of doors in fire separations, and
b) installed so as not to interfere with the proper operation of the
doors.
2.2.2.4. Inspection and Maintenance
1)
Defects that interfere with the operation of closures in fire separations shall be corrected, and such closures shall be maintained to ensure that they are operable at all times by

a) keeping fusible links and other heat-actuated devices undamaged
and free of paint and dirt,
b) keeping guides, bearings and stay rolls clean and lubricated,
c) making necessary adjustments and repairs to door hardware and
accessories to ensure proper closing and latching, and
d) repairing or replacing inoperative parts of hold-open devices
and automatic releasing devices.
2) Doors in fire separations shall be inspected at intervals not greater than 24 h to ensure that they remain closed
unless the door is equipped with a hold-open device conforming to the British Columbia
Building Code.
3)
Doors in fire separations shall be operated at intervals not greater than one month to ensure that
they are properly maintained in accordance with Sentence (1), as specified in the fire safety plan prepared in conformance with Section 2.8.

4)
Closures in fire separations shall not be obstructed, blocked, wedged open,
or altered in any way that would prevent the intended operation of
the closure.

5)
Fire dampers and fire stop flaps shall be inspected at intervals not greater than 12 months to ensure that they are in place and are
not obviously damaged or obstructed.

2.2.2.5. Fire Door Signs
1)
Every door used as a closure with a required fire-protection rating shall have a permanent sign clearly displaying the words, “FIRE DOOR KEEP CLOSED” posted on the visible
side of the door when it is in the open position, except where the door
is


a) located between a corridor and an adjacent sleeping room in a hospital or a nursing home,
b) located between a corridor and an adjacent classroom,
d) fitted with an acceptable hold-open device designed to be released by a signal
from a fire detector, fire alarm system or sprinkler
system. (See Appendix A.)