Division B
Acceptable Solutions

Part 6 — Heating, Ventilating and Air-conditioning

Section 6.3. Chimneys and Venting Equipment

6.3.1. General

6.3.1.1. Requirement for Venting
1) Intent StatementExcept as provided in Articles 6.3.1.2. and 6.3.1.3., the products of combustion from oil-, gas- and solid-fuel-burning appliances shall be vented in conformance with the requirements in the applicable appliance installation standard listed in Article 6.2.1.4.
6.3.1.2. Masonry or Concrete Chimneys
1) Intent StatementRectangular masonry or concrete chimneys not more than 12 m in height shall conform to Part 9 if they serve
a) appliances with a combined total rated heat output of 120 kW or less, or
b) fireplaces.
2) Intent StatementMasonry or concrete chimneys other than those described in Sentence (1) shall be designed and installed in conformance with the appropriate requirements in NFPA 211, “Chimneys, Fireplaces, Vents, and Solid-Fuel Burning Appliances.”
6.3.1.3. Metal Smoke Stacks
1) Intent StatementSingle wall metal smoke stacks shall be designed and installed in conformance with NFPA 211, “Chimneys, Fireplaces, Vents, and Solid-Fuel Burning Appliances.”
6.3.1.4. Lightning Protection Systems
1) A lightning protection system, when provided, shall conform to CAN/CSA-B72-M, “Installation Code for Lightning Protection Systems.”

contentHistory

6.3.1.5. Access Ladders
1) Intent StatementAccess ladders for chimneys, when provided, shall consist of steel or bronze rungs, built into the walls of the chimneys.
2) Intent StatementRungs for external ladders shall begin at not less than 2.5 m from ground level.