Division B
Acceptable Solutions

Part 9 — Housing and Small Buildings

Section 9.10. Fire Protection

9.10.1. Definitions and Application

9.10.1.1. Sloped Roofs
1) Intent StatementFor the purposes of this Section, roofs with slopes of 60° or more to the horizontal that are adjacent to a room or space intended for occupancy shall be considered as a wall.
9.10.1.2. change beginCommissioning of Life Safety and Fire Protection Systems
1) Where life safety and fire protection systems are installed to comply with the provisions of this change beginBy-lawchange end or the change beginFire By-lawchange end, the commissioning of these integrated systems must be performed as a whole to ensure the proper operation and inter-relationship of the systems. (See A-3.2.4.6.(1) in Appendix A.)change end

contentHistory

9.10.1.3. Items under Part 3 Jurisdiction
1) Intent StatementTents, air-supported structures, transformer vaults, walkways, elevators and escalators shall conform to Part 3.
2) Intent StatementWhere rooms or spaces are intended for an assembly occupancy, such rooms or spaces shall conform to Part 3.
3) Intent StatementBasements containing more than 1 storey or exceeding 600 m2 in area shall conform to Part 3.
4) Intent StatementWhere rooms or spaces are intended for the storage, manufacture or use of hazardous or explosive material, such rooms or spaces shall conform to Part 3. (See A-3.3.1.2.(1) in Appendix A.)
5) Intent StatementExcept as provided in Article 3.3.5.8., facilities for the dispensing of fuel shall not be installed in any building.
6) Intent StatementOpenings through floors that are not protected by shafts or closures shall be protected in conformance with Subsection 3.2.8. (See also Sentence 9.9.4.7.(1).)
7) Intent StatementChutes and shafts shall conform to Subsection 3.6.3. except where they are entirely contained within a dwelling unit.
8) change beginSprinkler systems shall be designed, constructed and installed in conformance with Articles 3.2.5.12. to 3.2.5.15. and 3.2.5.17.

contentHistory

9) Intent StatementStandpipe and hose systems shall be designed, constructed and installed in conformance with Articles 3.2.5.8. to 3.2.5.11. and 3.2.5.17.
10) Intent StatementFire pumps shall be installed in conformance with Articles 3.2.5.17. and 3.2.5.18.change end
11) Intent StatementWhere fuel-fired appliances are installed on a roof, such appliances shall be installed in conformance with Article 3.6.1.4.
9.10.1.4. Items under Part 6 Jurisdiction
1) Intent StatementIn kitchens containing commercial cooking equipment used in processes producing grease-laden vapours, the equipment shall be designed and installed in conformance with Article 6.2.2.7. (See Appendix A.)

9.10.2. Occupancy Classification

9.10.2.1. Occupancy Classification
1) Intent StatementExcept as provided in Article 9.10.2.2., every building or part thereof shall be classified according to its major occupancy as belonging to one of the groups or divisions described in Table 9.10.2.1.
Table 9.10.2.1.
Occupancy Classifications
Forming part of Sentence 9.10.2.1.(1)
Group Division

Description of Major Occupancies(1)

C

Residential occupancies

D

Business and personal services occupancies

E

Mercantile occupancies

F 2

Medium-hazard industrial occupancies

F 3

Low-hazard industrial occupancies (Does not include storage garages serving individual dwelling units)

Notes to Table 9.10.2.1.:

(1) See A-3.1.2.1.(1) in Appendix A.
9.10.2.2. Custodial, Convalescent and Residential Care Homes
1) Intent StatementChildren's custodial homes and convalescent homes for ambulatory occupants living as a single housekeeping unit in a dwelling unit with sleeping accommodation for not more than 10 persons are permitted to be classified as change beginGroup C, residential occupancies.change end
2) A care facility accepted for residential use pursuant to provincial legislation is permitted to be classified as a residential occupancy provided
a) the occupants live change beginas a single housekeeping unit in a dwelling unitchange end with sleeping accommodation for not more than 10 persons,
b) interconnected smoke alarms are installed in each sleeping room in addition to the requirements of Article 9.10.19.2.,
c) emergency lighting is provided in conformance with change beginArticle 9.9.12.3.change end, and
d) the building is sprinklered throughout.

contentHistory

9.10.2.3. change beginGroup A, Division 2, Low Occupant Load
1) This Part may apply to a Group A, Division 2 assembly occupancy that is permitted by Article 3.1.2.6. to be classified as Group D, business and personal services occupancy, provided the building in which the assembly occupancy is located complies with Sentence 1.3.3.3.(1) of Division A.change end
9.10.2.4. Major Occupancies above Other Major Occupancies
1) Intent StatementExcept as permitted in Article 9.10.2.5., in any building containing more than one major occupancy in which one major occupancy is located entirely above another, the requirements of Article 9.10.8.1. for each portion of the building containing a major occupancy shall be applied to that portion as if the entire building was of that major occupancy.
9.10.2.5. Buildings Containing More Than One Major Occupancy
1) In a building containing more than one major occupancy, where the aggregate area of all major occupancies in a particular group or division does not exceed 10 change beginper centchange end of the floor area on the storey on which they are located, they need not be considered as major occupancies for the purposes of Articles 9.10.8.1. and 9.10.2.4. provided they are not classified as Group F, Division 2 occupancies.

contentHistory

9.10.3. Ratings

9.10.3.1. Fire-Resistance and Fire-Protection Ratings
1) Intent StatementWhere a fire-resistance rating or a fire-protection rating is required in this Section for an element of a building, such rating shall be determined in conformance with the test methods described in Part 3, A-9.10.3.1. in Appendix A, or Appendix D.
9.10.3.2. Flame-Spread Ratings
1) Intent StatementWhere a flame-spread rating is required in this Section for an element of a building, such rating shall be determined in accordance with the test methods described in Part 3, or in accordance with Appendix D.
2) Intent StatementUnless the flame-spread rating is referred to herein as a “surface flame-spread rating,” it shall apply to any surface of the element being considered that would be exposed by cutting through it as well as to the exposed surface of the element.
9.10.3.3. Fire Exposure
1) Intent StatementFloor, roof and ceiling assemblies shall be rated for exposure to fire on the underside.
2) Exterior walls shall be rated for exposure to fire from inside the building, except that such walls need not comply with the temperature rise limitations required by the standard tests referred to in Article 9.10.3.1., if such walls have a limiting distance of not less than 1.2 m, and due allowance is made for the effects of heat radiation in accordance with the requirements in Part 3.

contentHistory

3) Intent StatementInterior vertical fire separations required to have fire-resistance ratings shall be rated for exposure to fire on each side.
9.10.3.4. Suspended Membrane Ceilings
1) Where a ceiling construction has a suspended membrane ceiling with lay-in panels or tiles which contribute to the required fire-resistance rating, hold down clips or other means shall be provided to prevent the lifting of such panels or tiles in the event of a fire.

contentHistory

9.10.4. Building Size Determination

9.10.4.1. Mezzanines not Considered as Storeys
1) Except as required by Sentences (2) and 9.10.4.2.(1), the space above a mezzanine is permitted to be excluded from the calculation of building height, provided
a) the aggregate area of mezzanines that are not superimposed does not exceed 10 change beginper centchange end of the floor area of the building in which they are located, and
b) the area of mezzanine in a suite does not exceed 10 change beginper centchange end of the area of that suite on the storey on which it is located.

contentHistory

2) Except as provided in Sentence 9.10.4.2.(1), a mezzanine need not be considered as a storey in calculating the building height provided
a) not less than 60 change beginper centchange end of the horizontal plane separating the mezzanine from the room or floor space in which it is located is open, and
b) except from within enclosures described in Sentence (3), the space above the mezzanine is used as an open area without partitions or subdividing walls higher than 1 070 mm above the mezzanine floor.
(See Appendix Note A-3.2.1.1.(3).)

contentHistory

3) The space above a mezzanine conforming to Sentence (2) is permitted to include an enclosed space whose area does not exceed 10 change beginper centchange end of the open area of the room in which the mezzanine is located, provided the enclosed space does not obstruct visual communication between the open space above the mezzanine and the room in which it is located.

contentHistory

4) Intent StatementFor the purpose of determining occupant load, the areas of mezzanines that are not considered as storeys shall be added to the floor area of the storey on which they are located. (See Appendix A.)
5) Platforms and catwalks intended solely for periodic inspection and maintenance need not be considered as floor assemblies or mezzanines for the purpose of calculating building height, provided
a) they are not used for storage, and
b) they are constructed with noncombustible materials, unless the building is permitted to be of combustible construction.

