Division B
Acceptable Solutions
Part 6 — Heating, Ventilating and Air-conditioning
Section 6.2. Design and Installation
(See Part 10)6.2.1. General
6.2.1.1. Good Engineering Practice
(See Appendix A.)1)
Heating, ventilating and air-conditioning systems, including mechanical refrigeration equipment, shall be designed, constructed
and installed in conformance with good engineering practice such as
that described in, but not limited to,

a) the ASHRAE Handbooks and Standards,
b) the HRAI Digest,
c) the Hydronics Institute Manuals,
d) the NFPA Standards,
e) the SMACNA Manuals,
f) the Industrial Ventilation Manual published by the ACGIH,
g) CAN/CSA-B214, “Installation Code for Hydronic Heating Systems,”
6.2.1.2. Fire Safety Requirements
1)
The fire safety characteristics of heating, ventilating and air-conditioning systems shall comply with Subsection 3.6.5.

2)
Characteristics referred to in Sentence (1) include but are not limited to

a) use of combustible materials in duct systems,
b) flame-spread ratings and smoke-developed ratings of duct and pipe materials and coverings,
c) installation of equipment relative to property lines, and
d) requirements for fire dampers and fire stop flaps.
6.2.1.3. Structural Movement
(See Appendix A.)1) Mechanical systems and equipment shall be designed and installed to accommodate the maximum relative structural movement provided for in the construction of the building. (See Article 4.1.3.5., Subsection 4.1.8. and Sentence 4.1.3.3.(2) for information on the types of structural movements that may be encountered.)
6.2.1.4. Installation Standards
1) Except as provided in Articles 6.2.1.5. and 6.2.1.6., the installation of heating and air-conditioning equipment, including mechanical refrigeration equipment, and
including provisions for mounting, clearances and air supply, shall conform to the
requirements of
a)
CAN/CSA-B139, “Installation Code for Oil Burning Equipment,”
for the installation of oil burning equipment,


b)
the BC Safety Standards Act and the following of its regulations:

i) the Gas Safety Regulation for the installation of natural gas and propane burning equipment,
ii) the Electrical Safety Regulation, and
iii) the Power Engineers, Boiler, Pressure Vessel and Refrigeration Safety
Regulation for the installation of boilers, pressure vessels, pressure
piping and mechanical refrigeration, and
c) CAN/CSA B365, “Installation Code for Solid-Fuel Burning Appliances and Equipment,” for the installation of solid-fuel-burning
equipment
.

2)
For the purposes of Clause (1)(c), section 3.1 of CAN/CSA-B365, “Installation Code for Solid-Fuel-Burning Appliances and Equipment.” shall be read as though that section included the following paragraph:

a) an alternative safety approach under which a solid-fuel-burning boiler is accepted for use under section 10 of the
Safety Standards Act.

6.2.1.5. Fireplaces
1)
Fireplaces shall conform to the requirements of Section 9.22.

6.2.1.6. Heat Recovery Ventilators
1)
Heat recovery ventilators with rated capacities of not less than 25 L/s and not more than 200 L/s shall
be installed in accordance with Subsection 9.32.3.

6.2.1.7. Outdoor Design Conditions
1)
The outdoor conditions to be used in designing heating, ventilating and air-conditioning systems shall be determined in conformance with Subsection 1.1.3.

2) Reserved.
6.2.1.8. Installation - General
1)
Equipment requiring periodic maintenance and forming part of a heating, ventilating or air-conditioning system shall be installed
with provision for access for inspection, maintenance, repair and
cleaning. (See Appendix A.)

3)
Heating, ventilating or air-conditioning systems shall be protected from freezing if they may be adversely affected by freezing temperatures.

6.2.1.9. Expansion, Contraction and System Pressure
1)
Heating and cooling systems shall be designed to allow for expansion and contraction of the heat transfer fluid and to maintain the system
pressure within the rated working pressure limits of all components
of the system.

6.2.1.10. Asbestos
1)
Asbestos shall not be used in air distribution systems or equipment in a form or in a location where asbestos fibres could enter the air
supply or return systems.

6.2.1.11. Access Openings
1)
Any covering of an access opening through which a person could enter shall be openable from the inside without the use of keys where
there is a possibility of the opening being accidentally closed while
the system or equipment is being serviced.

