Division B
Acceptable Solutions
Part 9 — Housing and Small Buildings
Section 9.10. Fire Protection
9.10.1. Definitions and Application
9.10.1.1. Sloped Roofs
1) 
For the purposes of this Section, roofs with slopes of 60° or more to the horizontal that are adjacent to a room or space intended for
occupancy shall be considered as a wall.
9.10.1.2.
Commissioning of Life Safety and Fire Protection Systems
1) Where life safety and fire protection systems are installed to comply with the
provisions of this

By-law

or the

Fire By-law

, the commissioning of these integrated systems must be performed as a whole to ensure the proper
operation and inter-relationship of the systems. (See
A-3.2.4.6.(1) in Appendix A.)


BC2012 2012-01-01 R1NC2010 2010-01-01 R1
1) Where life safety and fire protection systems are installed to comply with the
provisions of this By-lawCode or the British Columbia Fire By-lawCode, the commissioning
of these integrated systems must be performed as a whole to ensure the proper
operation and inter-relationship of the systems. (See A-3.2.4.6.(1) in Appendix A.)
1) 
Where life safety and fire protection systems are installed to comply with the provisions of this
By-lawCode or the
Fire By-law NFC, the commissioning
of these integrated systems must be performed as a whole to ensure the proper
operation and inter-relationship of the systems. (See A-3.2.4.6.(1) in Appendix A.)
9.10.1.3. Items under Part 3 Jurisdiction
4) 
Where rooms or spaces are intended for the storage, manufacture or use of hazardous or explosive material, such rooms or spaces shall
conform to
Part 3.
(See A-3.3.1.2.(1) in Appendix A.) 5) 
Except as provided in
Article 3.3.5.8., facilities for the dispensing of fuel shall not be installed in any
building.
8)
Sprinkler systems shall be designed, constructed and installed in conformance with
Articles 3.2.5.12. to 3.2.5.15. and 3.2.5.17.
NC2010 2010-01-01 R1
8) 
Sprinkler systemsSprinklersystems shall be designed, constructed and installed in conformance with Articles 3.2.5.12. to 3.2.5.15. and 3.2.5.17.
9.10.1.4. Items under Part 6 Jurisdiction
1) 
In kitchens containing commercial cooking equipment used in processes producing grease-laden vapours, the equipment shall be designed
and installed in conformance with
Article 6.2.2.7. (See
Appendix A.)
9.10.2. Occupancy Classification
9.10.2.1. Occupancy Classification
9.10.2.2. Custodial, Convalescent and Residential Care Homes
1) 
Children's custodial homes and convalescent homes for ambulatory occupants living as a single housekeeping unit in a
dwelling unit with sleeping accommodation for not more than 10 persons are permitted to be classified
as

Group C,
residential occupancies.

2) A care facility accepted for residential use pursuant to provincial legislation is permitted to be classified as a
residential occupancy provided
a) the occupants live

as a single housekeeping unit in a
dwelling unit
with sleeping accommodation for not more than 10 persons,

NC2010 2010-01-01 R1
9.10.2.2. Custodial, Convalescent and Residential Care HomesCustodial and Convalescent Homes
1) 
Children's custodial homes and convalescent homes for ambulatory occupants living as a single housekeeping unit in a
dwelling unit with
sleeping accommodation for not more than 10 persons are permitted to be classified
as
Group C, residential occupanciesresidential occupancies
(Group C).
2) A care facility accepted for residential use pursuant to provincial legislation is
permitted to be classified as a
residential occupancy
provided
a) the occupants live as a single housekeeping unit in a dwelling unit with sleeping accommodation for not more than 10
persons,
b) interconnected smoke alarms are installed in each
sleeping room in addition to the requirements of Article 9.10.19.2.,
c) emergency lighting is provided in conformance with Article 9.9.12.3., and
d) the building is sprinklered throughout.
9.10.2.3.
Group A, Division 2, Low Occupant Load
9.10.2.4. Major Occupancies above Other Major Occupancies
9.10.2.5. Buildings Containing More Than One Major Occupancy
1) In a
building containing more than one
major occupancy, where the aggregate area of all
major occupancies in a particular group or division does not exceed 10

per cent

of the
floor area on the
storey on which they are located, they need not be considered as
major occupancies for the purposes of
Articles 9.10.8.1. and 9.10.2.4. provided they are not classified as Group F, Division 2
occupancies.

NC2010 2010-01-01 R1
1) 
In a
building containing more than one
major occupancy, where the aggregate area of all
major occupancies in a particular group or division does not exceed
10 per cent 10% of the
floor area on the
storey on which they are located, they need not be considered
as
major occupancies for the purposes of Articles 9.10.8.1. and 9.10.2.4. provided they are not
classified as Group F, Division 2
occupancies.
9.10.3. Ratings
9.10.3.1. Fire-Resistance and Fire-Protection Ratings
9.10.3.2. Flame-Spread Ratings
2) 
Unless the
flame-spread rating is referred to herein as a “surface
flame-spread rating,” it shall apply to any surface of the element being
considered that would be exposed by cutting through it as well as
to the exposed surface of the element.
9.10.3.3. Fire Exposure
1) 
Floor, roof and ceiling assemblies shall be rated for exposure to fire on the underside.
2) Exterior walls shall be rated for exposure to fire from inside the
building, except that such walls need not comply with the temperature rise limitations required by the standard tests referred to in
Article 9.10.3.1., if such walls have a
limiting distance of not less than 1.2 m, and due allowance is made
for the effects of heat radiation in accordance with the requirements in
Part 3.

NC2010 2010-01-01 R1
2) 
Exterior walls shall be rated for exposure to fire from inside the
building, except that such walls need not comply with the temperature rise limitations required by the standard tests referred to in Article 9.10.3.1.
, if such walls have a
limiting
distance of not less than 1.2 m, and due allowance is made
for the effects of heat radiation in accordance with the requirements in Part 3.
9.10.3.4. Suspended Membrane Ceilings
1) Where a ceiling
construction has a suspended membrane ceiling with lay-in panels or tiles which contribute to the required
fire-resistance rating, hold down clips or other means shall be provided to prevent the
lifting of such panels or tiles in the event of a fire.

NC2010 2010-01-01 R1
1) 
Where a ceiling
constructionconstruction has a suspended membrane ceiling with lay-in panels or tiles which contribute to the required
fire-resistance
rating, hold down clips or other means shall be provided to prevent the
lifting of such panels or tiles in the event of a fire.
9.10.4. Building Size Determination
9.10.4.1. Mezzanines not Considered as Storeys
1) Except as required by
Sentences (2) and 9.10.4.2.(1), the space above a
mezzanine is permitted to be excluded from the calculation of
building height, provided
a) the aggregate area of
mezzanines that are not superimposed does not exceed 10

per cent

of the
floor area of the
building in which they are located, and
b) the area of
mezzanine in a
suite does not exceed 10

per cent

of the area of that
suite on the
storey on which it is located.

NC2010 2010-01-01 R1
1) 
Except as required by Sentences (2) and 9.10.4.2.(1), the space above a
mezzanine is permitted to be excluded from the calculation of
building height, provided
a) the aggregate area of mezzanines that are not
superimposed does not exceed 10 per cent 10% of the floor area of
the building in which they are located, and
b) the area of mezzanine in a suite does not exceed 10 per cent 10% of the area of that suite on the storey on which it is
located.
2) Except as provided in
Sentence 9.10.4.2.(1), a
mezzanine need not be considered as a
storey in calculating the
building height provided
a) not less than 60

per cent

of the horizontal plane separating the
mezzanine from the room or floor space in which it is located is open, and
b) except from within enclosures described in
Sentence (3), the space above the
mezzanine is used as an open area without partitions or subdividing walls higher than 1 070 mm above the
mezzanine floor.
(See Appendix Note A-3.2.1.1.(3).)
BC2012 2012-01-01 R1NC2010 2010-01-01 R1
2) Except as provided in Sentence 9.10.4.2.(1), a
mezzanine need not be considered as a
storey in calculating the
building
height provided
a) not less than 60 per cent60% of the horizontal plane separating the mezzanine from the room or floor space in which it is
located is open, and
b) except from within enclosures described in Sentence (3), the space above the mezzanine is used as an open area without partitions or subdividing
walls higher than 1 070 mm above the mezzanine floor.
(See Appendix Note A-3.2.1.1.(3).)
2) 
Except as
provided inrequired bySentence 9.10.4.2.(1),
the space above a
mezzanineneed not be considered as a storey in calculating the is permitted to be excluded from the calculation of building
height, provided
a) not less than 60 per cent of the horizontal plane separating the mezzanine from the room or floor space in which it is
located is open, andthe aggregate area of mezzanines that are not
superimposed does not exceed 40% of the open area of the room in which they are located
(see A-3.2.1.1.(3) in Appendix A), and
b) except from within enclosures described as permitted in Sentence (3), the space above the mezzaninefloor is used as an open area without partitionspartitions or subdividing
walls higher than 1 070 mm1 070 mm above the mezzanine floor.
(See Appendix Note A-3.2.1.1.(3).)
3) The space above a
mezzanine conforming to
Sentence (2) is permitted to include an enclosed space whose area does not exceed 10

per cent

of the open area of the room in which the
mezzanine is located, provided the enclosed space does not obstruct visual communication between the open space above the
mezzanine and the room in which it is located.

NC2010 2010-01-01 R1
3) 
The space above a
mezzanine conforming to Sentence (2) is permitted to include an enclosed space whose area does not exceed
10 per cent 10% of the open area of the room in which
the
mezzanine is located, provided the enclosed space
does not obstruct visual communication between the open space above the
mezzanine and the room in which it is located.
5) Platforms and catwalks intended solely for periodic inspection and maintenance
need not be considered as floor assemblies or
mezzanines for the purpose of calculating
building height, provided
a) they are not used for storage, and

NC2010 2010-01-01 R1
5) 
Platforms and catwalks intended solely for periodic inspection and maintenance need not be considered as floor assemblies or
mezzanines
for the purpose of calculating
building height,
provided
a) they are not used for storage, and
b) they are constructed with noncombustible
materials, unless the building is permitted to be of
combustible construction construction.
9.10.4.2. More Than One Level of Mezzanine
9.10.4.3. Basement Storage Garages
1) Where a
basement is used primarily as a
storage garage, the
basement is permitted to be considered as a separate
building for the purposes of this Section provided the floor above the
basement and the exterior walls of the
basement above the adjoining ground level are constructed as
fire separations of masonry or concrete having a
fire-resistance rating of not less than 2 h, except as permitted by
Sentences 3.2.1.2.(2) and (3).

NC2010 2010-01-01 R1
1) 
Where a
basement is used primarily as a
storage garage, the
basement is permitted to be considered as a separate
building for the
purposes of this Section provided the floor above the
basement and the exterior walls of the
basement above the adjoining ground level are constructed as
fire separations of masonry or concrete having a
fire-resistance rating of not less than 2
h
, except as permitted by Sentences 3.2.1.2.(2) and (3).
9.10.4.4.
Roof-Top Enclosures
1) A roof-top enclosure shall not be considered as a
storey in calculating the
building height if the roof-top enclosure is
a) provided for elevator machinery, a stairway or a
service room, and
b) used for no purpose other than for service to the
building.


NC2010 2010-01-01 R1
1) 
A roof-top enclosure Roof-top enclosures provided for elevator machinery, stairways and service rooms, used for no purpose other than for service to the building, shall not be considered as a
storey in calculating the
building height if the roof-top enclosure is. a) provided for elevator machinery, a stairway or a service room, and
b) used for no purpose other than for service to the building.
9.10.5. Permitted Openings in Wall and Ceiling Membranes
9.10.5.1. Permitted Openings in Wall and Ceiling Membranes
1) 
Except as permitted in
Sentences (2) and (4), a membrane forming part of an assembly required to have a
fire-resistance rating shall not be pierced by openings into the assembly unless the assembly has been tested and rated for such openings.
2) 
A wall or ceiling membrane forming part of an assembly required to have a
fire-resistance rating is permitted to be pierced by openings for electrical and similar service
outlet boxes provided such outlet boxes are tightly fitted.
4) 
A membrane ceiling forming part of an assembly assigned a
fire-resistance rating on the basis of
Table A-9.10.3.1.B or
Appendix D, is permitted to be pierced by openings leading to ducts within the ceiling space provided
the ducts, the amount of openings and their protection conform to
the requirements of
Appendix D.
9.10.6. Construction Types
9.10.6.1. Combustible Elements in Noncombustible Construction
9.10.6.2. Heavy Timber Construction
9.10.7. Steel Members
9.10.7.1. Protection of Steel Members
1) Except as permitted in
Article 3.2.2.3., structural steel members used in
construction
required to have a
fire-resistance rating shall be protected to provide the required
fire-resistance rating.

