1) Where unusual conditions exist, such as excessively
corrosive soil or water, only materials suited for use in such
locations shall be used.
2) Materials and equipment used in a drainage system where excessively corrosive wastes are present shall be suitable for the purpose.
1) Materials and equipment that have been used for a
purpose other than the distribution of potable water shall not be subsequently used in a potable water system.
1) Every length of pipe and every fitting shall
a)have cast, stamped or indelibly marked on it the maker's name or mark and the weight or class or quality of the product, or
b)be marked in accordance with the relevant standard.
2) Markings required in Sentence (1) shall be visible after installation.
1) Where the term pipe or piping is used, it shall also
apply to tube or tubing unless otherwise stated.
1) Piping, fittings and joints used in pressure sewer,
forcemain or sump pump discharge applications shall be capable
of withstanding at least one and one-half times the maximum
potential pressure.
1) The working pressure rating of a water service pipe shall not be less than the maximum water main pressure at their point of
connection as established by the water supply authority.
1) Every fixture shall have a smooth, hard, corrosion-resistant surface free from flaws and
blemishes that may interfere with cleaning.
1) Every fixture shall conform to CAN/CSA-B45 Series, “Plumbing Fixtures,” as
applicable.
2) Every vitreous china fixture shall conform to CAN/CSA-B45.1, “Ceramic Plumbing
Fixtures.”
3) Every enamelled cast-iron fixture shall conform to CAN/CSA-B45.2, “Enamelled Cast Iron Plumbing Fixtures.”
4) Every porcelain-enamelled steel fixture shall conform to CAN/CSA-B45.3, “Porcelain-Enamelled Steel Plumbing Fixtures.”
5) Every stainless steel fixture shall conform to CAN/CSA-B45.4, “Stainless Steel
Plumbing Fixtures.”
6) Every plastic fixture shall conform to CAN/CSA-B45.5, “Plastic Plumbing
Fixtures.”
7) Every hydromassage bathtub shall conform to
CAN/CSA-B45.10, “Hydromassage Bathtubs.”
8) Macerating toilet systems for single bathrooms
shall conform to CAN/CSA-B45.9, “Macerating Systems
and Related Components.”
1) Every shower receptor shall be constructed and
arranged so that water cannot leak through the walls or floor.
2) Not more than 6 shower heads shall be served by a
single shower drain.
3) Where 2 or more shower heads are served by a shower
drain, the floor shall be sloped and the drain located so that
water from one head cannot flow over the area that serves
another head. (See Appendix A.)
4) Except for column showers, when a battery of shower
heads is installed, the horizontal distance between 2 adjacent
shower heads shall be not less than 750 mm.
1) A dishwashing sink and a food preparation sink shall
not have concealed overflows. (See Appendix A.)
1) When a water closet is installed in a washroom for public use, it shall be of the elongated type and provided with a seat of the open front type.
1) Every water closet installed in a building shall be of a low consumption type which shall
a)conform with CSA B45 "Plumbing Fixtures", and
b)have an average water consumption not exceeding 6 litres per flush cycle.
1) Every urinal shall conform with CSA B45 “Plumbing Fixtures" and shall have an average
water consumption not exceeding 3.8 litres per flush cycle.
1) Except as provided for in Sentence (2), every trap shall
a)have a trap seal depth of not less than 38 mm,
b)be so designed that failure of the seal walls will cause exterior leakage, and
c)have a water seal that does not depend on the action of moving parts.
(See Appendix A.)2) The trap seal depth on fixtures draining to an acid waste system shall be a minimum of 50 mm.
3) Every trap that serves a lavatory, a sink or a laundry tray shall
a)be provided with a cleanout plug located at the lowest point of the trap and of the same material as the trap, except that a cast-iron trap shall be provided with a brass cleanout plug, or
b) be designed so that part of the trap can be removed for cleaning purposes.
(See Appendix A.)4) A bell trap shall not be installed in a drainage system. (See Appendix A.)