6.2.2. Ventilation
6.2.2.1. Required Ventilation
1)
Except as provided in Sentence (3), all buildings shall be ventilated in accordance with this Part.

2)
Except in storage garages covered by Article 6.2.2.3., the rates at which outdoor air is supplied in buildings by ventilation systems shall be not less than the rates required by
ANSI/ASHRAE 62, “Ventilation for Acceptable Indoor Air Quality” (except Addendum n).



3)
Self-contained mechanical ventilation systems serving only one dwelling unit shall comply with

a) this Part, or
4)
For suites in buildings of 6 storeys or less in building height and required to conform to Part 10, the outdoor air required by Sentence (3) shall be supplied directly to each suite by mechanical ventilation ducting.
(See Appendix A.)

6.2.2.2. Natural Ventilation
1) Except as permitted by Sentence (2)
and except as required by Sentence 6.2.2.1.(4)
, the ventilation required by Article 6.2.2.1. shall be provided by mechanical ventilation, except that it can be provided by natural ventilation or a combination of natural and mechanical ventilation in


a) buildings of other than residential occupancy having an occupant load of not more than one person per 40 m2 during normal use,
b) buildings of industrial occupancy where the nature of the processes contained therein permits or requires the use of large openings in the building envelope even during the winter, and
c) seasonal buildings not intended to be occupied during the winter.
2)
Where climatic conditions permit, buildings containing occupancies other than residential occupancies may be ventilated by natural ventilation methods in lieu of mechanical ventilation where
engineering data demonstrates that such a method will provide the
required ventilation for the type of occupancy.

6.2.2.3. Ventilation of Storage Garages
1)
Except as provided in Sentences (4) and (6), an enclosed storage garage shall have a mechanical ventilation system designed to

a) limit the concentration of carbon monoxide to not more than 100 parts per million parts of air,
b) limit the concentration of nitrogen dioxide to not more than 3 parts per million parts of air, where the majority of the
vehicles stored are powered by diesel-fuelled engines, or
c) provide, during operating hours, a continuous supply of outdoor
air at a rate of not less than 3.9 L/s for each square
metre of floor area (see Article 3.3.1.20.).
(See also Sentence 3.3.5.4.(4).)2)
Mechanical ventilation systems provided in accordance with Clause (1)(a) shall be controlled by carbon monoxide monitoring devices, and systems provided in accordance with Clause (1)(b) shall be controlled by nitrogen dioxide or other acceptable monitoring devices. (See Appendix A.)

3)
Mechanical ventilation systems provided in accordance with Sentence (1) shall be designed such that the pressure in the storage garage is less than the pressure in adjoining buildings of other occupancy, or in adjacent portions of the same building having a different occupancy.

4)
In storage garages subject to the requirements of Sentences (1) and (2), where motor vehicles are parked by mechanical means, the ventilation requirements may be reduced by one half.

5)
Except as provided in Sentence (6), ticket and attendant booths of storage garages shall be pressurized with a supply of uncontaminated air.

6)
The requirements of Sentences (1) to (5) shall not apply to open-air storeys in a storage garage.

6.2.2.4. Reserved
1) Reserved.
6.2.2.5. Air Contaminants
1)
Air contaminants released within buildings shall be removed insofar as possible at their points of origin and shall not be permitted to accumulate in concentrations greater than
permitted in the Industrial Ventilation Manual published by the American
Conference of Governmental Industrial Hygienists.

2)
Systems serving spaces that contain sources of contamination and systems serving other occupied parts of the building but located in or running through spaces that contain sources of contamination shall be designed in such a manner as to
prevent spreading of such contamination to other occupied parts of
the building.

3)
Heating, ventilating and air-conditioning systems shall be designed to minimize the growth of micro-organisms. (See Appendix A.)

6.2.2.6. Hazardous Gases, Dusts or Liquids
1)
Except as provided in Subsection 6.2.12.,
systems serving spaces that contain hazardous gases, dusts or liquids shall be designed, constructed and installed to conform to the requirements of the applicable provincial
enactments or city by-laws
or, in the absence of such
enactments
or bylaws, to good engineering practice such as that described in the publications of the National Fire Protection Association and in the
Fire By-law
. (See Appendix A.)