contentHistory

9.10.4.2. More Than One Level of Mezzanine
1) Intent StatementEach level of mezzanine that is partly or wholly superimposed above the first level of mezzanine shall be considered as a storey in calculating the building height.
9.10.4.3. Basement Storage Garages
1) Where a basement is used primarily as a storage garage, the basement is permitted to be considered as a separate building for the purposes of this Section provided the floor above the basement and the exterior walls of the basement above the adjoining ground level are constructed as fire separations of masonry or concrete having a fire-resistance rating of not less than 2 h, except as permitted by Sentences 3.2.1.2.(2) and (3).

contentHistory

9.10.4.4. change beginRoof-Top Enclosures
1) A roof-top enclosure shall not be considered as a storey in calculating the building height if the roof-top enclosure is
a) provided for elevator machinery, a stairway or a service room, and
b) used for no purpose other than for service to the building.change end

contentHistory

9.10.5. Permitted Openings in Wall and Ceiling Membranes

9.10.5.1. Permitted Openings in Wall and Ceiling Membranes
1) Intent StatementExcept as permitted in Sentences (2) and (4), a membrane forming part of an assembly required to have a fire-resistance rating shall not be pierced by openings into the assembly unless the assembly has been tested and rated for such openings.
2) Intent StatementA wall or ceiling membrane forming part of an assembly required to have a fire-resistance rating is permitted to be pierced by openings for electrical and similar service outlet boxes provided such outlet boxes are tightly fitted.
3) Intent StatementWhere boxes referred to in Sentence (2) are located on both sides of walls required to provide a fire-resistance rating, they shall be offset where necessary to maintain the integrity of the fire separation.
4) Intent StatementA membrane ceiling forming part of an assembly assigned a fire-resistance rating on the basis of Table A-9.10.3.1.B or Appendix D, is permitted to be pierced by openings leading to ducts within the ceiling space provided the ducts, the amount of openings and their protection conform to the requirements of Appendix D.

9.10.6. Construction Types

9.10.6.1. Combustible Elements in Noncombustible Construction
1) Intent StatementWhere a building or part of a building is required to be of noncombustible construction, combustible elements shall be limited in conformance with the requirements in Subsection 3.1.5.
9.10.6.2. Heavy Timber Construction
1) Intent StatementHeavy timber construction shall be considered to have a 45 min fire-resistance rating when it is constructed in accordance with the requirements for heavy timber construction in Article 3.1.4.7.

9.10.7. Steel Members

9.10.7.1. Protection of Steel Members
1) Except as permitted in Article 3.2.2.3., structural steel members used in change beginconstructionchange end required to have a fire-resistance rating shall be protected to provide the required fire-resistance rating.

contentHistory

9.10.8. Fire Resistance and Combustibility in Relation to Occupancy, Height and Supported Elements

9.10.8.1. Fire-Resistance Ratings for Floors and Roofs
1) Except as otherwise provided in this Subsection, the fire-resistance ratings of floors and roofs shall conform to Table 9.10.8.1. (See Subsection 9.10.2. for mixed occupancies and Subsection 9.10.21. for construction camps.)

contentHistory

Table 9.10.8.1.
Fire-Resistance Ratings for Structural Members and Assemblies
Forming part of Sentence 9.10.8.1.(1)

Major Occupancy

Maximum Building Height, storeys

Minimum Fire-Resistance Rating by Building Element, min

Floors Except Floors over Crawl Spaces

Mezzanine Floors

Roofs
Residential (Group C) 3 45 45

All other occupancies

2 45
3 45 45 45
9.10.8.2. Fire-Resistance Ratings in Sprinklered Buildings
1) The requirements in Table 9.10.8.1. for roof assemblies to have a fire-resistance rating are permitted to be waived in sprinklered buildings where
a) the sprinkler system is electrically supervised in conformance with Sentence 3.2.4.10.(3), and
b) the operation of the sprinkler system will cause a signal to be transmitted to the fire department in conformance with Sentence 3.2.4.8.(4).

contentHistory

9.10.8.3. Fire-Resistance Ratings for Walls, Columns and Arches
1) Intent StatementExcept as otherwise provided in this Subsection, all loadbearing walls, columns and arches in the storey immediately below a floor or roof assembly shall have a fire-resistance rating of not less than that required for the supported floor or roof assembly.
2) change beginReserved.change end

contentHistory

9.10.8.4. Support of Noncombustible Construction
1) Intent StatementWhere an assembly is required to be of noncombustible construction and to have a fire-resistance rating, it shall be supported by noncombustible construction.
9.10.8.5. Service Rooms
1) change beginConstructionchange end supporting a service room need not conform to Article 9.10.8.3.

contentHistory

9.10.8.6. Mezzanines
1) Intent StatementMezzanines required to be counted as storeys in Articles 9.10.4.1. and 9.10.4.2. shall be constructed in conformance with the requirements for “Floors Except Floors over Crawl Spaces” in Table 9.10.8.1.
9.10.8.7. Roofs Supporting an Occupancy
1) Intent StatementWhere a portion of a roof supports an occupancy, that portion shall be constructed as a fire separation having a fire-resistance rating conforming to the rating for “Floors Except Floors over Crawl Spaces” in Table 9.10.8.1.
9.10.8.8. Floors of Exterior Passageways
1) Intent StatementExcept as provided in Sentences (2) and (3), the floor assembly of every exterior passageway used as part of a means of egress shall have a fire-resistance rating of not less than 45 min or be of noncombustible construction.
2) Intent StatementNo fire-resistance rating is required for floors of exterior passageways serving buildings of Group D, E or F major occupancy that are not more than 2 storeys in building height.
3) No fire-resistance rating is required for floors of exterior passageways serving a single dwelling unit where no suite is located above or below the dwelling unit.

contentHistory

9.10.8.9. Crawl Spaces
1) Intent StatementWhere a crawl space exceeds 1.8 m in height or is used for any occupancy or as a plenum in combustible construction or for the passage of flue pipes, it shall be considered as a basement in applying the requirements in Article 9.10.8.1.
9.10.8.10. Application to Houses
1) Table 9.10.8.1. does not apply to a dwelling unit that has no other dwelling unit above or below it, or to a dwelling unit that is not above or below another major occupancy.

contentHistory

9.10.8.11. Part 3 as an Alternative
1) Intent StatementThe fire-resistance ratings of floors, roofs, loadbearing walls, columns and arches need not conform to this Subsection if such assemblies conform in all respects to the appropriate requirements in Section 3.2.

9.10.9. Fire Separations between Rooms and Spaces within Buildings

contentHistory

9.10.9.1. Application
1) This Subsection applies to fire separations required between rooms and spaces in buildings, except between rooms and spaces within a dwelling unit.

contentHistory

9.10.9.2. Continuous Barrier
1) Intent StatementExcept as permitted in Article 9.10.9.3., a wall or floor assembly required to be a fire separation shall be constructed as a continuous barrier against the spread of fire change beginand retard the passage of smokechange end.
2) change beginReserved.change end

contentHistory

3) The continuity of a fire separation shall be maintained where it abuts another fire separation, a floor, a ceiling, a roof, or an exterior wall assembly. (See A-3.1.8.3.(4).)

contentHistory

4) change beginReserved.change end

contentHistory

9.10.9.3. Openings to be Protected with Closures
1) Intent StatementExcept as permitted in Articles 9.10.9.5., 9.10.9.6. and 9.10.9.7., openings in required fire separations shall be protected with closures conforming to Subsection 9.10.13.
2) change beginReserved.change end

contentHistory

9.10.9.4. Floor Assemblies
1) Intent StatementExcept as permitted in Sentences (2) to (4), all floor assemblies shall be constructed as fire separations.
2) Floor assemblies contained within dwelling units need not be constructed as fire separations.