5) A drum trap shall not be used as a fixture trap unless required to serve as an interceptor and access for servicing is provided.
1) Every interceptor shall be designed so that it can be readily cleaned.
2) Every grease interceptor shall
a)be designed so that it does not become air bound, and
b)not have a water jacket.
1) Tubular metal or plastic traps conforming to CAN/CSA-B125, “Plumbing Fittings,”
shall be used only in accessible locations.
1) A T fitting shall not be used in a drainage system, except to connect a vent pipe.
2) A cross fitting shall not be used in a drainage system.
1) A single or double sanitary T fitting shall not be
used in a nominally horizontal soil-or-waste pipe, except that a single sanitary T fitting may be
used to connect a vent pipe.
2) A double sanitary T fitting shall not be used to
connect the trap arms of
a)back outlet water closets installed back-to-back, or
b)2 urinals where no cleanout fitting is provided above the connection.
1) Except as permitted in Sentence (2), 90° elbows of 4 inch size or less whose centre-line radius is less than the
size of the pipe shall not be used to join 2 soil-or-waste pipes.
2) For sanitary drainage systems of 4 inch size or less, 90° elbows shall only be permitted
a)to change the direction of piping from horizontal to vertical, in the direction of flow,
b)where a trap arm enters a wall, or
c)to connect trap arms as permitted by Sentence 7.5.6.3.(2).
1) Except as provided in Sentence (2), asbestos-cement pipe and its fittings for use in a drain, waste
or vent system shall conform to
a)CAN/CGSB-34.22, “Asbestos-Cement Drain Pipe,” or
b) CSA B127.1, “Asbestos Cement Drain, Waste and Vent Pipe and Pipe Fittings.”
2) Asbestos-cement pipe and fittings used underground
either outside a building or under a building shall conform to Sentence (1) or to
a) CAN/CGSB-34.9, “Asbestos-Cement Sewer Pipe,”
b)CAN/CGSB-34.23, “Asbestos-Cement House Connection Sewer Pipe,” or
c)CSA B127.2-M, “Components for Use in Asbestos Cement Building Sewer Systems.”
1) Asbestos-cement water pipe, couplings and bends shall
conform to CAN/CGSB-34.1, “Asbestos-Cement Pressure
Pipe.”
2) Asbestos-cement water pipe shall not be used above
ground.
1) Concrete pipe shall conform to
a)CSA A257.1, “Non-Reinforced Circular Concrete Culvert, Storm Drain, Sewer Pipe, and Fittings,” or
b)CSA A257.2, “Reinforced Circular Concrete Culvert, Storm Drain, Sewer Pipe, and Fittings.”
2) Joints with internal elastomeric gaskets shall conform
to CSA A257.3, “Joints for Circular Concrete Sewer and
Culvert Pipe, Manhole Sections, and Fittings Using Rubber
Gaskets.”
3) Concrete fittings fabricated on the site from lengths
of pipe shall not be used. (See Appendix A.)
4) Concrete pipe shall not be used above ground inside a
building.
5) Precast reinforced circular concrete manhole sections,
catch basins and fittings shall conform to CSA A257.4,
“Precast Reinforced Circular Concrete Manhole Sections,
Catch Basins, and Fittings.”
1) Vitrified clay pipe and fittings shall conform to
CSA A60.1-M, “Vitrified Clay Pipe.”
2) Couplings and joints for vitrified clay pipe shall
conform to CSA A60.3-M, “Vitrified Clay Pipe
Joints.”
3) Vitrified clay pipe and fittings shall not be used
except for an underground part of a drainage system.
1) Polyethylene water pipe, tubing and fittings shall
conform to Series 160 of CAN/CSA-B137.1, “Polyethylene
Pipe, Tubing, and Fittings for Cold-Water Pressure
Services.”
2) Polyethylene water pipe shall not be used except for a water service pipe.