NC2010 2010-01-01 R1
1) 
Except as permitted in Article 3.2.2.3., structural steel members used in
constructionconstruction required to have a
fire-resistance
rating shall be protected to provide the required
fire-resistance rating.
9.10.8. Fire Resistance and Combustibility in Relation to Occupancy, Height and Supported
Elements
9.10.8.1. Fire-Resistance Ratings for Floors and Roofs
9.10.8.2. Fire-Resistance Ratings in Sprinklered Buildings
1) The requirements in
Table 9.10.8.1. for roof assemblies to have a
fire-resistance rating are permitted to be waived in
sprinklered buildings where

NC2010 2010-01-01 R1
1) 
The requirements in Table 9.10.8.1. for roof assemblies to have a
fire-resistance rating are permitted to be waived
in
sprinklered buildings where
a) the sprinkler systemsprinklersystem is electrically supervised
in conformance with Sentence 3.2.4.10.(3), and
b) the operation of the sprinkler systemsprinklersystem will
cause a signal to be transmitted to the fire department in conformance with
Sentence 3.2.4.8.(4).
9.10.8.3. Fire-Resistance Ratings for Walls, Columns and Arches
1) 
Except as otherwise provided in this Subsection, all
loadbearing walls, columns and arches in the
storey immediately below a floor or roof assembly shall have a
fire-resistance rating of not less than that required for the supported floor or roof assembly.
2) 
Reserved.


NC2010 2010-01-01 R1
2) Reserved.
Light-frame walls, columns, arches and beams as well as loadbearing steel elements that support floors between dwelling units in a house with a secondary suite including their common spaces shall be protected by not less than 12.7 mm thick gypsum board. (See Appendix A.)
9.10.8.4. Support of Noncombustible Construction
9.10.8.5. Service Rooms
9.10.8.6. Mezzanines
9.10.8.7. Roofs Supporting an Occupancy
9.10.8.8. Floors of Exterior Passageways
3) No
fire-resistance rating is required for floors of exterior passageways serving a single
dwelling unit where no
suite is located above or below the
dwelling unit.

NC2010 2010-01-01 R1
3) 
No
fire-resistance rating is required for floors of exterior passageways serving
a single dwelling unit
where no suite is located above or below the dwelling unit.
a) a house with a secondary suite, or
b) a single dwelling unit where no suite is located above or below the dwelling unit (see also Sentence 9.9.9.3.(2)).
9.10.8.9. Crawl Spaces
9.10.8.10. Application to Houses
1) Table 9.10.8.1. does not apply to a
dwelling unit that has no other
dwelling unit above or below it, or to a
dwelling unit that is not above or below another
major occupancy.

NC2010 2010-01-01 R1
1) 
Table 9.10.8.1. does not apply to
a dwelling unit that has no other dwelling unit above or below it, or to a dwelling unit that is not above or below another major occupancy.
a) a dwelling unit that has no other dwelling unit above or below it,
b) houses with a secondary suite, where the floor framing is protected on the underside by a continuous smoke-tight
barrier of not less than 12.7 mm thick gypsum board, or
c) a dwelling unit that is not above or below another major occupancy.
9.10.8.11. Part 3 as an Alternative
9.10.9. Fire Separations between Rooms and Spaces within Buildings

NC2010 2010-01-01 R1
9.10.9.Fire Separations and Smoke-tight Barriers between Rooms and Spaces within Buildings
9.10.9.1. Application
1) This Subsection applies to
fire separations required between rooms and spaces in
buildings, except between rooms and spaces within a
dwelling unit.

NC2010 2010-01-01 R1
1) 
This Subsection applies to
fire separations required between rooms and spaces in buildings, except between rooms and spaces
within a dwelling unit.
a) fire separations required between rooms and spaces in buildings, and
b) smoke-tight barriers required in houses with a secondary suite including their common spaces.
9.10.9.2. Continuous Barrier
1) 
Except as permitted in
Article 9.10.9.3., a wall or floor assembly required to be a
fire separation shall be constructed as a continuous barrier against the spread of fire

and retard the passage of smoke

.
2) 
Reserved.


NC2010 2010-01-01 R1
2) Reserved.
Except as permitted in Article 9.10.9.3., a wall or floor assembly required to be a smoke-tight barrier shall be constructed as a continuous barrier against the spread of smoke.
3) The continuity of a
fire separation shall be maintained where it abuts another
fire separation, a floor, a ceiling, a roof, or an exterior wall assembly. (See
A-3.1.8.3.(4).)

NC2010 2010-01-01 R1
3) 
The continuity of a
fire separation or smoke-tight barrier shall be
maintained where it abuts another
fire separation or smoke-tight barrier, a
floor, a ceiling, a roof, or an exterior wall assembly. (See
Appendix A and A-3.1.8.3.(4)
.) in Appendix A.)
4) 
Reserved.


NC2010 2010-01-01 R1
4) Reserved.
All gypsum board joints in the assemblies described in Sentences (1)and (2) shall conform to CSA A82.31-M, “Gypsum Board Application,” and penetrations in these assemblies shall be sealed using flexible sealant or tape to maintain the integrity of the smoke -tight barrier over the entire surface.
9.10.9.3. Openings to be Protected with Closures
2) 
Reserved.


NC2010 2010-01-01 R1
2) Reserved.
Doors in smoke-tight barriers shall a) be solid-core, wood doors at least 45 mm thick, and
b) have a self-closing device.
(See Appendix A.)
9.10.9.4. Floor Assemblies
2) Floor assemblies contained within
dwelling units need not be constructed as
fire separations.

NC2010 2010-01-01 R1
2) 
Floor assemblies contained within
dwelling unitsand within houses with a secondary suiteneed not be constructed as
fire separations.
9.10.9.5. Interconnected Floor Spaces
9.10.9.6. Penetration of Fire Separations
(See A-3.1.9. in Appendix A.)1) 
Piping, tubing, ducts,
chimneys, wiring, conduit, electrical outlet boxes and other similar service equipment
that penetrate a required
fire separation shall be tightly fitted or fire stopped to maintain the integrity of the separation.
(See Appendix A.) 4) 
Electrical wires or similar wiring enclosed in
noncombustible totally enclosed raceways are permitted to partly or wholly penetrate an assembly required to have
a
fire-resistance rating without being incorporated in the assembly at the time of testing as required in
Sentence (3).
5) 

Single conductor metal-sheathed cables with
combustible jacketting that are more than 25 mm in overall diameter are permitted to penetrate a
fire separation required to have a
fire-resistance rating without being incorporated in the assembly at the time of testing as required in
Sentence (2), provided the cables are not grouped and are spaced a minimum of 300 mm apart.

6) 
Electrical wires or cables, single or grouped, with
combustible insulation or jacketting that is not totally enclosed in raceways of
noncombustible material, are permitted to partly or wholly penetrate an assembly required to have a
fire-resistance rating without being incorporated in the assembly at the time of testing as required in
Sentence (3), provided the overall diameter of the wiring is not more than 25 mm.
7)
Combustible totally enclosed raceways which are embedded in a concrete floor slab are permitted in an assembly
required to have a
fire-resistance rating without being incorporated in the assembly at the time of testing as required in
Sentence (3), where the concrete provides not less than 50 mm of cover between
the raceway and the bottom of the slab.
8)
Combustible outlet boxes are permitted in an assembly required to have a
fire-resistance rating without being incorporated in the assembly at the time
of testing as required in
Sentence (3), provided the opening through the membrane into the box does not exceed 160 cm
2.
9.10.9.7. Combustible Drain, Waste and Vent Piping
(See A-3.1.9. in Appendix A.)2) Combustible drain, waste and vent piping not located in a vertical shaft is permitted to penetrate a
fire separation required to have a
fire-resistance rating or a membrane that forms part of an assembly required to have a
fire-resistance rating provided the piping is sealed at the penetration by a
fire stop
that has an F rating not less than the
fire-resistance rating required for the
fire separation.

NC2010 2010-01-01 R1
2) 
Combustible drain, waste and vent piping not located in a vertical shaft is permitted to penetrate a
fire
separation required to have a
fire-resistance
rating or a membrane that forms part of an assembly required to have a
fire-resistance rating provided the piping is
sealed at the penetration by a
fire
stopfirestopsystem that has an F rating not less than the
fire-resistance rating required for the
fire separation.
3) 
The rating referred to in
Sentence (2) shall be based on CAN/ULC-S115, “Fire Tests of Firestop Systems,” with a pressure differential of 50 Pa between the exposed and unexposed sides, with the higher pressure on the exposed
side.
5)
Combustible drain, waste and vent piping is permitted on one side of a vertical
fire separation provided it is not located in a vertical shaft.
9.10.9.8. Collapse of Combustible Construction
9.10.9.9. Reduction in Thickness of Fire Separation by Beams and Joists
1) 
Where pockets for the support of beams or joists are formed in a masonry or concrete
fire separation, the remaining total thickness of solid masonry and/or grout and/or concrete shall be not less than the required equivalent thickness
shown for Type S monolithic concrete in
Table D-2.1.1. in Appendix D for the required
fire-resistance rating.
9.10.9.10. Concealed Spaces above Fire Separations
2) Where a
horizontal service space or other concealed space is located above a required vertical
fire separation other than a vertical shaft, such space need not be divided as
required in
Sentence (1) provided the
construction between such space and the space below is constructed as a
fire separation having a
fire-resistance rating not less than that required for the vertical
fire separation, except that where the vertical
fire separation is not required to have a
fire-resistance rating greater than 45 min, the
fire-resistance rating of the ceiling may be reduced to 30 min.

NC2010 2010-01-01 R1
2) 
Where a
horizontal service space or other concealed space is located above a required vertical
fire
separation other than a vertical shaft, such space need not be divided as
required in Sentence (1) provided the
constructionconstruction
between such space and the space below is constructed as a
fire separation having a
fire-resistance
rating not less than that required for the vertical
fire separation, except that where the vertical
fire separation is not required to have a
fire-resistance rating greater than 45 min, the
fire-resistance rating of the ceiling may be reduced to
30 min.
9.10.9.11. Separation of Residential Occupancies
9.10.9.12. Residential Suites in Industrial Buildings
9.10.9.13. Separation of Suites
1) Except as required in
Article 9.10.9.14. and as permitted by
Sentence (2)
and (3), a
suite
shall be separated from adjoining
suites by a
fire separation having a
fire-resistance rating of not less than 45 min.

NC2010 2010-01-01 R1
1) 
Except as required in Article 9.10.9.14. and as permitted by Sentence (2)
and (3),
aeachsuitein other than business and personal services occupanciesshall be separated from adjoining
suites by a
fire separation having a
fire-resistance rating of not less than 45 min.
9.10.9.14. Separation of Residential Suites
2) 
Sleeping rooms in boarding and lodging houses where sleeping accommodation is provided for not more than 8 boarders or lodgers
need not be separated from the remainder of the
floor area as required in
Sentence (1) where the sleeping rooms form part of the proprietor's residence and do not contain cooking facilities.
3) Dwelling units that contain 2 or more
storeys including
basements shall be separated from the remainder of the
building by a
fire separation having a
fire-resistance rating of not less than 1 h. (See
A-3.3.4.4.(1) in Appendix A.)

NC2010 2010-01-01 R1
3) 
Except as provided in Sentence (4), Dwellingdwelling units that contain 2 or more
storeys including
basements shall be separated from the remainder of the
building by a
fire separation having a
fire-resistance rating of not less than 1 h. (See A-3.3.4.4.(1) in Appendix A.)
4) 
Reserved.


NC2010 2010-01-01 R1
4) Reserved.
Walls and floor-ceiling framing in a house with a secondary suite that separate dwelling units from each other or dwelling units from ancillary spaces and common spaces need not comply with Sentence (1), where the walls and floor-ceiling framing are protected by a continuous smoke-tight barrier of not less than 12.7 mm thick gypsum board installed on
a) both sides of walls, and
b) the underside of floor-ceiling framing.
(See Sentence 9.10.9.3.(2) for closures.)
9.10.9.15. Separation of Public Corridors
1) Except as provided in
Sentences (2) and (3),
public corridors shall be separated from the remainder of the
building by a
fire separation having not less than a 45 min
fire-resistance rating.

NC2010 2010-01-01 R1
1) 
Except as provided in Sentences (2) and (3)
and (4),
public corridors shall be separated from the remainder of the
building by a
fire separation having not less than a 45 min
fire-resistance rating.
2) In other than
residential occupancies, no
fire-resistance rating is required for
fire separations between a
public corridor and the remainder of the
building if

NC2010 2010-01-01 R1
2) 
In other than
residential occupancies, no
fire-resistance rating is required for
fire separations between a
public corridor and the remainder of the
building
if
a) the floor area is sprinklered,
b) the sprinkler systemsprinklersystem is electrically supervised in conformance with Sentence 3.2.4.10.(3), and
c) the operation of the sprinkler systemsprinklersystem will cause a signal to be transmitted to
the fire department in conformance with Sentence 3.2.4.8.(4).
3) In other than
residential occupancies, no
fire separation is required between a
public corridor and the remainder of the
building if
d) the corridor exceeds 5 m in width.