2) 
When indoor piping for Class I flammable liquids is installed in a trench, the trench shall be


a) provided with positive ventilation to the outdoors, or
b) designed to prevent the accumulation of flammable vapours.

6.2.2.7. Commercial Cooking Equipment
1) Except as provided in Subsection 6.2.12., systems for the ventilation of commercial cooking equipment shall be designed, constructed
and installed to conform to NFPA 96, “Ventilation Control and Fire Protection of Commercial Cooking Operations,” except as required by
Sentences (3) and (4), Sentence 3.6.3.1.(1)
and Article 3.6.4.2.


2)
Fire protection systems for commercial cooking equipment referred to in Sentence (1) using vegetable oil or animal fat shall conform to

3)
The exhaust from a commercial cooking unit shall discharge through an ecology unit or acceptable equipment complying with Sentence (5), where the exterior wall termination of the exhaust is within 3 m of a lane, property line or street property line. (See Appendix A.)

4) The exhaust from a commercial cooking unit which is discharged from an exterior wall
termination shall not
a) be discharged in a location or manner which causes a concentrated stream of air to
fall directly onto pedestrians,
b) be discharged in a location or manner which causes exhaust to accumulate in an area
with outdoor seating, and
c) generate a sound pressure level which exceeds noise levels permitted by the Noise
Control By-law. (See Appendix A.)
5) Equipment provided in compliance with Sentence 6.2.2.7.(3) shall
a) remove 99.97% of the grease entering the equipment,
b) be of continuously welded 1.5 mm thick carbon steel or 1.1 mm stainless steel,
c) prevent the leakage of flame, smoke, or grease from the equipment at normal or abnormal
temperatures,
d) limit the temperature rise of adjacent combustible materials to no more than 97°C above room temperature, and
e) limit the temperature of exhaust air at the exhaust outlet to no more than 138��C.

6.2.2.8. Crawl Spaces and Attic or Roof Spaces
1)
Unconditioned and unoccupied crawl spaces and unconditioned and unoccupied attic or roof spaces shall be ventilated by natural or mechanical means as required by Part 5. (See Appendix A.)

6.2.3. Air Duct Systems
6.2.3.1. Application
1) This Subsection applies to the design, construction and installation of air duct distribution systems serving heating, ventilating and air-conditioning systems other
than those in dwelling units covered by Part 9.
6.2.3.2. Materials in Air Duct Systems
1)
All ducts, duct connectors, associated fittings and plenums used in air duct systems shall be constructed of materials as described in Article 3.6.5.1.

2)
Ducts that are used in a location where they may be subjected to excessive moisture shall have no appreciable loss of strength when
wet and shall be resistant to moisture-induced corrosion.

3)
All ductwork and fittings shall be constructed and installed as recommended in SMACNA Manuals and ASHRAE Standards.

4)
All duct materials shall be suitable for exposure to the temperature and humidity of the air being carried and shall be resistant to corrosion
caused by contaminants in the air being conveyed in the duct.

6.2.3.3. Connections and Openings in Air Duct Systems
1)
Air duct systems shall have

a) tight-fitting connections throughout, and
b) no openings other than those required for the proper operation and maintenance of the system.
2)
Access openings shall be provided in duct systems to allow the removal of material that may accumulate in plenums and ducts.

6.2.3.4. Duct Coverings and Linings
1)
Coverings, linings and associated adhesives and insulation used in air ducts, plenums and other parts of air duct systems shall comply with Article 3.6.5.4.

2)
Insulation and coverings on piping used in heating systems shall comply with Article 3.6.5.5.

3)
Duct linings shall be installed so that they will not interfere with the operation of volume or balancing dampers or of fire dampers, fire stop flaps and other closures.

6.2.3.5. Underground Ducts
1)
Underground ducts shall

a) be constructed and installed to provide interior drainage from and access to all low points,
b) not be connected directly to a sewer, and
c) be installed and constructed of materials recommended by ASHRAE
and SMACNA Standards and HRAI Manuals.
2)
A clean-out or pump-out connection shall be provided in an underground duct system at every low point of the duct system.