contentHistory

3) Intent StatementFloor assemblies for which no fire-resistance rating is required by Subsection 9.10.8. and floors of mezzanines not required to be counted as storeys in Articles 9.10.4.1. and 9.10.4.2. need not be constructed as fire separations.
4) Intent StatementWhere a crawl space is not required by Article 9.10.8.9. to be constructed as a basement, the floor above it need not be constructed as a fire separation.
9.10.9.5. Interconnected Floor Spaces
1) Intent StatementInterconnected floor spaces shall conform to Subsection 3.2.8.
9.10.9.6. Penetration of Fire Separations
(See A-3.1.9. in Appendix A.)
1) Intent StatementPiping, tubing, ducts, chimneys, wiring, conduit, electrical outlet boxes and other similar service equipment that penetrate a required fire separation shall be tightly fitted or fire stopped to maintain the integrity of the separation. (See Appendix A.)
2) Intent Statementchange beginPenetrations of a firewall shall be sealed at the penetration by a fire stop that, when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems,” has an FT rating not less than the fire-resistance rating for the fire separation.change end
3) Intent StatementExcept as provided in Sentences (4) to (12) and Article 9.10.9.7., pipes, ducts, electrical boxes, totally enclosed raceways or other similar service equipment that partly or wholly penetrate an assembly required to have a fire-resistance rating shall be noncombustible unless the assembly has been tested incorporating such equipment. (See A-3.1.9.2.(1) in Appendix A.)
4) Intent StatementElectrical wires or similar wiring enclosed in noncombustible totally enclosed raceways are permitted to partly or wholly penetrate an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required in Sentence (3).
5) Intent Statementchange beginSingle conductor metal-sheathed cables with combustible jacketting that are more than 25 mm in overall diameter are permitted to penetrate a fire separation required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required in Sentence (2), provided the cables are not grouped and are spaced a minimum of 300 mm apart.change end
6) Intent StatementElectrical wires or cables, single or grouped, with combustible insulation or jacketting that is not totally enclosed in raceways of noncombustible material, are permitted to partly or wholly penetrate an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required in Sentence (3), provided the overall diameter of the wiring is not more than 25 mm.
7) Intent StatementCombustible totally enclosed raceways which are embedded in a concrete floor slab are permitted in an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required in Sentence (3), where the concrete provides not less than 50 mm of cover between the raceway and the bottom of the slab.
8) Intent StatementCombustible outlet boxes are permitted in an assembly required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required in Sentence (3), provided the opening through the membrane into the box does not exceed 160 cm2.
9) Intent StatementCombustible water distribution piping is permitted to partly or wholly penetrate a fire separation that is required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required in Sentence (3), provided the piping is change beginprotected with a fire stop in conformance with Sentence 3.1.9.4.(4)change end.
10) Intent StatementCombustible sprinkler piping is permitted to penetrate a fire separation provided the fire compartments on each side of the fire separation are sprinklered.
11) Intent Statementchange beginSprinklers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the fire stop requirements of Sentence (1), provided the annular space created by the penetration of a fire sprinkler is covered by a metal escutcheon plate in accordance with NFPA 13, “Installation of Sprinkler Systems.”change end
12) Intent StatementCombustible piping for central vacuum systems is permitted to penetrate a fire separation provided the installation conforms to the requirements that apply to combustible drain, waste and vent piping specified in Sentences 9.10.9.7.(2) to (6).
13) Intent Statementchange beginFire dampers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the fire stop requirements of Sentence (1), provided the fire damper is
a) installed in conformance with NFPA 80, “Fire Doors and Other Opening Protectives,” or
b) specifically designed with a fire stop.change end
9.10.9.7. Combustible Drain, Waste and Vent Piping
(See A-3.1.9. in Appendix A.)
1) Intent StatementExcept as permitted in Sentences (2) to (6), combustible piping shall not be used in any part of a drain, waste and vent piping system where any part of that system partly or wholly penetrates a fire separation required to have a fire-resistance rating or penetrates a membrane that contributes to the required fire-resistance rating of an assembly.
2) Combustible drain, waste and vent piping not located in a vertical shaft is permitted to penetrate a fire separation required to have a fire-resistance rating or a membrane that forms part of an assembly required to have a fire-resistance rating provided the piping is sealed at the penetration by a change beginfire stopchange end that has an F rating not less than the fire-resistance rating required for the fire separation.

contentHistory

3) Intent StatementThe rating referred to in Sentence (2) shall be based on CAN/ULC-S115, “Fire Tests of Firestop Systems,” with a pressure differential of 50 Pa between the exposed and unexposed sides, with the higher pressure on the exposed side.
4) Intent StatementCombustible drain piping is permitted to penetrate a horizontal fire separation or a membrane that contributes to the required fire-resistance rating of a horizontal fire separation, provided it leads directly from a noncombustible watercloset through a concrete floor slab.
5) Intent StatementCombustible drain, waste and vent piping is permitted on one side of a vertical fire separation provided it is not located in a vertical shaft.
6) Intent StatementIn buildings containing 2 dwelling units only, combustible drain, waste and vent piping is permitted on one side of a horizontal fire separation.
9.10.9.8. Collapse of Combustible Construction
1) Intent StatementCombustible construction that abuts on or is supported by a noncombustible fire separation shall be constructed so that its collapse under fire conditions will not cause collapse of the fire separation.
9.10.9.9. Reduction in Thickness of Fire Separation by Beams and Joists
1) Intent StatementWhere pockets for the support of beams or joists are formed in a masonry or concrete fire separation, the remaining total thickness of solid masonry and/or grout and/or concrete shall be not less than the required equivalent thickness shown for Type S monolithic concrete in Table D-2.1.1. in Appendix D for the required fire-resistance rating.
9.10.9.10. Concealed Spaces above Fire Separations
1) Intent StatementExcept as provided in Sentence (2), a horizontal service space or other concealed space located above a required vertical fire separation shall be divided at the fire separation by an equivalent fire separation within the space.
2) Where a horizontal service space or other concealed space is located above a required vertical fire separation other than a vertical shaft, such space need not be divided as required in Sentence (1) provided the construction between such space and the space below is constructed as a fire separation having a fire-resistance rating not less than that required for the vertical fire separation, except that where the vertical fire separation is not required to have a fire-resistance rating greater than 45 min, the fire-resistance rating of the ceiling may be reduced to 30 min.

contentHistory

9.10.9.11. Separation of Residential Occupancies
1) Intent StatementExcept as provided in Sentence (2), residential occupancies shall be separated from all other major occupancies by a fire separation having a fire-resistance rating of not less than 1 h.
2) Intent StatementExcept as provided in Sentence (3), a major occupancy classified as a residential occupancy shall be separated from other major occupancies classified as mercantile or medium-hazard industrial occupancies by a fire separation having a fire-resistance rating of not less than 2 h.
3) Intent StatementWhere not more than 2 dwelling units are located in a building containing a mercantile occupancy, such mercantile occupancy shall be separated from the dwelling units by a fire separation having not less than 1 h fire-resistance rating.
9.10.9.12. Residential Suites in Industrial Buildings
1) Intent StatementNot more than one suite of residential occupancy shall be contained within a building classified as a Group F, Division 2 major occupancy.
9.10.9.13. Separation of Suites
1) Except as required in Article 9.10.9.14. and as permitted by Sentence (2) change beginand (3), a suitechange end shall be separated from adjoining suites by a fire separation having a fire-resistance rating of not less than 45 min.

contentHistory

2) Intent Statementchange beginIn sprinklered buildings, suites of business and personal services occupancy and mercantile occupancy that are served by public corridors conforming with Clause 3.3.1.4.(4)(b) are not required to be separated from each other by fire separations.
3) No fire separation is required between suites of business and personal services occupancy.change end
9.10.9.14. Separation of Residential Suites
1) Except as provided in Sentences (2), change beginand (3) and Article 9.10.21.2.change end, suites in residential occupancies shall be separated from adjacent rooms and suites by a fire separation having a fire-resistance rating of not less than 45 min.

contentHistory

2) Intent StatementSleeping rooms in boarding and lodging houses where sleeping accommodation is provided for not more than 8 boarders or lodgers need not be separated from the remainder of the floor area as required in Sentence (1) where the sleeping rooms form part of the proprietor's residence and do not contain cooking facilities.
3) Dwelling units that contain 2 or more storeys including basements shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h. (See A-3.3.4.4.(1) in Appendix A.)

contentHistory

4) change beginReserved.change end

contentHistory

9.10.9.15. Separation of Public Corridors
1) Except as provided in Sentences (2) and (3), public corridors shall be separated from the remainder of the building by a fire separation having not less than a 45 min fire-resistance rating.

contentHistory

2) In other than residential occupancies, no fire-resistance rating is required for fire separations between a public corridor and the remainder of the building if
b) the sprinkler system is electrically supervised in conformance with Sentence 3.2.4.10.(3), and
c) the operation of the sprinkler system will cause a signal to be transmitted to the fire department in conformance with Sentence 3.2.4.8.(4).

contentHistory

3) In other than residential occupancies, no fire separation is required between a public corridor and the remainder of the building if
b) the sprinkler system is electrically supervised in conformance with Sentence 3.2.4.10.(3),
c) the operation of the sprinkler system will cause a signal to be transmitted to the fire department in conformance with Sentence 3.2.4.8.(4), and
d) the corridor exceeds 5 m in width.