3) Butt fusion fittings for polyethylene pipe shall
conform to ASTM D 3261, “Butt Heat Fusion Polyethylene
(PE) Plastic Fittings for Polyethylene (PE) Plastic Pipe and
Tubing.”
1) Polyethylene pipe used underground outside a building for the rehabilitation of existing drainage systems using trenchless technology shall conform to ASTM F 714,
“Polyethylene (PE) Plastic Pipe (SDR-PR) Based on
Outside Diameter,” and shall be HDPE 3408 and
SDR 11 or heavier. (See Appendix A.)
1) Crosslinked polyethylene pipe and its associated
fittings used in hot and cold potable water systems shall conform to CAN/CSA-B137.5, “Crosslinked Polyethylene (PEX)
Tubing Systems for Pressure Applications.” (See
Appendix A.)
1) PVC water pipe, fittings and solvent cement shall
a)conform to CAN/CSA-B137.3, “Rigid Polyvinyl Chloride (PVC) Pipe for Pressure Applications,” and
b)have a pressure rating of not less than 1 100 kPa.
2) PVC water pipe fittings shall conform to
a)ASTM D 2466, “Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40,” or
b)ASTM D 2467, “Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80.”
3) PVC injection-moulded gasketed fittings shall conform
to CAN/CSA-B137.2, “PVC Injection-Moulded Gasketed
Fittings for Pressure Applications.”
4) PVC water pipe and fittings referred to in Sentences (1), (2) and (3) shall not be used in a hot water system.
1) CPVC hot and cold water pipe, fittings and solvent
cements shall conform to CAN/CSA-B137.6, “CPVC Pipe,
Tubing, and Fittings for Hot- and Cold-Water Distribution
Systems.”
2) The design temperature and design pressure of a CPVC
piping system shall conform to Table 7.2.5.9.
Table
7.2.5.9. Maximum Permitted Pressure for CPVC Piping at Various Temperatures Forming Part of Sentence 7.2.5.9.(2) |
|
Maximum Temperature of Water, °C | Maximum Permitted Pressures, kPa |
---|---|
10 | 3 150 |
20 | 2 900 |
30 | 2 500 |
40 | 2 100 |
50 | 1 700 |
60 | 1 300 |
70 | 1 000 |
80 | 700 |
90 | 500 |
100 | 400 |
1) Plastic pipe, fittings and solvent cement used
underground outside a building or under a building in a drainage system shall conform to
a) ASTM F 628, “Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, Waste, and Vent Pipe With a Cellular Core,”
b)CAN/CSA-B181.1, “ABS Drain, Waste, and Vent Pipe and Pipe Fittings,”
c)CAN/CSA-B181.2, “PVC Drain, Waste, and Vent Pipe and Pipe Fittings,”
d)CAN/CSA-B182.1, “Plastic Drain and Sewer Pipe and Pipe Fittings,” with a pipe stiffness not less than 320 kPa,
e)CAN/CSA-B182.2, “PVC Sewer Pipe and Fittings (PSM Type),” with a pipe stiffness not less than 320 kPa,
f)CAN/CSA-B182.4, “Profile PVC Sewer Pipe and Fittings,” with a pipe stiffness not less than 320 kPa,
g)CAN/CSA-B182.6, “Profile Polyethylene Sewer Pipe and Fittings For Leak-Proof Sewer Applications,” with a pipe stiffness of not less than 320 kPa, or
h) CAN/CSA-B182.7, “Multilayer PVC Sewer Pipe (PSM Type) Having Reprocessed-Recycled Content,” with a pipe stiffness of not less than 320 kPa.
1) Solvent cement for transition joints shall conform to
a)CAN/CSA-B181.1, “ABS Drain, Waste, and Vent Pipe and Pipe Fittings,” or
b)CAN/CSA-B181.2, “PVC Drain, Waste, and Vent Pipe and Pipe Fittings.”
2) Transition solvent cement shall only be used for
joining an ABS drainage system to a PVC drainage system.