NC2010 2010-01-01 R1
3) 
In other than
residential occupancies, no
fire separation is required between a
public corridor and the remainder of the
building if
a) the floor area is sprinklered,
b) the sprinkler systemsprinklersystem is electrically supervised in conformance with Sentence 3.2.4.10.(3),
c) the operation of the sprinkler systemsprinklersystem will cause a signal to be transmitted to
the fire department in conformance with Sentence 3.2.4.8.(4), and
d) the corridor exceeds 5 m in width.
4) 
Reserved.


NC2010 2010-01-01 R1
4) Reserved.
Where a public corridor is located in a house with a secondary suite, a continuous smoke-tight barrier of not less than 12.7 mm thick gypsum board shall be installed on a) both sides of walls separating the corridor from the remainder of the building, and
b) the underside of floor-ceiling framing separating the corridor from the remainder
of the building.
(See Sentence 9.10.9.3.(2) for closures.)
9.10.9.16. Separation of Storage Garages
5) 
Where membrane materials are used to provide the required airtightness in the
air barrier system, all joints shall be sealed and structurally supported.
9.10.9.17. Separation of Repair Garages
2) 
Ancillary spaces directly serving a
repair garage, including waiting rooms, reception rooms, tool and
parts storage areas and supervisory office space, need not be separated
from the
repair garage but shall be separated from other
occupancies as required in
Sentence (1).
5) 
Where membrane materials are used to provide the required airtightness in the
air barrier system, all joints shall be sealed and structurally supported.
9.10.9.18. Exhaust Ducts Serving More Than One Fire Compartment
9.10.9.19. Central Vacuum Systems
1) 
A central vacuum system shall serve not more than one
suite.
9.10.9.20. Multiple Tenant Self Storage Warehouses
9.10.10. Service Rooms
9.10.10.1. Application
9.10.10.2. Service Room Floors
9.10.10.3. Separation of Service Rooms
2) 
Where a room contains a limited quantity of service equipment and the service equipment does not constitute a fire hazard, the requirements
in
Sentence (1) shall not apply.
9.10.10.4.
Location of Fuel-Fired Appliances
2) Except as required in the
appliance installation standards referenced in
Sentences 6.2.1.4.(1), 9.33.5.2.(1) and 9.33.5.3.(1), fuel-fired
space-heating appliances, space-cooling
appliances,
service water heaters 
and laundry
appliances
need not be separated from the remainder of the
building as required in
Sentence (1),

where the
appliances serve
a) not more than one room or
suite, or

NC2010 2010-01-01 R1
2) 
Except as required in the
appliance installation standards referenced in Sentences 6.2.1.4.(1), 9.33.5.2.(1) and 9.33.5.3.(1), fuel-fired
space-heating appliances, space-cooling
appliances,
service water
heaters and
and laundry
appliances need
not be separated from the remainder of the
building as
required in Sentence (1),
where the appliances serve
a) not more than one room or suite, or
b) a building with a building
area of not more than 400 m2 and a building height of not more than 2 storeys.
a) where the
appliances serve
i) not more than one room or suite, or
ii) a building with a building area of not more than 400 m2 and a building height of not more than 2 storeys, or
b) where the
appliancesi) serve a house with a secondary suite including their common spaces, and
ii) are located in a service room where both sides of any wall assemblies and the underside of any floor-ceiling framing
separating this room from both dwelling units or their common spaces are protected by a continuous smoke-tight barrier consisting
of not less than 12.7 mm thick gypsum board.
9.10.10.5. Incinerators
4) 
An incinerator shall not be located in a room with other fuel-fired
appliances.
9.10.10.6. Storage Rooms
9.10.11. Firewalls
9.10.11.1. Required Firewalls
9.10.11.2. Firewalls Not Required
1) In a
building of
residential occupancy in which there is no
dwelling unit above another
dwelling unit, a party wall on a property line between
dwelling units need not be constructed as a
firewall provided it is constructed as a
fire separation having not less than a 1 h
fire-resistance rating.

NC2010 2010-01-01 R1
1) 
In Except as stated in Sentence (2), a
buildingparty wallof residential occupancyon ain which there isproperty line
of ano dwelling
unitbuilding ofabove another dwelling unit, a party
wall on a property line between dwelling unitsresidential occupancyneed
not be constructed as a
firewall, provided it is
constructed as a
fire separation having not less than a
1 h
fire-resistance rating., where the party wall separates
a) two dwelling units where there is no dwelling unit above another dwelling unit,
b) a dwelling unit and a house with a secondary suite including their common spaces, or
c) two houses with a secondary suite including their common spaces.
2) 
Reserved.


NC2010 2010-01-01 R1
2) Reserved.
Where a building of residential occupancy contains more than 2 houses, a party wall that separates any 2 adjacent houses with a secondary suite from the rest of the building shall be constructed as a firewall to create separate buildings each containing no more than 2 adjacent houses with a secondary suite.
3) 
The wall described in
Sentence (1) shall provide continuous protection from the top of the footings to the underside of the roof deck.
4) 
Any space between the top of the wall described in
Sentence (1) and the roof deck shall be tightly filled with mineral wool or
noncombustible material.
9.10.11.3. Construction of Firewalls
9.10.12. Prevention of Fire Spread at Exterior Walls and between Storeys
9.10.12.1. Termination of Floors or Mezzanines
9.10.12.2. Location of Skylights
1) 
Where a wall in a
building is exposed to a fire hazard from an adjoining roof of a separate unsprinklered
fire compartment in the same
building, the roof shall contain no skylights within a horizontal distance of 5 m of the windows in the exposed wall.
9.10.12.3. Exterior Walls Meeting at an Angle

NC2010 2010-01-01 R1
9.10.12.3. Exterior Walls Meeting at an Angle
1) 
Except as provided in Article 9.9.4.5., where exterior walls of a
building meet at an external angle of
135° or less, the horizontal distance from
an unprotected openingopenings in one exterior wall to an
unprotected openingopenings in the other exterior
wall shall be not less than 1.2 m, where these openings
are
a) in different fire compartments, or
b) in different dwelling
units, ancillary spaces or common spaces in a house with a secondary suite.
2) 
The Except as provided in Sentence (3), the exterior wall of each
fire compartment referred to in Sentence (1) within the 1.2
m distance shall have a
fire-resistance
rating not less than that required for the interior vertical
fire separation between the compartment and the remainder
of the
building.
3) 
Where interior walls between
dwelling units, ancillary spaces or common spaces in a house with a
secondary suite are not constructed as
fire separations, the exterior wall of each
dwelling unit, ancillary space or common space referred to in Sentence (1) within the 1.2 m distance shall be finished on the interior with not less than 12.7 mm thick gypsum board.
9.10.12.4. Protection of Soffits
1) 
This Article applies to the portion of any soffit enclosing a projection that is
a) less than 2.5 m vertically above a window or door,
and
b) less than 1.2 m from either side of the window
or door.
(See Appendix A.) 2) Except as provided in
Sentences (4) and (5), the
construction described in
Sentence (1) shall have no
unprotected openings and shall be protected in accordance with
Sentence (3), where the soffit encloses
b) a floor space where an upper
storey projects beyond the exterior wall of a lower
storey and a
fire separation is required at the floor between the two, or
c) a floor space where an upper
storey projects beyond the exterior wall of a lower
storey, and the projection is continuous across a vertical
fire separation separating two
suites.

BC2012 2012-01-01 R1NC2010 2010-01-01 R1
2) Except as provided in Sentences (4) and (5), the
constructionconstruction
described in Sentence (1) shall have no
unprotected openings and shall be protected in
accordance with Sentence (3), where the soffit
encloses
a) a common attic or roof space that spans more
than 2 suites of residential
occupancy and projects beyond the exterior wall of the building,
b) a floor space where an upper storey projects beyond
the exterior wall of a lower storey and a fire separation is required at the floor between the
two, or
c) a floor space where an upper storey projects beyond
the exterior wall of a lower storey, and the projection
is continuous across a vertical fire separation
separating two suites.
2) 
Except as provided in Sentences (4) and (5), the
constructionconstruction described in Sentence (1) shall have no
unprotected openings and shall be protected in
accordance with Sentence (3), where the soffit
encloses
a) a common attic or roof space that spans more
than 2 suites of residential
occupancy and projects beyond the exterior wall of the building,
b) a floor space where an upper
storey projects beyond
the exterior wall of a lower
storey and
a fire separation is required at the floor between the
two, or
i) a fire separation is required at the floor between the two, or
ii) the floor separates dwelling units from each other or a dwelling unit from an ancillary space or a common space in a house with a secondary suite, or
c) a floor space where an upper
storey projects beyond
the exterior wall of a lower
storey, and the projection
is continuous across
a vertical fire separation
separating two suites.
i) a vertical fire separation separating two suites, or
ii) a wall separating dwelling units from each other or a dwelling unit from an ancillary space or a common space in a house with a secondary suite.
3) 
Protection required by
Sentence (2) shall be provided by
a)
noncombustible material having a minimum thickness of 0.38 mm and a melting point not
below 650°C,
c) not less than 11 mm thick plywood,
d) not less than 12.5 mm thick OSB or waferboard, or
e) not less than 11 mm thick lumber.
(See Appendix A.) 5) 
Where all
suites spanned by a common
attic or roof space or situated above or below the projecting floor are
sprinklered, the requirements of
Sentence (2) do not apply, provided that all rooms, including closets and bathrooms, having
openings in the wall beneath the soffit are
sprinklered, notwithstanding any exceptions in the sprinkler standards referenced in
Article 3.2.5.12. 9.10.13. Doors, Dampers and Other Closures in Fire Separations
9.10.13.1. Closures
9.10.13.2. Solid Core Wood Door as a Closure
2) 
Doors described in
Sentence (1) shall have not more than a 6 mm clearance beneath and not more
than 3 mm at the sides and top.
9.10.13.3. Unrated Wood Door Frames
1) 
Doors required to provide a 20 min
fire-protection rating or permitted to be 45 mm solid core wood shall be mounted in a wood frame of not less than 38 mm thickness where the frame has not
been tested and rated.
9.10.13.4. Doors as a Means of Egress
9.10.13.5. Wired Glass as a Closure
2) 
Wired glass described in
Sentence (1) shall be mounted in fixed steel frames having a metal thickness of not less than 1.35 mm and a glazing stop of not less
than 20 mm on each side of the glass.
3) 
Individual panes of glass described in
Sentence (1) shall not exceed 0.8 m
2 in area or 1.4 m in height or width, and the area of glass not structurally supported by mullions shall not exceed 7.5 m
2.
9.10.13.6. Steel Door Frames
9.10.13.7. Glass Block as a Closure
9.10.13.8. Maximum Size of Opening
1) The size of an opening in an interior
fire separation, even where protected with a
closure, shall not exceed 11 m
2, with no dimension greater than 3.7 m,
when the
fire compartments on both sides of the
fire separation are not
sprinklered.

NC2010 2010-01-01 R1
1) 
The size of an opening in an interior
fire separationfire separation, even where protected with a
closure, shall not exceed 11
m
2, with no dimension greater than 3.7 m,
when the
fire compartments on both sides of the
fire separation are not
sprinklered.
9.10.13.9. Door Latch
1) 
Every swing type door in a
fire separation shall be equipped with a latch.
9.10.13.10. Self-closing Device
9.10.13.11. Hold-Open Devices
9.10.13.12. Service Room Doors
1) 
Swing-type doors shall open into
service rooms containing fuel-fired equipment where such doors lead
to
public corridors or rooms used for assembly but shall swing outward from such rooms in all other cases.
9.10.13.13. Fire Dampers
2) 
A
fire damper is not required where a
noncombustible branch duct pierces a required
fire separation provided the duct
a) has a melting point not below 760°C,
b) has a cross-sectional area less than 130 cm2, and
c) supplies only air-conditioning units or combined air-conditioning
and heating units discharging air at not more than 1.2 m above the floor.
3) 
A
fire damper is not required where a
noncombustible branch duct pierces a required
fire separation around an
exhaust duct riser in which the airflow is upward provided
a) the melting point of the branch duct is not below 760°C,
b) the branch duct is carried up inside the riser not less than 500 mm, and
9.10.13.14. Fire Stop Flaps
9.10.13.15. Doors between Garages and Dwelling Units
1) 
A door between an attached or built-in garage and a
dwelling unit shall be tight fitting and weather-stripped to provide an effective barrier against the passage of gas and exhaust
fumes and shall be fitted with a self-closing device.
2) 
A doorway between an attached or built-in garage and a
dwelling unit shall not be located in a room intended for sleeping.
9.10.13.16. Door Stops
1) 
Where a door is installed so that it may damage the integrity of a
fire separation if its swing is unrestricted, door stops shall be installed to prevent such damage.
9.10.14. Spatial Separation Between Buildings
9.10.14.1. Application
9.10.14.2. Area and Location of Exposing Building Face
1) 
The area of an
exposing building face shall be
a) taken as the exterior wall area facing in one direction on any side of a
building, and
b) calculated as
i) the total area measured from the finished ground level to the
uppermost ceiling, or
3) For the purpose of using
Table 9.10.14.5.A to determine the required type of
construction, cladding and
fire-resistance rating for an irregularly shaped or skewed exterior wall,

NC2010 2010-01-01 R1
3) 
For the purpose of using Table 9.10.14.5.A to determine the required type of
constructionconstruction, cladding and
fire-resistance
rating for an irregularly shaped or skewed exterior wall,
a) the location of the exposing building face shall
be taken as a vertical plane located so that no portion of the actual exposing building face is between the vertical plane
and the line to which the limiting distance is
measured, and
b) the value for the maximum area of unprotected
openings (see second column of Table 9.10.14.5.A) shall be determined using the limiting distance measured from the location described in Clause (a). (See A-3.2.3.1.(4) in Appendix A.)
9.10.14.3. Limiting Distance and Fire Department Response
1) Except

as provided in
Sentence (2) and except

for the purpose of applying
Sentences 9.10.14.4.(2)
, (3), (8) and (9), and
Sentences 9.10.14.5.(3), (8) and (12)
, a
limiting distance equal to half the actual
limiting distance shall be used as input to the requirements of this Subsection, where
a)

the time from receipt of notification of a fire by the fire department until the first fire department vehicle arrives at the
building exceeds 10 min in 10

per cent

or more of all calls to the
building,

and
(See A-3.2.3. and A-3.2.3.1.(8) in Appendix A.)