contentHistory

4) change beginReserved.change end

contentHistory

9.10.9.16. Separation of Storage Garages
1) Intent StatementExcept as provided in Sentences (2) and (3), a storage garage shall be separated from other occupancies by a fire separation having not less than a 1.5 h fire-resistance rating.
2) Intent StatementExcept as permitted in Sentence (3), storage garages containing 5 motor vehicles or fewer shall be separated from other occupancies by a fire separation of not less than 1 h.
3) Intent StatementWhere a storage garage serves only the dwelling unit to which it is attached or in which it is built, it shall be considered as part of that dwelling unit and the fire separation required in Sentence (2) need not be provided between the garage and the dwelling unit.
4) Intent StatementExcept as provided in Sentence (5), where a storage garage is attached to or built into a building of residential occupancy,
a) an air barrier system conforming to Subsection 9.25.3. shall be installed between the garage and the remainder of the building to provide an effective barrier to gas and exhaust fumes, and
b) every door between the garage and the remainder of the building shall conform to Article 9.10.13.15.
(See Appendix A.)
5) Intent StatementWhere membrane materials are used to provide the required airtightness in the air barrier system, all joints shall be sealed and structurally supported.
9.10.9.17. Separation of Repair Garages
1) Intent StatementExcept as provided in Sentences (2) and (3), a repair garage shall be separated from other occupancies by a fire separation having a fire-resistance rating of not less than 2 h.
2) Intent StatementAncillary spaces directly serving a repair garage, including waiting rooms, reception rooms, tool and parts storage areas and supervisory office space, need not be separated from the repair garage but shall be separated from other occupancies as required in Sentence (1).
3) Intent StatementThe fire separation referred to in Sentence (1) shall have a fire-resistance rating of not less than 1 h, where
a) the building is not more than one storey in building height,
b) the building is operated as a single suite, and
c) the only occupancy other than the repair garage is a mercantile occupancy.
4) Intent StatementExcept as provided in Sentence (5), where a building containing a repair garage also contains a dwelling unit, an air barrier system conforming to Subsection 9.25.3. shall be installed between the dwelling unit and the suite containing the garage to provide an effective barrier to gas and exhaust fumes. (See A-9.10.9.16.(4) in Appendix A.)
5) Intent StatementWhere membrane materials are used to provide the required airtightness in the air barrier system, all joints shall be sealed and structurally supported.
9.10.9.18. Exhaust Ducts Serving More Than One Fire Compartment
1) Intent StatementWhere a vertical service space contains an exhaust duct that serves more than one fire compartment, the duct shall have a fan located at or near the exhaust outlet to ensure that the duct is under negative pressure.
2) Intent StatementIndividual fire compartments referred to in Sentence (1) shall not have fans that exhaust directly into the duct in the vertical service space.
9.10.9.19. Central Vacuum Systems
1) Intent StatementA central vacuum system shall serve not more than one suite.
9.10.9.20. Multiple Tenant Self Storage Warehouses
1) Multiple tenant self storage warehouses shall comply with Article 3.3.5.9.

9.10.10. Service Rooms

9.10.10.1. Application
1) Intent StatementThis Subsection applies to service rooms in all buildings except rooms located within a dwelling unit.
9.10.10.2. Service Room Floors
1) Intent StatementThe fire-resistance rating requirements in this Subsection do not apply to the floor assembly immediately below a service room.
9.10.10.3. Separation of Service Rooms
1) Intent StatementExcept as provided in Sentence (2) and Articles 9.10.10.5. and 9.10.10.6., service rooms shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h when the floor area containing the service room is not sprinklered.
2) Intent StatementWhere a room contains a limited quantity of service equipment and the service equipment does not constitute a fire hazard, the requirements in Sentence (1) shall not apply.
9.10.10.4. change beginLocation of Fuel-Fired Applianceschange end
1) Intent StatementExcept as provided in Sentences (2) change beginand (3)change end and Article 9.10.10.5., fuel-fired appliances shall be located in a service room separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating.
2) Except as required in the appliance installation standards referenced in Sentences 6.2.1.4.(1), 9.33.5.2.(1) and 9.33.5.3.(1), fuel-fired space-heating appliances, space-cooling appliances, service water heaters change beginand laundry applianceschange end need not be separated from the remainder of the building as required in Sentence (1), change beginwhere the appliances serve
a) not more than one room or suite, or
b) a building with a building area of not more than 400 m2 and a building height of not more than 2 storeys.change end

contentHistory

3) Intent Statementchange beginSentence (1) does not apply to fireplaces and cooking appliances.change end
9.10.10.5. Incinerators
1) Intent StatementService rooms containing incinerators shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 2 h.
2) The design, construction, installation and alteration of each indoor incinerator shall conform to NFPA 82, “Incinerators and Waste and Linen Handling Systems and Equipment.”

contentHistory

3) Intent StatementEvery incinerator shall be connected to a chimney flue conforming to the requirements in Section 9.21. and serving no other appliance.
4) Intent StatementAn incinerator shall not be located in a room with other fuel-fired appliances.
9.10.10.6. Storage Rooms
1) Intent StatementRooms for the temporary storage of combustible refuse in all occupancies or for public storage in residential occupancies shall be separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating, except that a 45 min fire separation is permitted where the fire-resistance rating of the floor assembly is not required to exceed 45 min, or where such rooms are sprinklered.

9.10.11. Firewalls

9.10.11.1. Required Firewalls
1) Intent StatementExcept as provided in Article 9.10.11.2., a party wall on a property line shall be constructed as a firewall. change begin(See A-3.2.3.4.(1) in Appendix A.)change end
9.10.11.2. Firewalls Not Required
1) In a building of residential occupancy in which there is no dwelling unit above another dwelling unit, a party wall on a property line between dwelling units need not be constructed as a firewall provided it is constructed as a fire separation having not less than a 1 h fire-resistance rating.

contentHistory

2) change beginReserved.change end

contentHistory

3) Intent StatementThe wall described in Sentence (1) shall provide continuous protection from the top of the footings to the underside of the roof deck.
4) Intent StatementAny space between the top of the wall described in Sentence (1) and the roof deck shall be tightly filled with mineral wool or noncombustible material.
9.10.11.3. Construction of Firewalls
1) Intent StatementWhere firewalls are used, the requirements in Part 3 shall apply.

9.10.12. Prevention of Fire Spread at Exterior Walls and between Storeys

9.10.12.1. Termination of Floors or Mezzanines
1) Intent StatementExcept as provided in Sentence (2) and in Articles 9.10.1.3. and 9.10.9.5., the portions of a floor area or mezzanine that do not terminate at an exterior wall, a firewall or a vertical shaft, shall terminate at a vertical fire separation having a fire-resistance rating not less than that required for the floor assembly that terminates at the separation.
2) Intent StatementA mezzanine need not terminate at a vertical fire separation where the mezzanine is not required to be considered as a storey in Articles 9.10.4.1. and 9.10.4.2.
9.10.12.2. Location of Skylights
1) Intent StatementWhere a wall in a building is exposed to a fire hazard from an adjoining roof of a separate unsprinklered fire compartment in the same building, the roof shall contain no skylights within a horizontal distance of 5 m of the windows in the exposed wall.
9.10.12.3. Exterior Walls Meeting at an Angle
1) Intent StatementExcept as provided in Article 9.9.4.5., where exterior walls of a building meet at an external angle of 135° or less, the horizontal distance from change beginunprotected opening in one exterior wall to an unprotected opening in the other exterior wallchange end shall be not less than 1.2 m, where these openings are
a) in different fire compartments, or
b) change beginin different dwelling units.change end
2) Intent StatementThe exterior wall of each fire compartment referred to in Sentence (1) within the 1.2 m distance shall have a fire-resistance rating not less than that required for the interior vertical fire separation between the compartment and the remainder of the building.

contentHistory

9.10.12.4. Protection of Soffits
1) Intent StatementThis Article applies to the portion of any soffit enclosing a projection that is
a) less than 2.5 m vertically above a window or door, and
b) less than 1.2 m from either side of the window or door.
(See Appendix A.)
2) Except as provided in Sentences (4) and (5), the construction described in Sentence (1) shall have no unprotected openings and shall be protected in accordance with Sentence (3), where the soffit encloses
a) a common attic or roof space that spans more than 2 suites of residential occupancy and projects beyond the exterior wall of the building,
b) a floor space where an upper storey projects beyond the exterior wall of a lower storey and a fire separation is required at the floor between the two, or
c) a floor space where an upper storey projects beyond the exterior wall of a lower storey, and the projection is continuous across a vertical fire separation separating two suites.

contentHistory

3) Intent StatementProtection required by Sentence (2) shall be provided by
a) noncombustible material having a minimum thickness of 0.38 mm and a melting point not below 650°C,
b) not less than 12.7 mm thick gypsum soffit board or gypsum wallboard installed according to CSA A82.31-M, “Gypsum Board Application,”
c) not less than 11 mm thick plywood,
d) not less than 12.5 mm thick OSB or waferboard, or
e) not less than 11 mm thick lumber.
(See Appendix A.)
4) Intent StatementIn the case of a soffit described in Sentence (1) that is at the edge of an attic or roof space and completely separated from the remainder of that attic or roof space by change beginfire blockschange end, the requirements in Sentence (2) do not apply.
5) Intent StatementWhere all suites spanned by a common attic or roof space or situated above or below the projecting floor are sprinklered, the requirements of Sentence (2) do not apply, provided that all rooms, including closets and bathrooms, having openings in the wall beneath the soffit are sprinklered, notwithstanding any exceptions in the sprinkler standards referenced in Article 3.2.5.12.