1) Plastic pipe, fittings and solvent cement used inside
or under a building in adrainage or venting system shall conform to
a) ASTM F 628, “Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, Waste, and Vent Pipe With a Cellular Core,”
b)CAN/CSA-B181.1, “ABS Drain, Waste, and Vent Pipe and Pipe Fittings,” or
c)CAN/CSA-B181.2, “PVC Drain, Waste, and Vent Pipe and Pipe Fittings.”
2) Requirements for combustible piping in relation to fire safety shall conform to Sentences 3.1.5.16.(1) and 9.10.9.6.(2) to (8), and Articles 3.1.9.4. and 9.10.9.7.
3) Where noncombustible piping pierces a fire separation or a fire stop, the requirements of fire stopping of Subsection 3.1.9., Sentence 9.10.9.6.(1) and Article 9.10.16.4. shall apply.
1) PE/AL/PE composite pipe and fittings shall conform to
CSA B137.9, “Polyethylene/Aluminum/Polyethylene
Composite Pressure-Pipe Systems.” (See Appendix A.)
2) PE/AL/PE pipe and fittings shall not be used in hot water systems.
1) PEX/AL/PEX composite pipe and fittings used in hot and
cold potable water systems shall conform to CAN/CSA-B137.10, “Crosslinked
Polyethylene/Aluminum/Crosslinked Polyethylene Composite
Pressure-Pipe Systems.” (See Appendix A.)
1) Polypropylene pipe and fittings used for hot and cold
potable water systems shall conform to CAN/CSA-B137.11, “Polypropylene (PP-R) Pipe and
Fittings for Pressure Applications.” (See Appendix A.)
1) Drainage piping, vent piping and fittings made of cast
iron shall conform to CAN/CSA-B70, “Cast Iron Soil Pipe,
Fittings, and Means of Joining.”
2) Cast-iron soil pipe and fittings shall not be used in
a water system.
1) Cast-iron fittings designed for use with
asbestos-cement pipe for drainage purposes shall conform to the
applicable requirements of
a)CSA B127.1, “Asbestos Cement Drain, Waste and Vent Pipe and Pipe Fittings,” or
b)CSA B127.2-M, “Components for Use in Asbestos Cement Building Sewer Systems.”
1) Threaded cast-iron drainage fittings shall conform to
ANSI/ASME B16.12, “Cast-Iron Threaded Drainage
Fittings.”
2) Threaded cast-iron drainage fittings shall not be used
in a water system.
1) Cast-iron water pipes shall conform to
ANSI/AWWA C151/A21.51, “Ductile-Iron Pipe,
Centrifugally Cast, for Water.”
2) Cement mortar lining for cast-iron water pipes shall
conform to ANSI/AWWA C104/A21.4, “Cement-Mortar Lining
for Ductile-Iron Pipe and Fittings for Water.”
3) Cast-iron fittings for cast-iron or ductile-iron water
pipes shall conform to ANSI/AWWA C110/A21.10,
“Ductile-Iron and Gray-Iron Fittings, 3 in. Through 48 in.
(75 mm Through 1200 mm), for Water and Other
Liquids.”
4) Rubber gasket joints for cast-iron and ductile-iron
pressure pipe for water shall conform to ANSI/AWWA
C111/A21.11, “Rubber-Gasket Joints for Ductile-Iron Pressure
Pipe and Fittings.”
1) Screwed cast-iron water fittings shall conform to
ANSI/ASME B16.4, “Gray Iron Threaded
Fittings.”
2) Screwed cast-iron water fittings used in a water system shall be cement-mortar lined or galvanized.
3) Screwed cast-iron water fittings shall not be used in
a drainage system.
1) Screwed malleable iron water fittings shall conform to
ANSI/ASME B16.3, “Malleable-Iron Threaded
Fittings.”
2) Screwed malleable iron water fittings used in a water system shall be cement-mortar lined or galvanized.