6.2.3.6. Fire Dampers
6.2.3.7. Smoke Detectors
1)
Air handling systems shall incorporate smoke detectors where and as required by Article 3.2.4.13.

6.2.3.8. Exhaust Ducts and Outlets
1)
Except as provided in Sentence (2), exhaust ducts of non-mechanical ventilating systems serving separate rooms or spaces shall not be combined.

2)
Exhaust ducts of non-mechanical ventilating systems serving similar occupancies may be combined immediately below the point of final delivery to the outdoors, such as at the base of a roof ventilator.

3)
Exhaust ducts of ventilating systems shall have provision for the removal of condensation where this may
be a problem.

5)
Except as permitted in Sentence (6), exhaust systems shall discharge directly to the outdoors. (See Appendix A.)

6)
Exhaust systems are permitted to exhaust into a storage garage, provided

a) they serve rooms that are accessible only from that storage garage,
b) the exhaust contains no contaminants that would adversely affect
the air quality in the storage garage (see Appendix A), and
c) they are designed in accordance with Sentence 6.2.3.9.(3).
(See Appendix A.)7)
Exhaust ducts connected to laundry drying equipment shall be

a) independent of other exhaust ducts,
b) accessible for inspection and cleaning, and
c) constructed of a smooth corrosion-resistant material.
8) 
Where collective venting of multiple installations of laundry-drying equipment is used, the ventilation system shall


a) be connected to a common exhaust duct that is vented by one central exhaust fan and incorporates one central lint trap,
b) include an interlock to activate the central exhaust fan when
laundry-drying equipment is in use, and
c) be provided with make-up air.
9)
Exhaust ducts or vents connected to laundry-drying equipment shall discharge directly to the outdoors.


10)
Except as provided in Sentence (12) and except for self-contained systems serving individual dwelling units, exhaust ducts serving rooms containing water closets, urinals, basins,
showers or slop sinks shall be independent of other exhaust ducts.

11)
Except as provided in Sentence (12) and except for self-contained systems serving individual dwelling units, exhaust ducts serving rooms containing residential cooking equipment
shall be independent of other exhaust ducts.

12)
Two or more exhaust systems described in Sentences (10) and (11) may be interconnected or connected with exhaust ducts serving other areas of the building, provided

a) the connections are made at the inlet of an exhaust fan, and all interconnected systems are equipped with suitable back pressure
devices to prevent the passage of odours from one system to another
when the fan is not in operation, or
b) the exhaust ducts discharge to a shaft that is served by an exhaust fan having a capacity that is
equal to or greater than the combined capacity of the exhaust fans
discharging to the plenum multiplied by the operation diversity factor, provided that the exhaust fan serving
the shaft operates continuously (see Appendix A).
13)
Where exhaust ducts containing air from conditioned spaces pass through or are adjacent to unconditioned spaces, the ducts shall be constructed
to prevent condensation from forming on the inside or outside of the
ducts.

14)
Where an exhaust duct system is used for smoke removal in a high building, the requirements of Article 3.2.6.6. shall apply.

15)
Where exhaust duct systems from more than one fire compartment are connected to an exhaust duct in a vertical service space, the requirements of Article 3.6.3.4. shall apply.

6.2.3.9. Interconnection of Systems
1)
In a
care or
residential occupancy, air from one suite shall not be circulated to any other suite or to a public corridor.



2)
Except as permitted by Sentences (3) and 6.2.3.8.(6), air duct systems serving storage garages shall not be directly interconnected with other parts of the building.

3) Exhaust ducts referred to in Sentence 6.2.3.8.(10) may exhaust through an enclosed storage garage prior to exhausting to the outdoors, provided
a) the storage garage's exhaust system runs continuously,
b) the capacity of the storage garage's exhaust system is equal to or exceeds the volume of the exhaust entering the garage,
and
c) a leakage rate 1 smoke/fire damper rated in accordance with
CAN/ULC-S112.1, “Leakage Rated Dampers for Use in Smoke Control Systems,”
is provided near the duct outlet location in the storage garage to prevent air from the storage garage from entering the exhaust ductwork system in the event the
building's exhaust fan is shut down.