9.10.13. Doors, Dampers and Other Closures in Fire Separations

9.10.13.1. Closures
1) Intent StatementExcept as provided in Article 9.10.13.2., openings in required fire separations shall be protected with a closure conforming to Table 9.10.13.1. and shall be installed in conformance with Chapters 2 to 14 of NFPA 80, “Fire Doors and Other Opening Protectives,” unless otherwise specified herein. (See also Article 9.10.3.1.)
Table 9.10.13.1.
Fire-Protection Ratings for Closures
Forming part of Sentence 9.10.13.1.(1)

Required Fire-Resistance Rating of Fire Separation

Minimum Fire-Protection Rating of Closure

30 or 45 min

20 min(1)

1 h

45 min(1)

1.5 h 1 h
2 h 1.5 h
3 h 2 h
4 h 3 h
Notes to Table 9.10.13.1.:

(1) See Article 9.10.13.2.
9.10.13.2. Solid Core Wood Door as a Closure
1) A 45 mm thick solid core wood door is permitted to be used where a minimum fire-protection rating of 20 min is permittedchange begin, between a secondary suite or lock-off unit and its primary dwelling unit,change end or between a public corridor and a suite provided that the door conforms to CAN/ULC-S113, “Wood Core Doors Meeting the Performance Required by CAN/ULC-S104 for Twenty Minute Fire Rated Closure Assemblies.” (See Appendix A.)

contentHistory

2) Intent StatementDoors described in Sentence (1) shall have not more than a 6 mm clearance beneath and not more than 3 mm at the sides and top.
9.10.13.3. Unrated Wood Door Frames
1) Intent StatementDoors required to provide a 20 min fire-protection rating or permitted to be 45 mm solid core wood shall be mounted in a wood frame of not less than 38 mm thickness where the frame has not been tested and rated.
9.10.13.4. Doors as a Means of Egress
1) Intent StatementDoors forming part of an exit or a public means of egress shall conform to Subsection 9.9.6. in addition to this Subsection.
9.10.13.5. Wired Glass as a Closure
1) Intent StatementWired glass conforming to Article 9.6.1.2. which has not been tested in accordance with Article 9.10.3.1. is permitted as a closure in a vertical fire separation required to have a fire-resistance rating of not more than 1 h provided such glass is not less than 6 mm thick and is mounted in conformance with Sentence (2).
2) Intent StatementWired glass described in Sentence (1) shall be mounted in fixed steel frames having a metal thickness of not less than 1.35 mm and a glazing stop of not less than 20 mm on each side of the glass.
3) Intent StatementIndividual panes of glass described in Sentence (1) shall not exceed 0.8 m2 in area or 1.4 m in height or width, and the area of glass not structurally supported by mullions shall not exceed 7.5 m2.
9.10.13.6. Steel Door Frames
1) Intent StatementSteel door frames forming part of a closure in a fire separation, including anchorage requirements, shall conform to CAN4-S105-M, “Fire Door Frames Meeting the Performance Required by CAN4-S104.”
9.10.13.7. Glass Block as a Closure
1) Intent StatementGlass block that has not been tested in accordance with Article 9.10.3.1. is permitted as a closure in a fire separation required to have a fire-resistance rating of not more than 1 h. (See Article 9.20.9.6.)
9.10.13.8. Maximum Size of Opening
1) The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 11 m2, with no dimension greater than 3.7 m, when the fire compartments on both sides of the fire separation are not sprinklered.

contentHistory

2) Intent StatementThe size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 22 m2, with no dimension greater than 6 m, when the fire compartments on both sides of the fire separation are sprinklered.
9.10.13.9. Door Latch
1) Intent StatementEvery swing type door in a fire separation shall be equipped with a latch.
9.10.13.10. Self-closing Device
1) Intent StatementExcept as described in Sentence (2), every door in a fire separation shall have a self-closing device.
2) Intent StatementSelf-closing doors are not required between public corridors and suites in business and personal services occupancies, except in dead-end corridors.
9.10.13.11. Hold-Open Devices
1) Intent StatementWhere hold-open devices are used on doors in required fire separations, they shall be installed in accordance with Article 3.1.8.12.
9.10.13.12. Service Room Doors
1) Intent StatementSwing-type doors shall open into service rooms containing fuel-fired equipment where such doors lead to public corridors or rooms used for assembly but shall swing outward from such rooms in all other cases.
9.10.13.13. Fire Dampers
1) Intent StatementExcept as permitted by Sentences (2) to (5) and Sentence 9.10.5.1.(4), a duct that penetrates an assembly required to be a fire separation with a fire-resistance rating shall be equipped with a fire damper in conformance with Articles 3.1.8.4. and 3.1.8.9.
2) Intent StatementA fire damper is not required where a noncombustible branch duct pierces a required fire separation provided the duct
a) has a melting point not below 760°C,
b) has a cross-sectional area less than 130 cm2, and
c) supplies only air-conditioning units or combined air-conditioning and heating units discharging air at not more than 1.2 m above the floor.
3) Intent StatementA fire damper is not required where a noncombustible branch duct pierces a required fire separation around an exhaust duct riser in which the airflow is upward provided
a) the melting point of the branch duct is not below 760°C,
b) the branch duct is carried up inside the riser not less than 500 mm, and
c) the exhaust duct is under negative pressure as described in Article 9.10.9.18.
4) Intent StatementNoncombustible ducts that penetrate a fire separation separating a vertical service space from the remainder of the building need not be equipped with a fire damper at the fire separation provided
a) the ducts have a melting point above 760°C, and
b) each individual duct exhausts directly to the outside at the top of the vertical service space.
5) Intent StatementA duct serving commercial cooking equipment and piercing a required fire separation need not be equipped with a fire damper at the fire separation. (See also Article 6.2.2.7.)
9.10.13.14. Fire Stop Flaps
1) Intent StatementFire stop flaps in ceiling membranes required in Sentence 9.10.5.1.(4) shall be constructed in conformance with Appendix D, Fire-Performance Ratings.
9.10.13.15. Doors between Garages and Dwelling Units
1) Intent StatementA door between an attached or built-in garage and a dwelling unit shall be tight fitting and weather-stripped to provide an effective barrier against the passage of gas and exhaust fumes and shall be fitted with a self-closing device.
2) Intent StatementA doorway between an attached or built-in garage and a dwelling unit shall not be located in a room intended for sleeping.
9.10.13.16. Door Stops
1) Intent StatementWhere a door is installed so that it may damage the integrity of a fire separation if its swing is unrestricted, door stops shall be installed to prevent such damage.