BC2012 2013-04-03 R2NC2010 2010-01-01 R1
1) Except as provided in Sentence (2) and except for the purpose of applying Sentences 9.10.14.4.(2), (3), (8) and (9), and Sentences 9.10.14.5.(3), (8) and (12), a
limiting distance equal to half the actual
limiting distance shall be used as input to the requirements of this Subsection, where
a) the time from receipt of notification of a fire by the fire department until the first
fire department vehicle arrives at the building exceeds 10 min in 10 per cent 10% or more of all calls to the building, and
b) any storey in the building is not sprinklered.
(See A-3.2.3. and A-3.2.3.1.(8) in Appendix A.)
1) 
Except
as provided in Sentence (2) and except for the purpose of applying Sentences 9.10.14.4.(2), (3), (8) and (9), and Sentences 9.10.14.5.(3), (8) and (12), a
limiting distance equal to half the actual
limiting distance shall be used as input to the requirements of this Subsection, where
a) the time from receipt of notification of a fire by the fire department until the first
fire department vehicle arrives at the building exceeds 10 min in 10 per cent 10% or more of all calls to the building, and
b) any storey in the building is not sprinklered.
(See A-3.2.3. and A-3.2.3.1.(8) in Appendix A.)
2) 
Except for the purpose of applying
Sentences 9.10.14.4.(2),
9.10.14.4.(3),
9.10.14.4.(8) and
9.10.14.4.(9) and
Sentences 9.10.14.5.(3),
9.10.14.5.(8) and
9.10.14.5.(12), a
limiting distance equal to half the actual
limiting distance shall be used as input to the requirements of this Subsection, where
a) a
building for which a
building permit was applied for before December 20, 2014 is or is proposed to be located in a subdivision for which a subdivision plan was registered in a land title office before
December 20, 2013,
b)

Deleted, and


BC2012 2013-04-03 R2
2) Except for the purpose of applying Sentences 9.10.14.4.(2), 9.10.14.4.(3), 9.10.14.4.(8) and 9.10.14.4.(9) and Sentences 9.10.14.5.(3), 9.10.14.5.(8) and 9.10.14.5.(12), a
limiting distance equal to half the actual
limiting distance shall be used as input to the requirements of this Subsection, where
a) a building for which a building permit was applied for before December 20, 2014 is or is proposed to be located in
a subdivision for which a subdivision plan was registered in a land title office before
December 20, 2013,
b) Deleted, andthere is no fire department or the fire department is not organized, trained and equipped
to meet the needs of the community, and
c) the building is not sprinklered.
9.10.14.4. Openings in Exposing Building Face
5) 
For the purpose of
Sentence (4), “single room or space” shall mean
a) two or more adjacent spaces having a full-height separating
wall extending less than 1.5 m from the interior face
of the exterior wall, or
b) two or more stacked spaces that are on the same
storey.

6) 
If a
building is not
sprinklered,

the maximum aggregate area of
unprotected openings shall be not more than twice the area determined according to
Sentence (1), where the
unprotected openings are glazed with

NC2010 2010-01-01 R1
6) 
If a building is not sprinklered, the The maximum aggregate area of
unprotected openings shall be not more than twice the area determined according to Sentence (1), where the
unprotected openings are glazed with
a) wired glass in steel frames, as described in Article 9.10.13.5., or
b) glass blocks, as described in Article 9.10.13.7.
8) 
If a
storage garage has a
limiting distance of no less than 3 m, the
exposing building face of such
storage garage may have unlimited
unprotected openings.


NC2010 2010-01-01 R1
8) If a storage garage has a limiting distance of no less than 3 m, the exposing building face of such storage garage may have unlimited unprotected openings.
The maximum aggregate area of unprotected openings in an exposing building face of a storage garage need not comply with Sentence (1), where
a) all storeys are constructed as open-air storeys, and
b) the storage garage has a limiting distance of not less than 3 m.
9.10.14.5. Construction of Exposing Building Face and Walls above Exposing Building Face
3) 
Except as provided in
Sentences (4) to (8) and permitted by
Sentence (9),

cladding on
exposing building faces and on exterior walls located above
exposing building faces 
of
buildings or
fire compartments where the maximum permitted area of
unprotected openings is more than 25

per cent

but not more than 50

per cent

of the
exposing building face need not be
noncombustible
, where

BC2012 2014-12-19 R6NC2010 2010-01-01 R1
3) Except as provided in Sentences (4) to (8) and permitted by Sentence (9), cladding on
exposing building faces and on exterior walls
located above
exposing building
faces of
buildings or
fire compartments where the maximum permitted area of
unprotected openings is more than
25 per cent 25% but not more
than
50 per cent 50% of the
exposing building face need not be
noncombustible, where
a) the limiting distance is greater
than 5.0 m,
b) the limiting distance is greater
than 2.5 m where the area and width-to-height ratio of the exposing building face conform to Table 9.10.14.5.B,
c) the building or fire compartment is sprinklered,
d) the cladding
i) conforms to Subsections 9.27.6., 9.27.7., 9.27.8. or 9.27.9., 9.27.8. or 9.27.9.,
ii) is installed without furring members, or on furring not
more than 25 mm thick, over gypsum sheathing at least
12.7 mm thick or over masonry, and
iii) after conditioning in conformance with ASTM D 2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing,” has a flame-spread rating not greater than
25 when tested in accordance with Sentence 3.1.12.1.(2), or
e) the cladding
i) conforms to Subsection 9.27.12.,
ii) is installed with or without furring members
over a gypsum sheathing at least 12.7
mm thick or over masonry,
iii) has a flame-spread rating not greater than
25 when tested in accordance with Sentence 3.1.12.1.(2), and
iv) does not exceed 2 mm in thickness exclusive of fasteners,
joints and local reinforcements.
3) 
Except as provided in Sentences (4) to (8) and permitted by Sentence (9), cladding on
exposing building faces and on exterior walls
located above
exposing building
faces of
buildings or
fire compartments where the maximum permitted area of
unprotected openings is more than
25 per cent 25% but not more
than
50 per cent 50% of the
exposing building face need not be
noncombustible, where
a) the limiting distance is greater
than 5.0 m,
b) the limiting distance is greater
than 2.5 m where the area and width-to-height ratio of the exposing building face conform to Table 9.10.14.5.B, and
c) the building or fire compartment is sprinklered,
d) the cladding
i) conforms to Subsections 9.27.6., 9.27.7., 9.27.8. or 9.27.9.,
ii) is installed without furring members, or on furring not
more than 25 mm thick, over gypsum sheathing at least
12.7 mm thick or over masonry, and
iii) after conditioning in conformance with ASTM D 2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing,” has a flame-spread rating not greater than
25 when tested in accordance with Sentence 3.1.12.1.(2), or
e) the cladding
i) conforms to Subsection 9.27.12.,
ii) is installed with or without furring members
over a gypsum sheathing at least 12.7
mm thick or over masonry,
iii) has a flame-spread rating not greater than
25 when tested in accordance with Sentence 3.1.12.1.(2), and
iv) does not exceed 2 mm in thickness exclusive of fasteners,
joints and local reinforcements.
4) Except as provided in
Sentence (5),

if a detached garage or accessory
building serves one
dwelling unit; or if a detached garage serves both units in a
two-family dwelling and has a continuous internal
fire separation, with a 45 minute
fire resistance rating from the floor slab to the roof sheathing separating the parking spaces for each unit,

the
exposing building face:

NC2010 2010-01-01 R1
4) 
Except as provided in Sentence (5),
ifwhere a
detached garage or accessory
building serves one
dwelling unit; or if a detached garage serves both
units in a two-family dwelling only and
has a
continuous internalis detached from anyfire separationbuilding,
with a 45 minute
fire resistance rating from the floor slab to the
roof sheathing separating the parking spaces for each unit, the the exposing building
face:a) need not conform to the minimum required fire-resistance rating stated in Table 9.10.14.5.A, where the limiting
distance is 0.6 m or more,
b) shall have a fire-resistance rating of not less
than 45 min, where the limiting
distance is less than 0.6 m, and
c) need not conform to the type of cladding required by Table 9.10.14.5.A, regardless of the limiting
distance.
5) The requirements regarding
fire-resistance rating, type of
construction and type of cladding need not apply to the
exposing building face of a detached garage

conforming to
Sentence 9.10.14.5.(4)
or accessory
building facing a
one-family dwelling or
two-family dwelling
, where

NC2010 2010-01-01 R1
5) 
The requirements regarding
fire-resistance rating, type of
constructionconstruction and type of cladding need not apply to the
exposing building face of a detached garage
conforming to Sentence 9.10.14.5.(4)or accessory
building facing a
one-family dwelling or two-family dwellingdwelling unit, where
a) the detached garage or accessory building serves only one-family dwellingoneor two-family dwellingdwelling unit,
b) the detached garage or accessory building is located on the same property as that one-family dwelling or two-family dwellingdwelling unit, and
c) the one-family dwellingdwelling unitor two-family dwellingserved by the detached garage or accessory building is the only major occupancy on the property.
6) 
Except

as provided in
Sentence (7),
combustible projections on the exterior of a wall that are more than 1 m above ground level and that could expose an adjacent
building to fire spread shall not be permitted within
a) 1.2 m of a property line or the centre line of
a
public way, or
7) 
Except as provided in
Sentences (9) to (11),
Sentence (6) shall not apply to
b) detached garages or accessory
buildings, where
(See Appendix A.)
NC2010 2010-01-01 R1
7) 
Except as provided in Sentences (9) to (11), Sentence (6) shall not apply to
a) buildings containing one-family dwelling1 or two-family dwelling2 dwelling units only, and
b) detached garages or accessory
buildings, where
i) the detached garage conforming to Sentence 9.10.14.5.(4)or accessory building serves only one-family dwellingoneor two-family dwellingdwelling unit,
ii) the detached garage conforming to Sentence 9.10.14.5.(4)or accessory building is located on the same property as that one-family dwelling or two-family dwellingdwelling unit, and
iii) the one-family dwellingdwelling unitor two-family dwellingserved by the detached garage conforming to Sentence 9.10.14.5.(4)or accessory building is the only major occupancy on the property.
(See Appendix A.)
8) Where
combustible projections on an
exposing building face are permitted by
Sentence (7), are totally enclosed and constructed with solid faces, such as for fireplaces and
chimneys, and extend within 1.2 m of a property line,
b) where the underside of the projection is more than 0.6 m above
finished ground level, it shall be protected by
iv) not less than 11 mm thick plywood,
v) not less than 12.5 mm thick OSB or waferboard, or
vi) not less than 11 mm thick lumber.
(See Appendix A.)
NC2010 2010-01-01 R1
8) 
Where
combustible projections on an
exposing building face are permitted by Sentence (7), are totally enclosed and constructed with solid faces, such as for fireplaces and
chimneys, and extend within 1.2 m of a property
line,
a) the constructionconstruction of the face and sides of the projection shall comply with the
corresponding requirements for exposing building
faces for limiting distances less than
1.2 m as stated in Sentence (2) or (3), and
b) where the underside of the projection is more than 0.6 m above
finished ground level, it shall be protected by
i) not less than 0.38 mm thick noncombustible material,
ii) unvented aluminum conforming to CAN/CGSB-93.2-M, “Prefinished Aluminum Siding, Soffits, and Fascia, for Residential
Use,”
iii) not less than 12.7 mm thick gypsum soffit board or gypsum
ceiling board installed according to CSA A82.31-M, “Gypsum Board Application,”
iv) not less than 11 mm thick plywood,
v) not less than 12.5 mm thick OSB or waferboard, or
vi) not less than 11 mm thick lumber.
(See Appendix A.)
11) 
Where roof soffits project to less than 1.2 m from the property line, the centre line of a lane or public thoroughfare,
or an imaginary line between 2
buildings or
fire compartments on the same property, they shall
a) have no openings, and
b) be protected by
i) not less than 0.38 mm thick sheet steel,
iv) not less than 11 mm thick plywood,
v) not less than 12.5 mm thick OSB or waferboard, or
vi) not less than 11 mm thick lumber.
(See A-3.2.3.6.(2) in Appendix A.)