3) Screwed malleable iron water fittings shall not be
used in a drainage system.
1) Except as provided in Sentences (2) and (3), welded and seamless steel pipe shall not be used in a plumbing system.
2) Galvanized steel pipe is permitted to be used in a drainage system or a venting system above ground inside a building.
3) Galvanized steel pipe and fittings shall not be used
in a water distribution system except
a)in buildings of industrial occupancy as described in this By-law, or
b)for the repair of existing galvanized steel piping systems.
(See Appendix A.)4) Galvanized steel pipe and fittings shall conform to
ASTM A 53/A 53M, “Pipe, Steel, Black and Hot-Dipped,
Zinc-Coated, Welded and Seamless.”
1) Corrugated steel pipe and couplings shall conform to
CSA G401, “Corrugated Steel Pipe Products.”
2) Corrugated steel pipe shall only be used underground
outside a building in a storm drainage system.
3) Couplings for corrugated steel pipe shall be
constructed so that when installed they shall
a)maintain the pipe alignment,
b)resist the separation of adjoining lengths of pipe,
c)prevent root penetration, and
d)prevent the infiltration of surrounding material.
1) A sheet metal leader shall not be used except above ground outside a building.
1) Copper pipe shall conform to ASTM B 42,
“Seamless Copper Pipe, Standard Sizes.”
2) Brass pipe shall conform to ASTM B 43,
“Seamless Red Brass Pipe, Standard Sizes.”
1) Brass or bronze pipe flanges and flanged fittings
shall conform to ANSI/ASME B16.24, “Cast Copper Alloy
Pipe Flanges and Flanged Fittings.”
1) Brass or bronze threaded water fittings shall conform
to ANSI/ASME B16.15, “Cast Bronze Threaded Fittings,
Classes 125 and 250.”
2) Brass or bronze threaded water fittings shall not be
used in a drainage system.
1) Copper tube shall conform to
a)ASTM B 88, “Seamless Copper Water Tube,” or
b)ASTM B 306, “Copper Drainage Tube (DWV).”
2) Except as provided in Sentence (3), the use of copper tube shall conform to Table 7.2.7.4.
3) Copper tube shall not be used for the fixture drain or the portion of the vent pipe below the flood level rim of a flush-valve-operated urinal.
Table
7.2.7.4. Permitted Use of Copper Tube and Pipe Forming Part of Sentence 7.2.7.4.(2) |
||||||||
Type of Copper Tube or Pipe |
Plumbing Purposes | |||||||
---|---|---|---|---|---|---|---|---|
Water Service Pipe |
Water Distribution System | Building Sewer | Drainage System | Venting System | ||||
Under- ground |
Above- ground |
Under- ground |
Above- ground |
Under- ground |
Above- ground |
|||
K & L hard temper | N | N | P | P | P | P | P | P |
K & L soft temper | P | P | P | N | N | N | N | N |
M hard temper | N | N | N | N | N | P | N | P |
M soft temper | N | N | N | N | N | N | N | N |
DWV | N | N | N | N | N | P | N | P |
P = Permitted N = Not Permitted |
1) Solder-joint fittings for drainage systems shall conform to
a) ASME B16.23, “Cast Copper Alloy Solder Joint Drainage Fittings: DWV,” or
b)ANSI/ASME B16.29, “Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings – DWV.”
2) Solder-joint fittings for drainage systems shall not be used in a water system.
1) Except as provided in Sentence (2), solder-joint fittings for water systems shall conform to
a)ANSI B16.18, “Cast Copper Alloy Solder-Joint Pressure Fittings,” or
b)ANSI/ASME B16.22, “Wrought Copper and Copper Alloy Solder-Joint Pressure Fittings.”
2) Solder-joint fittings for water systems not made by casting or the wrought process
shall conform to the applicable requirements of ANSI
B16.18, “Cast Copper Alloy Solder-Joint Pressure
Fittings.”