9.10.14. Spatial Separation Between Buildings

9.10.14.1. Application
1) Intent StatementThis Subsection applies to buildings other than those to which Subsection 9.10.15. applies.
9.10.14.2. Area and Location of Exposing Building Face
1) Intent StatementThe area of an exposing building face shall be
a) taken as the exterior wall area facing in one direction on any side of a building, and
b) calculated as
i) the total area measured from the finished ground level to the uppermost ceiling, or
ii) the area for each fire compartment, where a building is divided into fire compartments by fire separations with fire-resistance ratings not less than 45 min.
2) Intent StatementFor the purpose of using Table 9.10.14.4.A to determine the maximum aggregate area of unprotected openings in an irregularly shaped or skewed exterior wall, the location of the exposing building face shall be taken as a vertical plane located so that there are no unprotected openings between the vertical plane and the line to which the limiting distance is measured. (See A-3.2.3.1.(4) in Appendix A.)
3) For the purpose of using Table 9.10.14.5.A to determine the required type of construction, cladding and fire-resistance rating for an irregularly shaped or skewed exterior wall,
a) the location of the exposing building face shall be taken as a vertical plane located so that no portion of the actual exposing building face is between the vertical plane and the line to which the limiting distance is measured, and
b) the value for the maximum area of unprotected openings (see second column of Table 9.10.14.5.A) shall be determined using the limiting distance measured from the location described in Clause (a). (See A-3.2.3.1.(4) in Appendix A.)

contentHistory

9.10.14.3. Limiting Distance and Fire Department Response
1) Except change beginas provided in Sentence (2) and exceptchange end for the purpose of applying Sentences 9.10.14.4.(2)change begin, (3), (8) and (9), and Sentences 9.10.14.5.(3), (8) and (12)change end, a limiting distance equal to half the actual limiting distance shall be used as input to the requirements of this Subsection, where
a) change beginthe time from receipt of notification of a fire by the fire department until the first fire department vehicle arrives at the building exceeds 10 min in 10 change beginper centchange end or more of all calls to the building,change end and
b) change beginany storey inchange end the building is not sprinklered.
change begin(See A-3.2.3. and A-3.2.3.1.(8) in Appendix A.)change end

contentHistory

2) change beginExcept for the purpose of applying Sentences 9.10.14.4.(2), 9.10.14.4.(3), 9.10.14.4.(8) and 9.10.14.4.(9) and Sentences 9.10.14.5.(3), 9.10.14.5.(8) and 9.10.14.5.(12), a limiting distance equal to half the actual limiting distance shall be used as input to the requirements of this Subsection, where
a) a building for which a building permit was applied for before December 20, 2014 is or is proposed to be located in a subdivision for which a subdivision plan was registered in a land title office before December 20, 2013,
b) change beginDeleted, andchange end
c) the building is not sprinklered.change end

contentHistory

9.10.14.4. Openings in Exposing Building Face
1) Intent StatementExcept as provided in Sentences (6) to (10), the maximum aggregate area of unprotected openings in an exposing building face shall
a) conform to Table 9.10.14.4.A,
b) conform to Subsection 3.2.3., or
Table 9.10.14.4.A
Maximum Aggregate Area of Unprotected Openings in Exterior Walls(1)
Forming part of Sentence 9.10.14.4.(1)

Occupancy Classification of Building

Maximum Total Area of Exposing Building Face, m2

Maximum Aggregate Area of Unprotected Openings,
% of Exposing Building Face Area

Limiting Distance, m

Less than 1.2 1.2 1.5 2.0 4.0 6.0 8.0 10.0 12.0 16.0 20.0 25.0

Residential, business and personal services, and low-hazard industrial

30 0 7 9 12 39 88 100
40 0 7 8 11 32 69 100
50 0 7 8 10 28 57 100
100 0 7 8 9 18 34 56 84 100
Over 100 0 7 7 8 12 19 28 40 55 92 100

Mercantile and medium-hazard industrial

30 0 4 4 6 20 44 80 100
40 0 4 4 6 16 34 61 97 100
50 0 4 4 5 14 29 50 79 100
100 0 4 4 4 9 17 28 42 60 100
Over 100 0 4 4 4 6 10 14 20 27 46 70 100
Notes to Table 9.10.14.4.A:

(1) See also Sentences (6) and (7) to calculate the maximum permitted area of unprotected openings in sprinklered buildings or where wired glass or glass blocks are used.
2) Intent StatementOpenings in a wall having a limiting distance of less than 1.2 m shall be protected by closures, of other than wired glass or glass block, whose fire-protection rating is in conformance with the fire-resistance rating required for the wall. (See Table 9.10.13.1.)
3) Intent Statementchange beginExcept for buildings that are sprinklered and for openable windows having an unobstructed opening equal to 0.35 m2 installed in accordance with Sentences 9.9.10.1.(1) and (2), where the limiting distance is 2 m or less, individual unprotected openings shall be no greater than
a) the area stated in Table 9.10.14.4.B, or
b) where the limiting distance is equal to or greater than 1.2 m, the area calculated by
where
Area= area of the unprotected opening, and
Table 9.10.14.4.B
Maximum Concentrated Area of Unprotected Openings
Forming part of Sentence 9.10.14.4.(3)
Limiting Distance, m Maximum Area of Individual Unprotected Openings, m2
1.2 0.35
1.5 0.78
2.0 1.88
4) Intent StatementThe spacing between individual unprotected openings described in Sentence (3) that serve a single room or space described in Sentence (5) shall be not less than
a) 2 m horizontally of another unprotected opening that is on the same exposing building face and serves the single room or space, or
b) 2 m vertically of another unprotected opening that serves the single room or space, or another room or space on the same storey.
5) Intent StatementFor the purpose of Sentence (4), “single room or space” shall mean
a) two or more adjacent spaces having a full-height separating wall extending less than 1.5 m from the interior face of the exterior wall, or
b) two or more stacked spaces that are on the same storey.change end
6) change beginIf a building is not sprinklered,change end the maximum aggregate area of unprotected openings shall be not more than twice the area determined according to Sentence (1), where the unprotected openings are glazed with
a) wired glass in steel frames, as described in Article 9.10.13.5., or
b) glass blocks, as described in Article 9.10.13.7.

contentHistory

7) Intent StatementWhere the building is sprinklered, the maximum aggregate area of unprotected openings shall be not more than twice the area determined according to Sentence (1), provided all rooms, including closets and bathrooms, that are adjacent to the exposing building face and that have unprotected openings are sprinklered, notwithstanding any exemptions in the sprinkler standards referenced in Article 3.2.5.12.
8) change beginIf a storage garage has a limiting distance of no less than 3 m, the exposing building face of such storage garage may have unlimited unprotected openings.change end

contentHistory

9) Intent StatementThe maximum aggregate area of unprotected openings in an exposing building face of a storey that faces a street and is at the same level as the street need not comply with Sentence (1), where the limiting distance is not less than 9 m.
10) Intent StatementExcept as provided in Sentence (11), for garages or accessory buildings that serve a single dwelling unit only and are detached from any building, the maximum aggregate area of glazed openings shall comply with the requirements for unprotected openings.
11) Intent StatementThe limits on the area of glazed openings stated in Sentence (10) need not apply to the exposing building face of a detached garage or accessory building facing a dwelling unit, where
a) the detached garage or accessory building serves only one dwelling unit,
b) the detached garage or accessory building is located on the same property as that dwelling unit, and
c) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.
12) change beginWhere a building of residential occupancy is sprinklered and the limiting distance is less than 1.2 m but no less than 1 m, the maximum percentage of unprotected openings may be 10 per cent provided
a) the windows are glazed with tempered, wired or laminated glass, or glass block, and
b) the exposing building face is constructed according to Article 9.10.14.5.change end
9.10.14.5. Construction of Exposing Building Face and Walls above Exposing Building Face
1) Except as permitted in Sentences (3) to (14), each exposing building face and any exterior wall located above an exposing building face that encloses an attic or roof space shall be constructed in conformance with Table 9.10.14.5.A. change begin(See Appendix A.)change end (See also Subsection 9.10.8.)

contentHistory

Table 9.10.14.5.A
Minimum Construction Requirements for Exposing Building Faces
Forming part of Sentence 9.10.14.5.(1)

Occupancy
Classification of Building change beginor Fire Compartmentchange end

Maximum Area of Unprotected Openings Permitted, % of Exposing Building Face Area

Minimum Required Fire-Resistance Rating

Type of Construction Required Type of Cladding Required

Residential, business and personal services, and low-hazard industrial

0 to 10

1 h

Noncombustible

Noncombustible

change begin> 10change end to 25

1 h

Combustible or noncombustible

Noncombustible

change begin> 25 to 50change end change begin45 minchange end change beginCombustible or noncombustiblechange end change beginNoncombustiblechange end
change begin> 50 to < 100change end

45 min

Combustible or noncombustible

Combustible or noncombustible

Mercantile and medium-hazard industrial

0 to 10

2 h

Noncombustible

Noncombustible

change begin> 10change end to 25

2 h

Combustible or noncombustible

Noncombustible

change begin> 25 to 50change end change begin1 hchange end change beginCombustible or noncombustiblechange end change beginNoncombustiblechange end
change begin> 50 to < 100change end