VC2014 2014-03-01 R1
9.10.14.5. Construction of Exposing Building Face and Walls above Exposing Building Face
14) Where a residential building is sprinklered, and Table 9.10.14.5.A requires noncombustible construction, the exposing building faces may use a wood stud wall assembly having a 1 hour fire-resistance rating provided the limiting distance is at least 1.0 m, the studs are filled with noncombustible insulation, and the wall assembly is of clad with noncombustibleconstruction throughout excepting structural elements and sheathingcladding.
9.10.15. Spatial Separation Between
Residential Buildings
(see Appendix A)

NC2010 2010-01-01 R1
9.10.15.Spatial Separation Between Residential BuildingsHouses
(see Appendix A)
9.10.15.1. Application
1) 
This Subsection applies to
e) accessory buildings that serve a building described in
Clause (a).


VC2014 2015-01-01 R1BC2012 2014-12-19 R7BC2012 2012-01-01 R1NC2010 2010-01-01 R1
1) This Subsection applies to
a) buildings containing only dwelling units with no dwelling unit above another dwelling unit except as described in Clause (b) or (c),
b) one-family dwellings with secondary suite,
c) two-family dwellings having no dwelling unit above another dwelling unit except secondary suite within the principal dwelling unit, and
d) laneway houses, and.
e) accessory buildings that serve a building described in Clause (a).
1) This Subsection applies to
a) buildingscontaining that contain only dwelling unitswith and have no dwelling unit above another dwelling unit except as described in Clause (b) or (c),, and
b) one-family dwellings with secondary suite,
c) two-family dwellings having no dwelling unit above another dwelling unit except secondary suite within the principal dwelling unit,
d) laneway houses, and
e) accessory buildingsbuildings that serve a buildingbuilding described in Clause (a).
1) This Subsection applies to
buildings that contain only dwelling units and have no dwelling unit above another dwelling unit; (See Appendix A.)
a) buildings containing only dwelling units with no dwelling unit above another dwelling unit except as described in Clause (b) or (c),
b) one-family dwellings with secondary suite,
c) two-family dwellings having no dwelling unit above another dwelling unit except secondary suite within the principal dwelling unit,
d) laneway houses, and
e) accessory buildings that serve a building described in Clause (a).
1) 
This Subsection applies to
a) buildingscontaining that contain only dwelling unitswith and have no dwelling unit above another dwelling unit except as described in Clause (b) or (c),, and
b) one-family dwellings with secondary suite,
c) two-family dwellings having no dwelling unit above another dwelling unit except secondary suite within the principal dwelling unit,
d) laneway houses, and
e) accessory buildings that serve a building described in Clause (a).houses with a secondary suite including their common spaces.
(See Appendix A.)
9.10.15.2. Area and Location of Exposing Building Face
1) The area of an
exposing building face shall be
a) taken as the exterior wall area facing in one direction on any side of a
building, and
b) calculated as
i) the total area measured from the finished ground level to the uppermost
ceiling,

NC2010 2010-01-01 R1
1) 
The area of an
exposing building face shall be
a) taken as the exterior wall area facing in one direction on any side of a building, and
b) calculated as
i) the total area measured from the finished ground level to the uppermost
ceiling,
ii) the area for each fire compartment, where a
building is divided into fire compartments by fire
separations with fire-resistance
ratings not less than 45 min, or
iii) except as provided in Sentence (2), where Table 9.10.15.4. is used to determine the maximum aggregate area of
unprotected openingsglazed openings, the area of any number of individual vertical portions of
the wall measured from the finished ground level to the uppermost ceiling.
(See A-9.10.15.4.(2) in Appendix
A.)
3) For the purpose of using
Table 9.10.15.4. to determine the maximum permitted area of
unprotected openings
in an irregularly shaped or skewed exterior wall, the location of the
exposing building face shall be taken as a vertical plane located so that there are no
unprotected openings
between the vertical plane and the line to which the
limiting distance is measured. (See
A-3.2.3.1.(4) in Appendix A.)

NC2010 2010-01-01 R1
3) 
For the purpose of using Table 9.10.15.4. to determine the maximum permitted area of
unprotected openingsglazedopenings in an irregularly shaped or skewed exterior wall,
the location of the
exposing building face shall be
taken as a vertical plane located so that there are no
unprotected openingsglazedopenings between the
vertical plane and the line to which the
limiting
distance is measured. (See A-3.2.3.1.(4)
in Appendix A.)
9.10.15.3. Limiting Distance
and Fire Department Response
1) Except

as provided in
Sentence 9.10.15.3.(2) and except

for the purpose of applying
Sentences 9.10.15.2.(2), 9.10.15.4.(3) and 9.10.15.5.(12),

a
limiting distance equal to half the actual
limiting distance shall be used as input to the requirements of this Subsection, where
a)

the time from receipt of notification of a fire by the fire department until the first fire department vehicle arrives at the
building exceeds 10 min in 10

per cent

or more of all calls to the
building,

and
(See A-3.2.3. and A-3.2.3.1.(8) in Appendix A.)

BC2012 2013-04-03 R2NC2010 2010-01-01 R1
1) Except as provided in Sentence 9.10.15.3.(2) and except for the purpose of applying Sentences 9.10.15.2.(2), 9.10.15.4.(3) and 9.10.15.5.(12), a
limiting distance equal to half the actual
limiting distance shall be used as input to the
requirements of this Subsection, where
a) the time from receipt of notification of a fire by the fire
department until the first fire department vehicle arrives at the building exceeds 10 min in 10 per cent 10 min in 10% or more of all calls to
the building, and
b) any storey in the building is not sprinklered.
(See A-3.2.3. and A-3.2.3.1.(8) in Appendix A.)
1) 
Except
as provided in Sentence 9.10.15.3.(2) and except for the purpose of applying Sentences 9.10.15.2.(2), 9.10.15.4.(3) and 9.10.15.5.(12), a
limiting distance equal to half the actual
limiting distance shall be used as input to the requirements of this Subsection, where
a) the time from receipt of notification of a fire by the fire
department until the first fire department vehicle arrives at the building exceeds 10 min in 10 per cent 10 min in 10% or more of all calls to
the building, and
b) any storey in the building is not sprinklered.
(See A-3.2.3. and A-3.2.3.1.(8) in Appendix A.)
2) 

Deleted.



BC2012 2013-04-03 R2BC2012 2012-01-01 R1
2) Deleted.Except for the purpose of applying Sentences 9.10.15.2.(2), Sentence 9.10.15.4.(3) and 9.10.15.5.(12), a limiting distance equal to half the actual limiting distance shall be used as input to the requirements of this Subsection, where
a) a building for which a building permit was applied for before December 20, 2014 is or is proposed
to be located in a subdivision for which a subdivision plan was registered in a land
title office before December 20, 2013,
b) there is no fire department or the fire department is not organized, trained and equipped
to meet the needs of the community, and
c) the building is not sprinklered.
2) Deleted.Despite Sentence 9.10.15.3.(1), except for the purposes of applying Sentences 9.10.15.2.(2), Sentence 9.10.15.4.(3) and 9.10.15.5.(12), a limiting distance equal to half the actual limiting distance shall be used as input to the requirements of this Subsection, where
a) a building for which a building permit was applied for before December 20, 2014 is or is proposed
to be located in a subdivision for which a subdivision plan was registered in a land
title office before December 20, 2013,
b) there is no fire department or the fire department is not organized, trained and equipped
to meet the needs of the community, and
c) the building is not sprinklered.
9.10.15.4.
Unprotected
Openings in Exposing Building Face

NC2010 2010-01-01 R1
9.10.15.4. UnprotectedGlazed Openings in Exposing Building Face
1) Except as provided in
Sentences (6), (7) and (8)
, the maximum aggregate area of
unprotected openings
in an
exposing building face shall

NC2010 2010-01-01 R1
1) 
Except as provided in Sentences (6)
, (7) and (8), the maximum aggregate area of
unprotected openingsglazedopenings in an
exposing building face shall
a) conform to Table 9.10.15.4.,
b) in a building which conforms to Sentence (8), comply with Subsection 3.2.3., orconform to Subsection 3.2.3., or
c) where the limiting distance is not less than 1.2 m, be equal to or less than the limiting distance squared.
2) Where the limits on the area of
unprotected openings
are determined for individual portions of the exterior wall, as described in
Subclause 9.10.15.2. (1)(b)(iii), the maximum aggregate area of
unprotected openings
for any portion shall conform to the values in the row of
Table 9.10.15.4. corresponding to the maximum total area of
exposing building face (see column 1 of the Table) that is equal to the sum of all portions of the
exposing building face. (See
Appendix A.)

NC2010 2010-01-01 R1
2) 
Where the limits on the area of
unprotected openingsglazedopenings are determined for individual portions of the exterior wall, as described in Subclause 9.10.15.2. (1)(b)(iii), the maximum aggregate area of
unprotected openingsglazed
openings for any portion shall conform to the values in the row of Table 9.10.15.4. corresponding to the maximum total area of
exposing building face (see column 1 of the Table) that
is equal to the sum of all portions of the
exposing building
face. (See Appendix A.)
3) 
Except for
buildings that are
sprinklered and for openable windows having an unobstructed opening equal to 0.35 m
2 installed in accordance with
Sentences 9.9.10.1.(1) and (2), where the
limiting distance is 2 m or less, individual
unprotected openings
or a group of
unprotected openings
in an
exposing building face shall not exceed 50

per cent

of the maximum allowable aggregate area of
unprotected openings
determined in
Sentence (1).

NC2010 2010-01-01 R1
3) 
Except for
buildings that are
sprinklered and for openable windows having an unobstructed opening equal to 0.35 m
2 installed in accordance with Sentences 9.9.10.1.(1) and (2), where the
limiting distance is 2 m or less,
individual
unprotected openingsglazedopenings or a group of
unprotected openingsglazedopenings in an
exposing building face shall not exceed
50 per cent 50% of the
maximum allowable aggregate area of
unprotected openingsglazedopenings determined in Sentence (1).
4) The spacing between individual
unprotected openings
described in
Sentence (3) serving a single room or space described in
Sentence (5) shall be not less than
b) 2 m vertically of another
unprotected opening
that serves the single room or space, or another room or space on the same
storey.

NC2010 2010-01-01 R1
4) 
The spacing between individual
unprotected openingsglazedopenings described in Sentence (3) serving a single room or space described in Sentence (5) shall be not less
than
a) 2 m horizontally of another unprotected openingglazedopening that is on the same
exposing building face and serves the single
room or space, or
b) 2 m vertically of another unprotected openingglazedopening that serves the single
room or space, or another room or space on the same storey.
5) 
For the purpose of
Sentence (4), “single room or space” shall mean
a) two or more adjacent spaces having a full-height separating
wall extending less than 1.5 m from the interior face of the exterior
wall, or
b) two or more stacked spaces that are on the same
storey.

6) The limits on the area of
unprotected openings
shall not apply to the
exposing building face of
one-family dwelling or
two-family dwelling
facing a detached garage or accessory
building, where

NC2010 2010-01-01 R1
6) 
The limits on the area of
unprotected openingsglazedopenings shall not apply to the
exposing building face of
one-family dwellinga dwelling unitor two-family dwellingfacing a detached garage or accessory
building, where
a) the detached garage conforming to Sentence 9.10.15.5.(4)or accessory building serves only one-family dwellingoneor two-family dwellingdwelling unit,
b) the detached garage conforming to Sentence 9.10.14.5.(4)or accessory building is located on the same property as that one-family dwelling or two-family dwellingdwelling unit, and
c) the one-family dwellingdwelling unitor two-family dwellingserved by the detached garage conforming to Sentence 9.10.15.5.(4)or accessory building is the only major occupancy on the property.