1) Flared-joint fittings for copper tube water systems shall conform to ANSI/ASME B16.26, “Cast Copper Alloy Fittings for
Flared Copper Tubes.”
2) Flared-joint fittings for copper tube water systems not made by casting shall conform to the applicable requirements of ANSI/ASME
B16.26, “Cast Copper Alloy Fittings for Flared Copper
Tubes.”
1) Lead waste pipe and fittings shall not be used in a water system or as a building sewer.
2) When there is a change in size of a lead closet bend, the change shall be in the vertical section of
the bend or made in a manner that prevents the retention of
liquid in the bend.
1) Pipes and fittings to be used for drainage and venting
of acid and corrosive wastes shall conform to
a)ASTM A 518/A 518M, “Corrosion-Resistant High-Silicon Iron Castings,”
b)ASTM C 1053, “Borosilicate Glass Pipe and Fittings for Drain, Waste, and Vent (DWV) Applications,” or
c)CAN/CSA-B181.3, “Polyolefin Laboratory Drainage Systems.”
1) Cement mortar shall not be used for jointing.
1) Solders for solder joint fittings shall conform to
ASTM B 32, “Solder Metal.”
2) Solders and fluxes having a lead content in excess of
0.2% shall not be used in a potable water system.
3) Fluxes for soldered joints shall conform to
ASTM B 813, “Liquid and Paste Fluxes for
Soldering of Copper and Copper Alloy Tube.”
4) Except as provided in Sentence (5), joints in copper tubes installed underground shall be made
with either flared or compression fittings, or be brazed
using a brazing alloy within the American Welding Society's
AWS-BCuP range.
5) Compression fittings shall not be used underground
under a building.
1) Brass floor flanges shall conform to CSA
B158.1, “Cast Brass Solder Joint Drainage, Waste and Vent
Fittings.”
1) Every screw, bolt, nut and washer shall be of
corrosion-resistant materials when used
a)to connect a water closet to a water closet flange,
b)to anchor the water closet flange to the floor, or
c)to anchor the water closet to the floor.
1) Every plug, cap, nut or bolt that is intended to be
removable from a ferrous fitting shall be of a non-ferrous
material.
2) A cleanout fitting that, as a result of normal maintenance operations, cannot withstand the
physical stresses of removal and reinstallation or cannot ensure
a gas-tight seal shall not be installed.
1) Groove and shoulder type mechanical couplings for
pressure applications shall conform to CSA B242-M,
“Groove and Shoulder Type Mechanical Pipe
Couplings.”
2) Mechanical couplings for non-pressure applications
shall conform to CAN/CSA-B602, “Mechanical Couplings for
Drain, Waste, and Vent Pipe and Sewer Pipe.”
1) A saddle hub or fitting shall not be installed in drainage, venting or water systems. (See Appendix A.)
1) Supply and waste fittings shall conform to
CAN/CSA-B125, “Plumbing Fittings.”
2) Every lavatory faucet, kitchen sink faucet and shower head shall be of a low consumption
type which shall
a)conform with CSA-B125 "Plumbing Fittings", and
b)have a maximum flow rate for
i)lavatory and kitchen sink faucets of 8.3 litres per minute, and
ii)shower heads of 9.5 litres per minute.
1) Except as provided in Sentences (2) and (3), all valves supplying fixed-location shower
heads shall be individual pressure-balanced or
thermostatic-mixing valves conforming to CAN/CSA-B125, “Plumbing
Fittings.”
2) Individual pressure-balanced or
thermostatic-mixing valves shall not be required for showers
having a single tempered water supply that is controlled by a
master thermostatic-mixing valve conforming to CAN/CSA-B125,
“Plumbing Fittings.”
3) Deck-mounted, hand-held, flexible-hose spray
attachments are exempt from the requirements of Sentence (1).