6.2.3.10. Ducts in Exits
1)
Where ducts penetrate fire separations separating exits from the remainder of the building, they shall be in accordance with Article 3.4.4.4.

6.2.3.11. Makeup Air
(See A-6.2.1.1. in Appendix A.)1)
In ventilating systems that exhaust air to the outdoors, provision shall be made for the admission of a supply of makeup air in sufficient
quantity so that the operation of the exhaust system and other exhaust
equipment or combustion equipment is not adversely affected.

2)
Makeup air facilities required by Sentence (1) shall be interlocked with the exhaust devices they serve so that both operate together.

3)
Where makeup air facilities are intended to introduce air directly from the outdoors to occupied parts of the building in winter, they shall incorporate means of tempering that air to maintain the indoor design temperature.

6.2.3.12. Supply, Return, Intake and Exhaust Air Openings
1)
Supply, return and exhaust air openings located less than 2 m above the floor in rooms or spaces in buildings shall be protected by grilles having openings of a size that will not allow the passage of a 15 mm diam
sphere.

2)
Outdoor air intakes and exhaust outlets on the exterior of buildings shall be designed or located so that air entering the building system does not contain more contaminants than the normal exterior air of the locality
in which the building is situated.

3)
Exterior openings for outdoor air intakes and exhaust outlets shall be shielded from the entry of snow and rain and shall be fitted
with corrosion-resistant screens of mesh having openings not larger
than 15 mm, except where experience has shown that climatic
conditions require larger openings to prevent the screen openings
from icing over.

4)
Screens required in Sentence (3) shall be accessible for maintenance.

5)
Combustible grilles, diffusers and other devices covering supply, return, intake and exhaust openings
shall comply with Article 3.6.5.7.

6.2.3.13. Filters and Odour Removal Equipment
1)
Air filters for air duct systems shall conform to the requirements for Class 2 air filter units as described in ULC-S111, “Fire Tests for Air Filter Units.”

2)
When electrostatic-type filters are used, they shall be installed so as to ensure that the electric circuit is automatically de-energized
when filter access doors are opened or, in dwelling units, when the furnace circulation fan is not operating.

3)
When odour removal equipment of the adsorption type is used, it shall be

a) installed to allow access so that adsorption material can be
reactivated or renewed, and
b) protected from dust accumulation by air filters installed on
the inlet side.
4)
Facilities for flushing and drainage shall be provided where filters are designed to be washed in place.

6.2.3.14. Air Washers and Evaporative Cooling Sections or Towers
1)
The filter and water evaporation medium of every air washer and evaporative cooling section enclosed within a building shall be made of noncombustible material.

2)
Sumps for air washers and evaporative cooling sections shall be constructed and installed so that they can be flushed and drained.

3)
Evaporative cooling sections or towers shall comply with the requirements of NFPA 214, “Water-Cooling Towers.”

6.2.3.15. Fans and Associated Air-Handling Equipment
1)
Fans for heating, ventilating and air-conditioning systems shall be located and installed so that their operation

a) does not adversely affect the draft required for proper operation
of fuel-fired appliances, and
2)
Fans and associated air-handling equipment, such as air washers, filters and heating and cooling units, when installed on the roof
or elsewhere outside the building, shall be of a type designed for outdoor use.

6.2.3.16. Vibration Isolation Connectors
1)
Vibration isolation connectors in air duct systems shall comply with Article 3.6.5.2.

6.2.3.17. Tape
1)
Tape used for sealing joints in air ducts, plenums and other parts of air duct systems shall comply with Article 3.6.5.3.

6.2.3.18. Insulation and Coverings
1)
Insulation and coverings on pipes shall comply with Article 3.6.5.5.

6.2.3.19. Clearance of Ducts and Plenums
6.2.3.20. Return-Air System
1)
Return-air systems shall comply with Article 3.6.5.8.

2)
Where a ceiling space is used as a return-air plenum, the requirements of Article 3.6.4.3. shall apply.