NC2010 2010-01-01 R1
Table 9.10.15.4. Maximum Area of UnprotectedGlazed Openings in Exterior Walls of
Houses Forming part of Sentences 9.10.15.4.(1) and (2)
|
Maximum Total
Area of Exposing Building Face,
m2 |
Maximum Aggregate Area of UnprotectedGlazed Openings, % of Exposing Building Face
Area
|
|
Limiting Distance,
m
|
|
Less than 1.2 |
1.2 |
1.5 |
2.0 |
4.0 |
6.0 |
8.0 |
10.0 |
12.0 |
16.0 |
20.0 |
25.0 |
30 |
0 |
7 |
9 |
12 |
39 |
88 |
100 |
— |
— |
— |
— |
— |
40 |
0 |
7 |
8 |
11 |
32 |
69 |
100 |
— |
— |
— |
— |
— |
50 |
0 |
7 |
8 |
10 |
28 |
57 |
100 |
— |
— |
— |
— |
— |
100 |
0 |
7 |
8 |
9 |
18 |
34 |
56 |
84 |
100 |
— |
— |
— |
Over 100 |
0 |
7 |
7 |
8 |
12 |
19 |
28 |
40 |
55 |
92 |
100 |
— |
9.10.15.5. Construction of Exposing Building Face of Houses
1) Except as provided in
Sentences (4), (12) and (13),

each
exposing building face and any exterior wall located above an
exposing building face that encloses an
attic or roof space shall be constructed in conformance with
Sentences (2) and (3)
(See also Subsection 9.10.8.)

NC2010 2010-01-01 R1
1) 
Except as provided in Sentences (4), (12)
and (13), each
exposing building face and any exterior wall located above an
exposing building face that encloses an
attic or roof space shall be constructed in conformance
with Sentences (2) and (3)
a) for the exposing building face as a whole,
or
b) for any number of separate portions of the exposing
building face (see Subclause (b)(iii), Sentence 9.10.15.4.(2), and A-9.10.15.4.(2) in Appendix
A).
(See also Subsection 9.10.8.)
2) 
Except as provided in
Sentences (4) and (5),

where the
limiting distance is less than 0.6 m, the
exposing building face and exterior walls located above the
exposing building face that enclose an
attic or roof space 
shall have a
fire-resistance rating of not less than 45 min, and

b)

the cladding shall

ii) be installed without furring members over gypsum sheathing at least 12.7 mm thick or over masonry,
iv) not exceed 2 mm in thickness exclusive of fasteners, joints and local reinforcements, or

NC2010 2010-01-01 R1
2) 
Except as provided in Sentences (4) and (5), where the
limiting distance is less than 0.6
m, the
exposing building face and exterior
walls located above the
exposing building face that
enclose an
attic or roof space shall have a
fire-resistance rating of
not less than 45 min, and
a) the cladding shall be metal or noncombustible cladding installed in accordance with Section 9.20., 9.27. or 9.28. (see A-9.10.14.5.(1) in Appendix A),
b) the cladding shall
i) conform to Subsection 9.27.12.,
ii) be installed without furring members over gypsum sheathing at least
12.7 mm thick or over masonry,
iii) have a flame-spread rating not greater than
25 when tested in accordance with Sentence 3.1.12.1.(2), and
iv) not exceed 2 mm in thickness exclusive of fasteners, joints
and local reinforcements, or
c) the wall assembly shall comply with Sentences 3.1.5.5.(3) and (4) when tested in
conformance with CAN/ULC-S134, “Fire Test of Exterior Wall Assemblies.”
3) 
Except as provided in
Sentence (4), where the
limiting distance is equal to or greater than 0.6 m and less than 1.2 m, the
exposing building face and any exterior wall located above the
exposing building face that encloses an
attic or roof space shall have a
fire-resistance rating of not less than 45 min, and
b) the cladding shall
ii) be installed without furring members, or on furring not more than 25 mm thick, over gypsum sheathing at least 12.7 mm thick or over masonry, and
iii) after conditioning in conformance with ASTM D 2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing,” have a flame-spread rating not greater than 25 when tested in accordance with Sentence 3.1.12.1.(2), c) the cladding shall
ii) be installed with or without furring members over gypsum sheathing at least 12.7 mm thick or over masonry,
iv) not exceed 2 mm in thickness exclusive of fasteners, joints and local reinforcements, or

NC2010 2010-01-01 R1
3) 
Except as provided in Sentence (4), where the
limiting distance is equal to or greater than 0.6 m and less than 1.2 m, the
exposing building face and any exterior wall located above the
exposing building face that encloses an
attic or roof space shall have a
fire-resistance rating of not less than 45 min, and
a) the cladding shall be metal or noncombustible cladding installed in accordance with Section 9.20., 9.27. or 9.28.(See(seeA-9.10.14.5.(1) in Appendix A),
b) the cladding shall
i) conform to Subsection 9.27.6., 9.27.7., 9.27.8., 9.27.9., or 9.27.10.,
ii) be installed without furring members, or on furring not more than 25 mm thick, over gypsum sheathing at least 12.7 mm thick or over masonry, and
iii) after conditioning in conformance with ASTM D 2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing,” have a flame-spread rating not greater than 25 when tested in accordance with Sentence 3.1.12.1.(2),
c) the cladding shall
i) conform to Subsection 9.27.12.,
ii) be installed with or without furring members over gypsum sheathing at least 12.7 mm thick or over masonry,
iii) have a flame-spread rating not greater than 25 when tested in accordance with Sentence 3.1.12.1.(2), and
iv) not exceed 2 mm in thickness exclusive of fasteners, joints and local reinforcements, or
d) the wall assembly shall comply with Sentences 3.1.5.5.(3) and (4) when tested in conformance with CAN/ULC-S134, “Fire Test of Exterior Wall Assemblies.”
5) 
Except as provided in
Sentence (6)
,
combustible projections on the exterior of a wall that are more than 1 m above ground level and that could expose an adjacent
building to fire spread shall not be permitted within
a) 1.2 m of a property line or the centre line of
a
public way, or
7) Where
combustible projections on an
exposing building face are permitted by
Sentence (6), are totally enclosed and constructed with solid faces, such as for fireplaces and
chimneys, and extend within 1.2 m of a property line,
b) where the underside of the projection is more than 0.6 m above
finished ground level, it shall be protected by
iv) not less than 11 mm thick plywood,
v) not less than 12.5 mm thick OSB or waferboard, or
vi) not less than 11 mm thick lumber.
(See A-9.10.14.5.(8) in Appendix A.)
NC2010 2010-01-01 R1
7) 
Where
combustible projections on an
exposing building face are permitted by Sentence (6), are totally enclosed and constructed with solid faces, such as for fireplaces and
chimneys, and extend within 1.2 m of a property
line,
a) the constructionconstruction of the face and sides of the projection shall comply with the
corresponding requirements for exposing building
faces for limiting distances less than
1.2 m as stated in Sentence (2) or (3), and
b) where the underside of the projection is more than 0.6 m above
finished ground level, it shall be protected by
i) not less than 0.38 mm thick noncombustible material,
ii) unvented aluminum conforming to CAN/CGSB-93.2-M, “Prefinished Aluminum Siding, Soffits, and Fascia, for Residential
Use,”
iii) not less than 12.7 mm thick gypsum soffit board or gypsum
ceiling board installed according to CSA A82.31-M, “Gypsum Board Application,”
iv) not less than 11 mm thick plywood,
v) not less than 12.5 mm thick OSB or waferboard, or
vi) not less than 11 mm thick lumber.
(See A-9.10.14.5.(8) in Appendix
A.)
10) 
Roof soffits located within 1.2 m of a property line or the centre line of a
public way, or located within 1.2 m of an imaginary line between two
buildings or two
fire compartments on the same property, shall

a) have no openings, and
b) be protected by
i) no less than 0.38 mm thick sheet steel,
iv) no less than 11 mm thick plywood,
v) no less than 12.5 mm thick OSB or waferboard, or
vi) no less than 11 mm thick lumber.
(See A-3.2.3.6.(2) in Appendix A.)
NC2010 2010-01-01 R1
10) 
Roof soffits located within Where roof soffits project to less than 1.2 m
of afrom the property line
or , the centre line of a
public way, or located within 1.2 mlane or public thoroughfare orof an imaginary line between two
buildings or
two fire compartments on the same property,
they shall
a) have no openings, and
b) be protected by
i) nonot less than 0.38 mm thick sheet steel,
ii) unvented aluminum conforming to CAN/CGSB-93.2-M, “Prefinished Aluminum Siding, Soffits, and Fascia, for Residential
Use,”
iii) nonot less than 12.7 mm thick gypsum soffit board or gypsum
ceiling board installed according to CSA A82.31-M, “Gypsum Board Application,”
iv) nonot less than 11 mm thick plywood,
v) nonot less than 12.5 mm thick OSB or waferboard, or
vi) nonot less than 11 mm thick lumber.
(See A-3.2.3.6.(2) in Appendix A.)
11) For
buildings of
combustible construction, materials installed to provide the required protection for soffits may be covered with a
combustible or
noncombustible finish material.


NC2010 2010-01-01 R1
11) 
For
buildings of
combustible construction construction, materials installed to provide the required protection for soffits may be covered with a
combustible
or
noncombustible finish material.

VC2014 2014-03-01 R1
9.10.15.5. Construction of Exposing Building Face of Houses
13) If a
building is
sprinklered, and the maximum percentage of
unprotected openings complies with Sentence 9.10.15.4.(7), the
exposing building faces may be constructed with a wood stud wall assembly provided
a) the exposing building face has a one hour fire-resistance rating,
b) the wall assembly is of non-combustible construction throughout excepting structural elements and sheathing, andthe void spaces between studs are filled with non-combustible insulation, and
c) the wall assembly is clad with non-combustible cladding.
9.10.16. Fire
Blocks
9.10.16.1. Required Fire
Blocks
in Concealed Spaces
1) 
Vertical concealed spaces in interior walls and exterior walls shall be separated by
fire blocks
a) one from the other, and
b) from horizontal concealed spaces.
2) 
Horizontal concealed spaces in attics, roof spaces, ceilings, floors, and crawl spaces shall be separated by
fire blocks
a) one from the other, and
b) from vertical concealed spaces.
3)
Fire blocks
shall be provided at all interconnections between concealed vertical and horizontal spaces in interior coved ceilings, drop ceilings and soffits where
the exposed
construction materials within the concealed spaces have a surface
flame-spread rating greater than 25.

NC2010 2010-01-01 R1
3) 
Fire blocks shall be provided at all interconnections between concealed vertical and horizontal spaces in interior coved ceilings, drop ceilings and soffits where
the exposed
constructionconstruction materials within the concealed spaces have a surface
flame-spread rating greater than 25.
4)
Fire blocks
shall be provided at the top and bottom of each run of stairs where they pass through a floor containing concealed space in which the exposed
construction materials within the space have a surface
flame-spread rating greater than 25.

NC2010 2010-01-01 R1
4) 
Fire blocks shall be provided at the top and bottom of each run of stairs where they pass through a floor containing concealed space in which the exposed
constructionconstruction materials within the space have a surface
flame-spread rating greater than 25.
5) In unsprinklered
buildings of
combustible construction, every concealed space created by a ceiling, roof space or unoccupied attic space shall be separated by
fire blocks
into compartments
a) not more than 60 m in greatest dimension, and

NC2010 2010-01-01 R1
5) 
In unsprinklered
buildings of
combustible construction construction, every concealed space created by a ceiling, roof space or unoccupied attic space shall be separated by
fire blocks into compartments
a) not more than 60 m in greatest dimension, and
b) where such space contains exposed constructionconstruction materials having a surface
flame-spread rating greater than 25, not more
than 300 m2 in area.
6) 
No dimension of the concealed space described in
Clause (5)(b) shall exceed 20 m.
7) Concealed spaces in mansard or gambrel style roofs, exterior cornices, balconies
and canopies of
combustible construction in which the exposed
construction materials within the space have a surface
flame-spread rating exceeding 25 shall have vertical
fire blocks
at intervals of not more than 20 m and at points where such concealed spaces extend across the ends of required vertical
fire separations.

NC2010 2010-01-01 R1
7) 
Concealed spaces in mansard or gambrel style roofs, exterior cornices, balconies and canopies of
combustible construction construction in which the
exposed
constructionconstruction materials within the space have a surface
flame-spread rating exceeding 25 shall have vertical
fire blocks at intervals of not more than 20 m and at points where
such concealed spaces extend across the ends of required vertical
fire separations.
9.10.16.2. Required Fire
Blocks
in Wall Assemblies
1) 
Except as permitted in
Sentence (2),
fire blocks
shall be provided to block off concealed spaces within wall assemblies, including spaces created by furring,
a) at each floor level,
c) at other locations within the wall, so that the distance between
fire blocks does not exceed 20 m horizontally and 3 m vertically.
2) Fire blocks described in
Sentence (1) are not required, provided
a)

the insulated wall assembly contains not more than one concealed air space whose horizontal thickness is not more than

25 mm,
c) the exposed
construction materials within the space, including insulation, but not including wiring, piping or similar services, have a
flame-spread rating of not more than 25, or
d) the concealed wall space is filled with insulation.