4) Pressure-balanced and thermostatic-mixing valves shall
be
a)designed such that the outlet temperature does not exceed 49°C, or
b)equipped with high-limit stops that are adjusted to a maximum hot water setting of 49°C.
1) Every direct flush valve shall
a)open fully and close positively under service pressure,
b)complete its cycle of operation automatically,
c)be provided with a means of regulating the volume of water that it discharges, and
d)be provided with a vacuum breaker unless the fixture is designed so that back-siphonage cannot occur.
1) The orifice of every drinking fountain bubbler shall
a)be of the shielded type, and
b)direct the water upward at an angle of approximately 45°.
2) Every drinking fountain bubbler shall include a means
of regulating the flow to the orifice.
3) Bubblers shall be installed only on drinking
fountains. (See Appendix A.)
1) Except as provided in Sentence (2), back-siphonage preventers and backflow preventers shall conform to
a)CAN/CSA-B64.0, “Definitions, General Requirements, and Test Methods for Vacuum Breakers and Backflow Preventers,”
b)CAN/CSA-B64.1.1, “Vacuum Breakers, Atmospheric Type (AVB),”
c)CAN/CSA-B64.1.2, “Vacuum Breakers, Pressure Type (PVB),”
d)CAN/CSA-B64.2, “Vacuum Breakers, Hose Connection Type (HCVB),”
e)CAN/CSA-B64.2.1, “Vacuum Breakers, Hose Connection Type (HCVB) with Manual Draining Feature,”
f)CAN/CSA-B64.2.2, “Vacuum Breakers, Hose Connection Type (HCVB) with Automatic Draining Feature,”
g)CAN/CSA-B64.3, “Backflow Preventers, Dual Check Valve Type with Atmospheric Port (DCAP),”
h)CAN/CSA-B64.4, “Backflow Preventers, Reduced Pressure Principle Type (RP),”
i)CAN/CSA-B64.5, “Backflow Preventers, Double Check Valve Type (DCVA),”
j)CAN/CSA-B64.6, “Backflow Preventers, Dual Check Valve Type (DuC),”
k)CAN/CSA-B64.7, “Vacuum Breakers, Laboratory Faucet Type (LFVB),” or
l)CAN/CSA-B64.8, “Backflow Preventers, Dual Check Valve Type with Intermediate Vent (DuCV).”
2) Back-siphonage preventers for tank-type water closets (anti-siphon ballcocks) shall
conform to CAN/CSA-B125, “Plumbing Fittings.”
1) Temperature-relief, pressure-relief, combined
temperature- and pressure-relief, and vacuum-relief valves shall
conform to ANSI Z21.22/CSA 4.4-M, “Relief Valves for Hot
Water Supply Systems.”
1) Direct-acting water-pressure-reducing valves for
domestic water supply systems shall conform to
CAN/CSA-B356, “Water Pressure Reducing Valves for
Domestic Water Supply Systems.”
1) Equipment for solar heating of potable water shall conform to CAN/CSA-F379.1, “Solar Domestic Hot Water Systems (Liquid to Liquid Heat
Transfer).”
1) Flashing fabricated on-site for vent pipes shall be fabricated from
a)copper sheet not less than 0.33 mm thick,
b)aluminum sheet not less than 0.61 mm thick,
c)alloyed zinc sheet not less than 0.35 mm thick,
d)lead sheet not less than 2.16 mm thick,
e)galvanized steel sheet not less than 0.41 mm thick, or
f)polychloroprene (neoprene) not less than 2.89 mm thick.
2) Prefabricated flashing for vent pipes shall conform to CSA B272,
“Prefabricated Self-Sealing Roof Vent Flashings.”
(See Article 2.5.6.5. for location of vent pipe terminals.)
1) Water hammer arresters shall conform to
ASSE 1010, “Water Hammer Arresters.”
1) Air admittance valves shall conform to ASSE 1051, “Individual and Branch
Type Air Admittance Valves for Sanitary Drainage
Systems.” (See Appendix A.)