1 h

Combustible or noncombustible

Combustible or noncombustible

2) change beginExcept as provided in Sentences (3) to (8), cladding on exposing building faces and exterior walls located above exposing building faces that enclose an attic or roof space, for buildings or fire compartments where the maximum permitted area of unprotected openings is more than 10 change beginper centchange end of the exposing building face, need not be noncombustible where the wall assembly complies with the requirements of Sentences 3.1.5.5.(3) and (4) when tested in conformance with CAN/ULC-S134, “Fire Test of Exterior Wall Assemblies.”change end

contentHistory

3) change beginExcept as provided in Sentences (4) to (8) and permitted by Sentence (9),change end cladding on exposing building faces and on exterior walls located above exposing building faces change beginof buildings or fire compartments where the maximum permitted area of unprotected openings is more than 25 change beginper centchange end but not more than 50 change beginper centchange end of the exposing building face need not be noncombustiblechange end, where
a) change beginthe limiting distance is greater than 5.0 m,change end
b) the limiting distance is change begingreater than 2.5 m where the area and width-to-height ratio of the exposing building face conform to Table 9.10.14.5.B,change end
d) change beginthe claddingchange end
ii) change beginis installed without furring members, or on furring not more than 25 mm thick, over gypsum sheathing at least 12.7 mm thick or over masonry, andchange end
iii) change beginafter conditioning in conformance with ASTM D 2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing,” has a flame-spread rating not greater than 25 when tested in accordance with Sentence 3.1.12.1.(2), orchange end
e) the cladding
i) conforms to Subsection 9.27.12.,
ii) is installed change beginwith orchange end without furring members over a change begingypsum sheathingchange end at least 12.7 mm thick or over masonry,
iii) has a flame-spread rating not greater than 25 when tested in accordance with Sentence 3.1.12.1.(2), and
iv) does not exceed 2 mm in thickness exclusive of fasteners, joints and local reinforcements.

contentHistory

Table 9.10.14.5.B
change beginMaximum Allowable Area and Ratio of Width to Height of Exposing Building Face
Forming part of Sentence 9.10.14.5.(3)
Maximum Ratio of Width to Height of Exposing Building Face Maximum Area of Exposing Building Face, m2
1:1 88
2:1 102
3:1 129
4:1 161
5:1 195change end
4) Except as provided in Sentence (5), change beginif a detached garage or accessory building serves one dwelling unit; or if a detached garage serves both units in a two-family dwelling and has a continuous internal fire separation, with a 45 minute fire resistance rating from the floor slab to the roof sheathing separating the parking spaces for each unit,change end the exposing building face:
a) need not conform to the minimum required fire-resistance rating stated in Table 9.10.14.5.A, where the limiting distance is 0.6 m or more,
b) shall have a fire-resistance rating of not less than 45 min, where the limiting distance is less than 0.6 m, and
c) need not conform to the type of cladding required by Table 9.10.14.5.A, regardless of the limiting distance.

contentHistory

5) The requirements regarding fire-resistance rating, type of construction and type of cladding need not apply to the exposing building face of a detached garage change beginconforming to Sentence 9.10.14.5.(4)change end or accessory building facing a change beginone-family dwelling or two-family dwellingchange end, where
a) the detached garage or accessory building serves only change beginone-family dwelling or two-family dwellingchange end,
b) the detached garage or accessory building is located on the same property as that change beginone-family dwelling or two-family dwellingchange end, and
c) the change beginone-family dwelling or two-family dwellingchange end served by the detached garage or accessory building is the only major occupancy on the property.

contentHistory

6) Intent StatementExcept change beginas provided in Sentence (7),change end combustible projections on the exterior of a wall that are more than 1 m above ground level and that could expose an adjacent building to fire spread shall not be permitted within
a) 1.2 m of a property line or the centre line of a public way, or
b) 2.4 m of a combustible projection on another building on the same property.
7) change beginExcept as provided in Sentences (9) to (11), Sentence (6) shall not apply to
b) detached garages or accessory buildings, where
i) the detached garage change beginconforming to Sentence 9.10.14.5.(4)change end or accessory building serves only change beginone-family dwelling or two-family dwelling,change end
ii) the detached garage change beginconforming to Sentence 9.10.14.5.(4)change end or accessory building is located on the same property as that change beginone-family dwelling or two-family dwelling,change end and
iii) the change beginone-family dwelling or two-family dwellingchange end served by the detached garage change beginconforming to Sentence 9.10.14.5.(4)change end or accessory building is the only major occupancy on the property.
(See Appendix A.)

contentHistory

8) Where combustible projections on an exposing building face are permitted by Sentence (7), are totally enclosed and constructed with solid faces, such as for fireplaces and chimneys, and extend within 1.2 m of a property line,
a) the construction of the face and sides of the projection shall comply with the corresponding requirements for exposing building faces for limiting distances less than 1.2 m as stated in Sentence (2) or (3), and
b) where the underside of the projection is more than 0.6 m above finished ground level, it shall be protected by
i) not less than 0.38 mm thick noncombustible material,
iii) not less than 12.7 mm thick gypsum soffit board or gypsum ceiling board installed according to CSA A82.31-M, “Gypsum Board Application,”
iv) not less than 11 mm thick plywood,
v) not less than 12.5 mm thick OSB or waferboard, or
vi) not less than 11 mm thick lumber.
(See Appendix A.)

contentHistory

9) Intent StatementWhere the exposing building face has a limiting distance of not more than 0.45 m, projecting roof soffits shall not be constructed above the exposing building face. (See A-3.2.3.6.(2) in Appendix A.)
10) Intent StatementWhere the exposing building face has a limiting distance of more than 0.45 m, the face of roof soffits above the exposing building face shall not project to less than 0.45 m from the property line. (See A-3.2.3.6.(2) in Appendix A.)
11) Intent StatementWhere roof soffits project to less than 1.2 m from the property line, the centre line of a lane or public thoroughfare, or an imaginary line between 2 buildings or fire compartments on the same property, they shall
a) have no openings, and
b) be protected by
i) not less than 0.38 mm thick sheet steel,
iii) not less than 12.7 mm thick gypsum soffit board or gypsum ceiling board installed according to CSA A82.31-M, “Gypsum Board Application,”
iv) not less than 11 mm thick plywood,
v) not less than 12.5 mm thick OSB or waferboard, or
vi) not less than 11 mm thick lumber.
(See A-3.2.3.6.(2) in Appendix A.)change end
12) Intent StatementHeavy timber and steel columns need not conform to the requirements of Sentence (1), provided the limiting distance is not less than 3 m.
13) Intent StatementNon-loadbearing wall components need not have a minimum fire-resistance rating, where the building
a) is 1 storey in building height,
c) is classified as a low-hazard industrial occupancy and used only for low fire load occupancies, such as power-generating plants or plants for the manufacture or storage of noncombustible materials, and
d) has a limiting distance of 3 m or more.
14) change beginWhere a residential building is sprinklered, and Table 9.10.14.5.A requires noncombustible construction, the exposing building faces may use a wood stud wall assembly having a 1 hour fire-resistance rating provided the limiting distance is at least 1.0 m and the wall assembly is of noncombustible construction throughout excepting structural elements and sheathing.change end

contentHistory

9.10.15. Spatial Separation Between change beginResidential Buildings

(see Appendix A)change end

contentHistory

9.10.15.1. Application
1) change beginThis Subsection applies to
a) buildings containing only dwelling units with no dwelling unit above another dwelling unit except as described in Clause (b) or (c),
c) two-family dwellings having no dwelling unit above another dwelling unit except secondary suite within the principal dwelling unit,
e) accessory buildings that serve a building described in Clause (a).change end

contentHistory

9.10.15.2. Area and Location of Exposing Building Face
1) The area of an exposing building face shall be
a) taken as the exterior wall area facing in one direction on any side of a building, and
b) calculated as
i) the total area measured from the finished ground level to the uppermost ceiling,
ii) the area for each fire compartment, where a building is divided into fire compartments by fire separations with fire-resistance ratings not less than 45 min, or
iii) change beginexcept as provided in Sentence (2),change end where Table 9.10.15.4. is used to determine the maximum aggregate area of change beginunprotected openingschange end, the area of any number of individual vertical portions of the wall measured from the finished ground level to the uppermost ceiling. (See A-9.10.15.4.(2) in Appendix A.)

contentHistory

2) Intent Statementchange beginWhere the exposing building face of any section of an exterior wall enclosing a single room or space, or combination room and space, has a limiting distance of 2 m or less, that section of the exposing building face serving the room or space shall not be divided into portions for the purpose of calculating area of exposing building face. (See Sentence 9.10.15.4.(5) and A-9.10.15.4.(2) in Appendix A.)change end
3) For the purpose of using Table 9.10.15.4. to determine the maximum permitted area of change beginunprotected openingschange end in an irregularly shaped or skewed exterior wall, the location of the exposing building face shall be taken as a vertical plane located so that there are no change beginunprotected openingschange end between the vertical plane and the line to which the limiting distance is measured. (See A-3.2.3.1.(4) in Appendix A.)