NC2010 2010-01-01 R1
2) 
Fire blocks described in Sentence (1) are not required, provided
a) the insulated wall assembly contains not more than
one concealed air space whose horizontal thickness is not more than 25 mm,
b) the exposed constructionconstruction materials within the space are noncombustible,
c) the exposed constructionconstruction materials within the space, including insulation, but
not including wiring, piping or similar services, have a flame-spread rating of not more than 25, or
d) the concealed wall space is filled with insulation.
9.10.16.3. Fire
Block
Materials
2) 
Fire blocks are deemed to comply with
Sentence (1) if they are

constructed of not less than
a) 0.38 mm sheet steel,
b) 12.7 mm gypsum wallboard,
c) 12.5 mm plywood, OSB or waferboard, with joints having continuous supports,
d) 2 layers of 19 mm lumber with joints staggered,
or
e) 38 mm lumber.
3) 
In a
building permitted to be of
combustible construction, semi-rigid fibre insulation board produced from glass, rock or slag is permitted to
be used to block the vertical space in a double-frame wall assembly
formed at the intersection of the floor assembly and the walls, provided
the width of the vertical space does not exceed 25 mm and the insulation board
a) has a density not less than 45 kg/m3,
b) is securely fastened to one set of studs,
c) extends from below the bottom of the top plates in the lower
storey to above the top of the bottom plate in the upper
storey, and
d) completely fills the portion of the vertical space between the
headers and between the wall plates.
(See A-3.1.11.7.(7) in Appendix A.) 9.10.16.4. Penetration of Fire
Blocks
1) 
Where
fire blocks
are pierced by pipes, ducts or other elements, the effectiveness of the
fire blocks shall be maintained around such elements.
9.10.17. Flame Spread Limits
9.10.17.1. Flame Spread Rating of Interior Surfaces
1) 
Except as otherwise provided in this Subsection, the exposed surface of every interior wall and ceiling, including skylights and
glazing, shall have a surface
flame-spread rating of not more than 150.
9.10.17.2. Ceilings in Exits or Public Corridors
1) At least 90

per cent

of the exposed surface of every ceiling in an
exit or unsprinklered ceiling in a
public corridor shall have a surface
flame-spread rating of not more than 25. (See
Article 9.10.17.6.)

NC2010 2010-01-01 R1
1) 
At least
90 per cent 90% of the exposed surface of every ceiling in an
exit or unsprinklered ceiling in a
public corridor shall have a surface
flame-spread
rating of not more than 25. (See Article 9.10.17.6.)
9.10.17.3. Walls in Exits
1) Except as provided in
Sentence (2), at least 90

per cent

of the exposed surfaces of every wall in an
exit shall have a surface
flame-spread rating of not more than 25. (See
Article 9.10.17.6.)

NC2010 2010-01-01 R1
1) 
Except as provided in Sentence (2), at least
90 per cent 90% of the exposed surfaces of every wall in an
exit shall have a surface
flame-spread
rating of not more than 25. (See Article 9.10.17.6.)
2) At least 75

per cent

of the wall surface of a lobby used as an
exit in
Article 9.9.8.5. shall have a surface
flame-spread rating of not more than 25. (See
Article 9.10.17.6.)

NC2010 2010-01-01 R1
2) 
At least
75 per cent 75% of the wall surface of a lobby used as an
exit in Article 9.9.8.5. shall have a surface
flame-spread rating of not more than 25. (See Article 9.10.17.6.)
9.10.17.4. Exterior Exit Passageways
1) Where an exterior
exit passageway provides the only
means of egress from the rooms or
suites it serves, the wall and ceiling finishes of that passageway, including the soffit beneath and the
guard on the passageway, shall have a surface
flame-spread rating of not more than 25, except that up to 10

per cent

of the total wall area and 10

per cent

of the total ceiling area is permitted to have a surface
flame-spread rating of not more than 150.

NC2010 2010-01-01 R1
1) 
Where an exterior
exit passageway provides the only
means of egress from the rooms or
suites it serves, the wall and ceiling finishes of that passageway, including the soffit beneath and the
guard on the
passageway, shall have a surface
flame-spread rating
of not more than 25, except that up to
10 per cent 10% of the total wall area and
10 per cent 10% of the
total ceiling area is permitted to have a surface
flame-spread rating of not more than 150.
9.10.17.5. Walls in Public Corridors
1) At least 90

per cent

of the total wall surface in any unsprinklered
public corridor shall have a surface
flame-spread rating of not more than 75, or at least 90

per cent

of the upper half of such walls shall have a surface
flame-spread rating of not more than 25. (See
Article 9.10.17.6.)

NC2010 2010-01-01 R1
1) 
At least
90 per cent 90% of the total wall surface in any unsprinklered
public corridor shall have a surface
flame-spread rating of not more than 75, or at least
90 per cent 90% of the upper half of such
walls shall have a surface
flame-spread rating of not
more than 25. (See Article 9.10.17.6.)
9.10.17.6. Calculation of Wall and Ceiling Areas
1) 
Skylights, glazing,
combustible doors, and
combustible light diffusers and lenses shall not be considered in the calculation of wall and ceiling areas
in this Subsection.
9.10.17.7. Corridors Containing an Occupancy
9.10.17.8. Light Diffusers and Lenses
9.10.17.9. Combustible Skylights
1) 
Individual
combustible skylights in corridors required to be separated from the remainder of the
building by
fire separations shall not exceed 1 m
2 in area and shall be spaced not less than 1.2 m apart.
9.10.17.10. Protection of Foamed Plastics
1) 
Except as provided in
Sentence (2), foamed plastics which form part of a wall or ceiling assembly in
combustible construction shall be protected from adjacent space in the
building, other than adjacent concealed spaces within
attic or roof spaces, crawl spaces, and wall assemblies, by
b) sheet metal mechanically fastened to the supporting assembly
independent of the insulation and having a thickness of not less than 0.38 mm and a melting point not below 650°C,
provided the
building does not contain a Group C
major occupancy, or
2) 
Thermosetting foamed plastic insulation having a
flame-spread rating of not more than 200 is permitted to be used in factory-assembled doors in
storage garages serving single
dwelling units provided that
a) the insulation is covered on the interior with a metallic foil,
c) the assembly incorporates no air spaces.
9.10.17.11. Walls and Ceilings in Bathrooms
9.10.17.12. Coverings or Linings of Ducts
9.10.18. Alarm and Detection Systems
9.10.18.1. Access Provided through a Firewall
1) 
Where access is provided through a
firewall, the requirements in this Subsection shall apply to the
floor areas on both sides of the
firewall as if they were in the same
building.
9.10.18.2. Fire Alarm System Required
1) 
Except as permitted in
Sentences (3) , (4) and (5), a fire alarm system shall be installed in
buildings in which a
sprinkler system is required by this Part.
(See Appendix.)

VC2014 2015-01-01 R1BC2012 2012-01-01 R1NC2010 2010-01-01 R1
1) Except as permitted in Sentences (3) , (4) and (5), a fire alarm system shall be installed in buildings in which a sprinkler system is required by this Part. (See Appendix.)
1) Except as permitted in Sentences (3) , (4) and (5), a fire alarm system shall be installed in buildings in which a sprinkler systemsprinklersystem is required by this Part. (See Appendix.)
1) 
Except as permitted in Sentences (3)
, (4)
and (5), a fire alarm system shall be installed in
buildings in which a
sprinkler systemsprinkleris required by this Partsystem is installed.
(See Appendix.)
2) 
Except as provided in
Sentence (5), a fire alarm system shall be installed
3) 
In
buildings in which a
sprinkler system has been installed in accordance with NFPA 13D, “Installation of Sprinkler Systems in One- and Two-Family Dwellings and
Manufactured Homes,” a fire alarm system need not be installed.

NC2010 2010-01-01 R1
3) 
In
buildings in which a
sprinkler systemsprinklersystem has been installed in accordance with NFPA 13D, “Installation of Sprinkler Systems in One- and Two-Family Dwellings and
Manufactured Homes,” a fire alarm system need not be installed.
9.10.18.3. Design and Installation Requirements
1) 
Except

as stated in
Sentence (2) and

as required by this Subsection, where fire alarm, fire detection and smoke detection devices and systems
are installed, these devices and systems and their installation shall
conform to
Subsection 3.2.4. 9.10.18.4. Rooms and Spaces Requiring Heat Detectors or Smoke Detectors
2) 

Except as provided in
Sentence (3), if a fire alarm system is required in a
building that is not
sprinklered,
fire detectors shall be installed in the following spaces:
c) janitors’ rooms
d) rooms in which hazardous substances are to be used or stored
(see
A-3.3.1.2.(1) in Appendix A),
e) elevator hoistways, chutes and dumbwaiter shafts, and
3) 
Except as required in
Sentence (4),
heat detectors and
smoke detectors described in
Sentence (2) are not required in
dwelling units or in
sprinklered buildings in which the
sprinkler system is electrically supervised and equipped with a water flow alarm.

NC2010 2010-01-01 R1
3) 
Except as required in Sentence (4), heat detectorsHeat detectors and
smoke detectors described in
Sentence (2) are not required in
dwelling units or in
sprinklered buildings in which the
sprinkler system sprinklersystem is electrically supervised and equipped with a water flow
alarm.
9.10.18.5. Smoke Detectors in Recirculating Air-Handling Systems
1) 
Except for a recirculating air system serving not more than one
dwelling unit, where a fire alarm system is required to be installed, every recirculating air-handling
system shall be designed to prevent the circulation of smoke upon
a signal from a duct-type
smoke detector where such system supplies more than one
suite on the same floor or serves more than 1
storey.
9.10.18.6. Portions of Buildings Considered as Separate Buildings
9.10.18.7. Central Vacuum Systems
1) 
Central vacuum cleaning systems

serving more than one
suite or
storey
in
buildings equipped with a fire alarm system shall be designed to shut down upon activation
of the fire alarm system.
9.10.18.8. Open-Air Storage Garages
9.10.19. Smoke Alarms
9.10.19.1. Required Smoke Alarms
1) Smoke alarms conforming to
CAN/ULC-S531, “Standard for Smoke Alarms,”
shall be installed in

NC2010 2010-01-01 R1
1) 
Smoke alarms conforming to CAN/ULC-S531, “Standard for Smoke Alarms,” shall be installed in
a) each dwelling unit, and
b) each sleeping room not within a dwelling
unit., and
c) ancillary spaces and common spaces not in dwelling units in a house with a secondary suite.
2) 
All
smoke alarms installed in
dwelling units in unsprinklered
buildings shall be equipped with a battery powered back up system and a wired in manually operated device which is capable of silencing a
smoke alarm signal for a period of not more than 10 minutes and re-sounding the signal if smoke levels in the vicinity trigger the
smoke alarm.

9.10.19.2.
Sound Patterns of Smoke Alarms
1) 
The sound patterns of
smoke alarms shall
b) be a combination of temporal pattern and voice relay.

9.10.19.3. Location of Smoke Alarms
9.10.19.4. Power Supply
1) 

Except as provided in
Sentences (2) and (3),
smoke alarms 
described in
Sentence 9.10.19.1.(1)
shall
a) be installed with permanent connections to an electrical circuit

(see
A-3.2.4.21.(6)(a) in Appendix A),

b) have no disconnect switch between the overcurrent device and the
smoke alarm, and
c)

in case the regular power supply to the
smoke alarm is interrupted, be provided with a battery as an alternative power source that can continue to provide
power to the
smoke alarm for a period of no less than 7 days in the normal condition, followed
by 4 minutes of alarm.

2) 
Where the
building is not supplied with electrical power,
smoke alarms are permitted to be battery-operated.
3)
Suites of
residential occupancy are permitted to be equipped with
smoke detectors in lieu of
smoke alarms, provided the
smoke detectorsa) are capable of independently sounding audible signals within the individual
suites,
c) form part of the fire alarm system.
(See A-3.2.4.21.(7) in Appendix A.)
NC2010 2010-01-01 R1
3) 
Suites of
residential occupancy are permitted to be equipped with
smoke detectors in lieu of
smoke alarms, provided the
smoke detectorsa) are capable of independently sounding audible signals within the individual suites,
b) except as permitted in Sentence (4), are installed in conformance with CAN/ULC-S524, “Installation of Fire Alarm Systems,” and
c) form part of the fire alarm system.
(See A-3.2.4.21.(7) in Appendix A.)
9.10.19.5. Interconnection of Smoke Alarms

NC2010 2010-01-01 R1
9.10.19.5. Interconnection of Smoke Alarms
1) 
Where more than one
smoke alarm is required in a
dwelling unit, the
smoke alarms shall be wired so that the activation of one alarm will cause all
alarms within the
dwelling unit to sound.
2)
Smoke alarms in a house with a
secondary suite shall be wired so that the activation of any one
smoke alarm causes all
smoke alarms within the house with a
secondary suite to sound.
9.10.19.6.
Silencing of Smoke Alarms
1) 
Except as permitted in
Sentence (2), a manually operated device shall be incorporated within the circuitry of a
smoke alarm installed in a
dwelling unit so that the signal emitted by the
smoke alarm can be silenced for a period of not more than 10 min, after which the
smoke alarm will reset and sound again if the level of smoke in the vicinity is sufficient to re-actuate it.
9.10.19.7. Instructions for Maintenance and Care
1) 
Where instructions are necessary to describe the maintenance and care required for
smoke alarms to ensure continuing satisfactory performance, they shall be posted in
a location where they will be readily available to the occupants for
reference.
9.10.20. Firefighting
9.10.20.1. Windows or Access Panels Required
1) 
Except as provided in
Sentence (3), a window or access panel providing an opening not less than 1 100 mm high and 550 mm wide and having a sill height of not more than 900 mm above the floor shall
be provided on the second and third
storeys of every
building in at least one wall facing on a
street if such
storeys are not
sprinklered.
2) 
Access panels required in
Sentence (1) shall be readily openable from both inside and outside or be glazed with plain glass.
3) Access panels required in
Sentence (1) need not be provided in
buildings containing only
dwelling units where there is no
dwelling unit above another
dwelling unit.