6.2.4. Carbon Monoxide Alarms
6.2.4.1. Carbon Monoxide Alarms
1)
This Article applies to every building that contains a residential occupancy,
a care occupancy with individual suites, or a care occupancy containing sleeping rooms not within a suite,
and that also contains



a) a fuel-burning appliance, or
b) a storage garage.
2)
Carbon monoxide (CO) alarms required by this Article shall

b) be equipped with an integral alarm that satisfies the audibility requirements of CAN/CSA-6.19, “Residential Carbon Monoxide Alarming Devices,”
c) have no disconnect switch between the overcurrent device and the CO alarm, where the CO alarm is powered by the electrical system
serving the
suite
(see Appendix A), and


d) be mechanically fixed at a height above the floor as recommended
by the manufacturer.
3)
Where a fuel-burning appliance is installed in a suite of residential occupancy
or in a suite of care occupancy
, a CO alarm shall be installed



a) inside each bedroom, or
b) outside each bedroom, within 5 m of each bedroom door, measured following corridors and doorways.
4) Where a fuel-burning appliance is installed in a service room that is not in a suite of residential occupancy
nor in a suite of care occupancy
, a CO alarm shall be installed


a) either inside each bedroom, or if outside, within 5 m of each bedroom door, measured following corridors and doorways, in every suite of residential occupancy
or suite of care occupancy
that shares a wall or floor/ceiling assembly with the service room, and


b) in the service room.
5)
For each suite of residential occupancy
or suite of care occupancy
that shares a wall or floor/ceiling assembly with a storage garage or that is adjacent to an attic or crawl space to which
the storage garage is also adjacent, a CO alarm shall be installed



a) inside each bedroom, or
b) outside each bedroom, within 5 m of each bedroom
door, measured following corridors and doorways.
6.2.5. Heating Appliances, General
6.2.5.1. Location of Appliances
1)
Except for appliances installed in dwelling units, fuel-fired heating appliances shall be located, enclosed or separated from the remainder of the building in conformance with Section 3.6. (See also Subsection 9.10.10.)

6.2.5.2. Appliances Installed Outside the Building
1)
Fuel-fired appliances installed outside a building shall be designed and constructed for outdoor use.

6.2.6. Incinerators
6.2.6.1. Applicable Standard
1) The design, construction, installation and alteration of every indoor incinerator shall conform to NFPA 82, “Incinerators and Waste and Linen Handling Systems and Equipment.”
6.2.7. Unit Heaters
6.2.7.1. Clearances
1)
Every unit heater using either steam or hot water as the heating medium shall be installed such that the
clearances between the appliance and adjacent combustible material conform to Table 6.2.9.3.

6.2.8. Radiators and Convectors
6.2.8.1. Lining or Backing
1)
A noncombustible lining or backing shall be provided for every steam or hot water radiator and convector

a) located in a recess or concealed space, or
b) attached to the face of a wall of combustible construction.
2)
Every steam or hot water radiator and convector shall be installed so as to conform to the clearance requirements of Table 6.2.9.3.

6.2.9. Piping for Heating and Cooling Systems
6.2.9.1. Piping Materials and Installation
1)
Piping shall be made from materials designed to withstand the effects of temperatures and pressures that may occur in the system.
(See Articles 3.1.5.16., 3.1.9.1., 9.10.9.6. and 9.10.9.7. for fire safety requirements.)

2)
Every pipe used in a heating or air-conditioning system shall be installed to allow for expansion and contraction due to temperature
changes.

3)
Supports and anchors for piping in a heating or air-conditioning system shall be designed and installed to ensure that undue stress
is not placed on the supporting structure.

6.2.9.2. Insulation and Coverings
1)
Insulation and coverings on pipes shall be composed of material that will withstand deterioration from softening, melting, mildew
and mould at the operating temperature of the system.

2)
Exposed piping or equipment subject to human contact shall be insulated so that the temperature of the exposed surface does not
exceed 70°C. (See Appendix A.)

6.2.9.3. Clearances
1)
Clearances between combustible material and bare pipes carrying steam or hot water shall conform to Table 6.2.9.3.

Table 6.2.9.3. Clearance Between Steam or Hot Water Pipes and Combustible Material Forming part of Articles 6.2.7.1. and 6.2.9.3., and Sentence 6.2.8.1.(2) | |
Steam or Water Temperature, °C | Minimum Clearance, mm |
Up to 95 | No clearance |
Above 95 to 120 | 15 |
Above 120 | 25 |
6.2.9.4. Surface Temperature
1)
The exposed surface temperature of a steam or hot water radiator shall not exceed 70°C unless precautions are taken to
prevent human contact.