NC2010 2010-01-01 R1
3) 
Access panels required in Sentence (1) need not be provided in
buildings containing only dwelling units where there is no dwelling unit above another dwelling
unit.
a) buildings containing only dwelling units where there is no dwelling unit above another dwelling unit, or
b) houses with a secondary suite.
9.10.20.2. Access to Basements
1) Except in
basements serving not more than one
dwelling unit, each unsprinklered
basement exceeding 25 m in length or width shall be provided with direct access to the outdoors to at least one
street.

NC2010 2010-01-01 R1
1) 
Except
for basementsin
houses with a secondary suite or basements serving not more than one
dwelling unit, each unsprinklered
basement exceeding 25 m in length or width shall be provided with direct access to the outdoors to at least one
street.
2) 
Access required in
Sentence (1) may be provided by a door, window or other means that provides an opening
not less than 1 100 mm high and 550 mm wide,
the sill height of which shall not be more than 900 mm above the floor.
3) 
Access required in
Sentence (1) may also be provided by an interior stair accessible from the outdoors.
9.10.20.3. Fire Department Access to Buildings
1) Access for fire department

vehicles

shall be provided to each

principal entrance of a
building in accordance with
Articles 3.2.5.4., 3.2.5.5. and 3.2.5.6.

NC2010 2010-01-01 R1
1) 
Access for fire department
vehiclesequipment shall be provided to each
principal entrance building by means of a
building in accordance with
Articles 3.2.5.4., 3.2.5.5. and 3.2.5.6.street, private roadway
or yard. (See Appendix A and A-3.2.5.6.(1) in Appendix A.)
2) 
Where access to a
building as required in
Sentence (1) is provided by means of a roadway or yard, the design and location of such roadway or yard
shall take into account connection with public thoroughfares, weight
of firefighting equipment, width of roadway, radius of curves, overhead
clearance, location of fire hydrants, location of fire department
connections and vehicular parking.
3) 
Despite the provisions of
Sentence (1), an unobstructed path of travel for firefighters shall be provided to an
ancillary residential building and the path of travel shall:
c) be at least 900 mm wide,
d) have an overhead clearance of at least 2 m, and
e) consist of concrete, asphalt, or similar material.
7) Two adjacent parcels may have a single shared path of travel for firefighters over
the common property line and the adjacent specified area to access both, provided
b) each parcel is subject to a covenant registered on title which prohibits construction
upon or obstruction of the common property line and of a specified area adjacent to
the property line; and

VC2014 2014-03-01 R1
9.10.20.3. Fire Department Access to Buildings
3) Despite the provisions of Sentence (1), an unobstructed path of travel for firefighters shall be provided to
anaancillary residential buildinglaneway house and the path of travel shall:
a) lead continuously from the street to the lane,
b) have a travel distance of no more than 45 m from the street to the principal entrance of the ancillary residential buildinglaneway house,
c) be at least 900 mm wide,
d) have an overhead clearance of at least 2 m, and
e) consist of concrete, asphalt, or similar material.
4) AnAancillary residential buildinglaneway house shall have a strobe light installed and maintained outside the principal entrance,
connected to an internal smoke alarm within the ancillary residential buildinglaneway house.
5) Despite Clause 9.10.20.3.(3)(b) the path of travel for firefighters towards not more than one ancillary residential building on a parcel may exceed may be greater than 45 mto a maximum ofbut not more than70 m provided the principal entrance to thattheancillary residential buildinglaneway house is visible from the street.
6) If the principal
building and the
ancillary residential buildinglaneway house are adjacent to a
lane, the path of foot travel for firefighters to the
ancillary residential buildinglaneway house may be through the
lane if
a) the travel distance from the street to the principal entrance of the ancillary residential buildinglanewayhouse is no more than 70 m,
b) the path has an overhead clearance of at least 3 m,
c) the path consists of concrete, asphalt, or similar material, and
d) the principal entrance of the ancillary residential buildinglaneway house is visible from the street.
7) Two adjacent parcels may have a single shared path of travel for firefighters over
the common property line and the adjacent specified area to access both, provided
a) each parcel contains an ancillary residential building,
b) each parcel is subject to a covenant registered on title which prohibits construction
upon or obstruction of the common property line and of a specified area adjacent to
the property line; and
c) the path of travel meets the requirements of Sentences (3) , (4) and (5).
7) If two adjacent parcels, each containing a laneway house, are both subject to a covenant registered on title which prohibits construction upon or obstruction of the common property line and of a specified area adjacent
to the property line, a single path of travel for firefighters over the common property
line and the adjacent specified area to access both laneway houses is acceptable, provided the path of travel meets the requirements of Sentences (3), (4) and (5).
9.10.20.4. Portable Extinguishers
1) Portable extinguishers shall be installed in all
buildings, except within
dwelling units, in conformance with the

Fire By-law

.

BC2012 2012-01-01 R1NC2010 2010-01-01 R1
1) Portable extinguishers shall be installed in all buildings, except within dwelling units,
in conformance with the British Columbia Fire By-lawCode.
1) 
Portable extinguishers shall be installed in all
buildings, except within
dwelling units, in conformance with the
Fire By-lawappropriate provincial or territorial regulations or municipal bylaws or, in the absence
of such regulations or bylaws, the NFC.
9.10.20.5. Freeze Protection of Fire Protection Systems
1) 
Equipment forming part of a fire protection system that may be adversely affected by freezing temperatures and that is located
in an unheated area shall be protected from freezing.
9.10.21. Fire Protection for Construction Camps
9.10.21.1. Requirements for Construction Camps
9.10.21.2. Separation of Sleeping Rooms
1) Except for sleeping rooms within
dwelling units, sleeping rooms in
construction camps shall be separated from each other and from the remainder of the
building by a
fire separation having not less than a 30 min
fire-resistance rating.

NC2010 2010-01-01 R1
1) 
Except for sleeping rooms within
dwelling units, sleeping rooms in
constructionconstruction camps shall be separated from each other and from the
remainder of the
building by a
fire
separation having not less than a 30 min
fire-resistance rating.
9.10.21.3. Floor Assemblies between the First and Second Storey
1) Except in a
dwelling unit, a floor assembly in a
construction camp
building separating the
first storey and the second
storey shall be constructed as a
fire separation having not less than a 30 min
fire-resistance rating.

NC2010 2010-01-01 R1
1) 
Except in a
dwelling unit, a floor assembly in a
constructionconstruction camp
building separating the
first storey and the second
storey
shall be constructed as a
fire separation having not
less than a 30 min
fire-resistance
rating.
9.10.21.4. Walkways Connecting Buildings
9.10.21.5. Spatial Separations
1) Construction camp
buildings shall be separated from each other by a distance of not less than 10 m except as otherwise
permitted in
Subsections 9.10.14. and 9.10.15.
NC2010 2010-01-01 R1
1) 
ConstructionConstruction camp
buildings shall be separated from each other by a distance of not less than 10 m except as otherwise
permitted in Subsections 9.10.14. and 9.10.15.
9.10.21.6. Flame-Spread Ratings
1) Except in
dwelling units and except as provided in
Sentence (2), the surface
flame-spread rating of wall and ceiling surfaces in corridors and
walkways, exclusive of doors, shall not exceed 25 over not less than 90

per cent

of the exposed surface area and not more than 150 over the remaining surface area.

NC2010 2010-01-01 R1
1) 
Except in
dwelling units and except as provided in Sentence (2), the surface
flame-spread rating of wall and ceiling surfaces in
corridors and
walkways, exclusive of doors, shall not
exceed 25 over not less than
90 per cent 90% of the exposed surface area and not more than 150
over the remaining surface area.
9.10.21.7. Smoke Detectors
1) Except in
dwelling units, corridors providing
access to exit from sleeping rooms in
construction camp
buildings with sleeping accommodation for more than 10 persons shall be provided with a
smoke detector connected to the
building alarm system.

NC2010 2010-01-01 R1
1) 
Except in
dwelling units, corridors providing
access to exit from sleeping rooms in
constructionconstruction camp
buildings with sleeping accommodation for more than
10 persons shall be provided with a
smoke detector
connected to the
building alarm system.
9.10.21.8. Portable Fire Extinguishers
1) Each
construction camp
building shall be provided with portable fire extinguishers in conformance with the appropriate provincial or
territorial regulations or municipal bylaws or, in the absence of such regulations
or bylaws, in conformance with the

Fire By-law

.

BC2012 2012-01-01 R1NC2010 2010-01-01 R1
1) Each constructionconstruction camp building shall be provided with
portable fire extinguishers in conformance with the appropriate provincial or
territorial regulations or municipal bylaws or, in the absence of such regulations
or bylaws, in conformance with the British Columbia Fire By-lawCode.
1) 
Each
constructionconstruction camp
building shall be provided with portable fire extinguishers in conformance with the appropriate provincial or
territorial regulations or municipal bylaws or, in the absence of such regulations
or bylaws, in conformance with the
Fire By-lawNFC.
9.10.21.9. Hose Stations
1) Every
construction camp
building providing sleeping accommodation for more than 30 persons shall be provided with a hose station that
is
protected from freezing and is equipped with a hose of sufficient length so that
every portion of the
building is within reach of a hose stream.

NC2010 2010-01-01 R1
1) 
Every
constructionconstruction camp
building providing sleeping accommodation for more than 30 persons shall be provided with a hose station that
is
protected from freezing and is equipped with a hose of sufficient length so that
every portion of the
building is within reach of a hose
stream.
3) 
Hoses referred to in
Sentence (1) shall be not less than 19 mm inside diam and shall be connected to a central water supply or to a storage tank having
a capacity of not less than 4 500 L with a pumping system
capable of supplying a flow of not less than 5 L/s at
a gauge pressure of 300 kPa.
9.10.22. Fire Protection for Gas, Propane and Electric
Cooktops and Ovens
(See Appendix A.)9.10.22.1. Installation of
Cooktops and Ovens
1) Except as required in
Sentence (2), natural gas and propane
cooktops and ovens

shall be installed in accordance with the British Columbia Gas Safety Regulation pursuant to the British Columbia Safety Standards Act. (See also
Article 9.34.1.1.)

NC2010 2010-01-01 R1
1) 
Except as required in Sentence (2), natural gas and propane
cooktops and
ovens shall be installed in accordance with the
British Columbia Gas
Safety Regulation pursuant to the British Columbia Safety Standards Act. applicable provincial
or territorial regulations or municipal bylaws or, in the absence of such
regulations or bylaws, with CAN/CSA-B149.1, “Natural Gas and Propane Installation Code.”(See also
Article 9.34.1.1.)
9.10.22.2. Vertical Clearances above
Cooktops
1) 
Except as provided in
Sentence (2), framing, finishes and cabinetry installed directly above the location of the
cooktop
shall be not less than 750 mm above the level of
cooktop
burners or elements.
2) The vertical clearance described in
Sentence (1) for framing, finishes and cabinets located directly above the location of the
cooktop
may be reduced to 600 mm above the level of the elements or burners, provided the framing, finishes and cabinets
b) are protected by
i)
noncombustible cementitious board
not less than 6 mm thick, covered with sheet metal not less than 0.33 mm thick, or ii) a metal hood with a 125 mm projection beyond the framing, finishes and cabinets.

NC2010 2010-01-01 R1
2) 
The vertical clearance described in Sentence (1) for framing, finishes and cabinets located directly above the location of the
cooktop may be reduced to 600 mm above the level of the elements or burners, provided the framing, finishes and cabinets
a) are noncombustible, or
b) are protected by
i) noncombustibleasbestoscementitious board millboard not less than 6 mm thick, covered with sheet metal not less than 0.33 mm thick, or
ii) a metal hood with a 125 mm projection beyond the framing, finishes and cabinets.
9.10.22.3. Protection around
Cooktops
1) 
Except as provided in
Sentences (2) and (3),
combustible wall framing, finishes or cabinets within 450 mm of the area where the
cooktop
is to be located shall be protected above the level of the heating elements or burners
by material providing fire resistance at least equivalent to that
provided by a 9.5 mm thickness of gypsum board.
2) 
Counter-top splash boards or back plates that extend above the level of heating elements or burners need not be protected as described
in
Sentence (1).
3) 
Except for cabinetry described in
Article 9.10.22.2., cabinetry located not less than 450 mm above the level of the heating elements or burners need not be protected as
described in
Sentence (1).