6.2.9.5. Protection
1) Where a pipe carrying steam or hot water at a temperature above
120°C passes through a combustible floor, ceiling or wall, the construction shall be protected by a sleeve of metal or other noncombustible material not less than 50 mm larger in diameter than the pipe.
6.2.9.6. Piping in Shafts
1)
Where piping for heating or air-conditioning systems is enclosed in a shaft, the requirements of Article 3.6.3.1. for shafts shall apply.

6.2.10. Refrigerating Systems and Equipment for Air-conditioning
6.2.10.1. Cooling Units
1)
Where a cooling unit is combined with a fuel-fired furnace in the same duct system, the cooling unit shall be installed

a) in parallel with the heating furnace,
c) downstream of the furnace provided the cooling unit is designed to prevent excessive temperature or pressure
in the refrigeration system.
6.2.11. Storage Bins
6.2.11.1. Storage Bins
1)
Service pipes passing through a storage bin for solid fuel shall be protected or so located as to avoid damage to the pipes.

2)
Except for fuel-thawing pipes, every pipe designed to operate at a temperature of 50°C or above shall be located where
solid fuel cannot be stored in contact with it.

4)
Storage bins for solid fuel shall be designed and constructed so that the air temperature in the bin or the surface temperature
of any part of the floor or walls is below 50°C.

6.2.11.2. Ash Storage Bins
1)
Every ash storage bin shall be constructed of noncombustible material.

2)
Every opening in an ash storage bin shall be protected by a tight-fitting metal door with metal frame securely fastened to the
bin.

6.2.12.
Ventilation for Laboratories
6.2.12.1. Application
1) This Subsection applies to laboratories where dangerous goods, including flammable liquids and combustible liquids, are used in normal laboratory operations in quantities or in a manner that creates a fire or explosion hazard.
6.2.12.2. General Ventilation
1)
A laboratory shall be provided with continuous mechanical ventilation designed to ensure that dangerous goods vapours and particles

a) do not accumulate in the laboratory,
b) are prevented from migrating to other parts of the building,
c) do not accumulate in the ventilation system,
d) are exhausted to the outdoors, and
e) are not returned to the building.
2)
A ventilation system required by this Subsection shall be provided with monitoring devices to

a) indicate that the ventilation system is in operation, and
b) sound an alarm if the ventilation system is malfunctioning.
3) A ventilation system required by this Subsection shall be maintained in
conformance with Article 5.5.4.1. of Division B of the
Fire By-law
.


6.2.12.3. Enclosure Exhaust Ventilation
1) The ventilation system for a power-ventilated enclosure required by Sentence
5.5.4.2.(1) of Division B of the
Fire By-law
shall


a) conform to NFPA 91, “Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids,”
b) provide continuous exhaust ventilation at an air velocity sufficient to
prevent the accumulation of combustible or reactive deposits in the power-ventilated enclosure and its exhaust duct system,
c) confine dangerous goods vapours and particles to the area where they are generated and exhaust them to the outdoors,
d) not return the exhausted air to the building, and
e) be provided with well identified control switches that are
i) located outside of the power-ventilated enclosure, and
ii) readily accessible in case of an emergency.
6.2.12.4. Enclosure Construction
1) The power-ventilated enclosure required by Sentence 5.5.4.2.(1) of Division B of
the
Fire By-law
and its exhaust duct system shall


a) except as provided in Sentences (2) and (3), be constructed of noncombustible materials compatible with and chemically resistant to the dangerous goods vapours and particles being exhausted, and
b) be provided with access doors to permit inspection and maintenance of the fan
assembly and exhaust ducts.
2)
Combustible materials are permitted in systems described in Clause (1)(a) if

a) such materials are required by the corrosive or reactive properties of the dangerous goods being used, and
b) their flame-spread rating is not more than 25.
3)
The flame-spread rating required by Sentence (2) is permitted to be greater than 25 if an automatic fire suppression system is provided inside the
power-ventilated enclosure and its exhaust duct system.