contentHistory

4) Intent Statementchange beginIn determining the required cladding-sheathing assemblychange end and fire-resistance rating for an irregularly shaped or skewed exterior wall, the location of the exposing building face shall be taken as a vertical plane located so that no portion of the actual exposing building face is between the vertical plane and the line to which the limiting distance is measured. (See change beginArticle 9.10.15.5.change end and A-3.2.3.1.(4) in Appendix A.)
9.10.15.3. Limiting Distance change beginand Fire Department Responsechange end
1) Except change beginas provided in Sentence 9.10.15.3.(2) and exceptchange end for the purpose of applying change beginSentences 9.10.15.2.(2), 9.10.15.4.(3) and 9.10.15.5.(12),change end a limiting distance equal to half the actual limiting distance shall be used as input to the requirements of this Subsection, where
a) change beginthe time from receipt of notification of a fire by the fire department until the first fire department vehicle arrives at the building exceeds 10 min in 10 change beginper centchange end or more of all calls to the building,change end and
b) change beginany storey inchange end the building is not sprinklered.
change begin(See A-3.2.3. and A-3.2.3.1.(8) in Appendix A.)change end

contentHistory

2) change beginchange beginDeleted.change endchange end

contentHistory

9.10.15.4. change beginUnprotectedchange end Openings in Exposing Building Face

contentHistory

1) Except as provided in change beginSentences (6), (7) and (8)change end, the maximum aggregate area of change beginunprotected openingschange end in an exposing building face shall
a) conform to Table 9.10.15.4.,
b) change beginin a building which conforms to Sentence (8), comply withchange end Subsection 3.2.3., or
c) change beginwhere the limiting distance is not less than 1.2 m,change end be equal to or less than the limiting distance squared.

contentHistory

2) Where the limits on the area of change beginunprotected openingschange end are determined for individual portions of the exterior wall, as described in Subclause 9.10.15.2. (1)(b)(iii), the maximum aggregate area of change beginunprotected openingschange end for any portion shall conform to the values in the row of Table 9.10.15.4. corresponding to the maximum total area of exposing building face (see column 1 of the Table) that is equal to the sum of all portions of the exposing building face. (See Appendix A.)

contentHistory

3) change beginExcept for buildings that are sprinklered and for openable windows having an unobstructed opening equal to 0.35 m2 installed in accordance with Sentences 9.9.10.1.(1) and (2), where the limiting distance is 2 m or less, individual change beginunprotected openingschange end or a group of change beginunprotected openingschange end in an exposing building face shall not exceed 50 change beginper centchange end of the maximum allowable aggregate area of change beginunprotected openingschange end determined in Sentence (1).

contentHistory

4) The spacing between individual change beginunprotected openingschange end described in Sentence (3) serving a single room or space described in Sentence (5) shall be not less than
a) 2 m horizontally of another change beginunprotected openingchange end that is on the same exposing building face and serves the single room or space, or
b) 2 m vertically of another change beginunprotected openingchange end that serves the single room or space, or another room or space on the same storey.

contentHistory

5) Intent StatementFor the purpose of Sentence (4), “single room or space” shall mean
a) two or more adjacent spaces having a full-height separating wall extending less than 1.5 m from the interior face of the exterior wall, or
b) two or more stacked spaces that are on the same storey.change end
6) The limits on the area of change beginunprotected openingschange end shall not apply to the exposing building face of change beginone-family dwelling or two-family dwellingchange end facing a detached garage or accessory building, where
a) the detached garage change beginconforming to Sentence 9.10.15.5.(4)change end or accessory building serves only change beginone-family dwelling or two-family dwellingchange end,
b) the detached garage change beginconforming to Sentence 9.10.14.5.(4)change end or accessory building is located on the same property as that change beginone-family dwelling or two-family dwellingchange end, and
c) the change beginone-family dwelling or two-family dwellingchange end served by the detached garage change beginconforming to Sentence 9.10.15.5.(4)change begin or accessory building is the only major occupancy on the property.

contentHistory

7) change beginIf a building is sprinklered and the limiting distance is less than 1.2 m but not less than 1 m, the maximum percentage of unprotected openings shall be 10 per cent provided
a) the windows are glazed with tempered , wired, or laminated glass or glass block, and
b) the exposing building face is constructed according to Sentence 9.10.15.5.(13).
8) If a building is sprinklered, the maximum aggregate area of unprotected openings may be no more than twice the area as determined in Table 9.10.15.4. provided all rooms, including closets and bathrooms, that are adjacent to the exposing building face and that have unprotected openings shall be sprinklered, notwithstanding any exemptions in the sprinkler standards referenced in Article 3.2.5.12.
9) If a storage garage has a limiting distance of no less than 3 m, the exposing building face of such storage garage may have unlimited unprotected openings.change end
Table 9.10.15.4.
Maximum Area of change beginUnprotectedchange end Openings in Exterior Walls change beginof Houseschange end
Forming part of Sentences 9.10.15.4.(1) and (2)

Maximum Total Area of Exposing Building Face, m2

Maximum Aggregate Area of change beginUnprotectedchange end Openings, % of Exposing Building Face Area

Limiting Distance, m

Less than 1.2 1.2 1.5 2.0 4.0 6.0 8.0 10.0 12.0 16.0 20.0 25.0
30 0 7 9 12 39 88 100
40 0 7 8 11 32 69 100
50 0 7 8 10 28 57 100
100 0 7 8 9 18 34 56 84 100
Over 100 0 7 7 8 12 19 28 40 55 92 100

contentHistory

9.10.15.5. Construction of Exposing Building Face of Houses
1) Except as provided in change beginSentences (4), (12) and (13),change end each exposing building face and any exterior wall located above an exposing building face that encloses an attic or roof space shall be constructed in conformance with change beginSentences (2) and (3)change end
a) for the exposing building face as a whole, or
b) for any number of separate portions of the exposing building face (see Subclause (b)(iii), Sentence 9.10.15.4.(2), and A-9.10.15.4.(2) in Appendix A).
change begin(See also Subsection 9.10.8.)change end

contentHistory

2) change beginExcept as provided in Sentences (4) and (5),change end where the limiting distance is less than 0.6 m, the exposing building face and exterior walls located above the exposing building face that enclose an attic or roof space change beginshall have a fire-resistance rating of not less than 45 min, andchange end
a) change beginthe cladding shall be metal or noncombustible cladding installed in accordance with Section 9.20., 9.27. or 9.28. (see A-9.10.14.5.(1) in Appendix A),change end
b) change beginthe cladding shallchange end
i) conform to change beginSubsection 9.27.12.change end,
ii) be installed without furring members over gypsum sheathing at least 12.7 mm thick or over masonry,
iii) have a flame-spread rating not greater than 25 when tested in accordance with Sentence 3.1.12.1.(2), and
iv) not exceed 2 mm in thickness exclusive of fasteners, joints and local reinforcements, or
c) change beginthe wall assembly shall comply with Sentences 3.1.5.5.(3) and (4) when tested in conformance with CAN/ULC-S134, “Fire Test of Exterior Wall Assemblies.”change end

contentHistory

3) change beginExcept as provided in Sentence (4), where the limiting distance is equal to or greater than 0.6 m and less than 1.2 m, the exposing building face and any exterior wall located above the exposing building face that encloses an attic or roof space shall have a fire-resistance rating of not less than 45 min, and
a) the cladding shall be metal or noncombustible cladding installed in accordance with Section 9.20., change begin9.27.change end or 9.28. (See A-9.10.14.5.(1) in Appendix A),
b) the cladding shall
ii) be installed without furring members, or on furring not more than 25 mm thick, over gypsum sheathing at least 12.7 mm thick or over masonry, and
iii) after conditioning in conformance with ASTM D 2898, “Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing,” have a flame-spread rating not greater than 25 when tested in accordance with Sentence 3.1.12.1.(2),
c) the cladding shall
i) conform to Subsection 9.27.12.,
ii) be installed with or without furring members over gypsum sheathing at least 12.7 mm thick or over masonry,
iii) have a flame-spread rating not greater than 25 when tested in accordance with Sentence 3.1.12.1.(2), and
iv) not exceed 2 mm in thickness exclusive of fasteners, joints and local reinforcements, or
d) the wall assembly shall comply with Sentences 3.1.5.5.(3) and (4) when tested in conformance with CAN/ULC-S134, “Fire Test of Exterior Wall Assemblies.”change end

contentHistory

4) Intent StatementThe requirements regarding fire-resistance rating and type of claddingchange begin-sheathing assemblychange end shall not apply to the exposing building face change beginor projections from an exposing building facechange end of a dwelling unit facing a detached garage or accessory buildingchange begin, or a garage or accessory building facing a dwelling unit,change end where
a) the detached garage or accessory building serves only one dwelling unit,
b) the detached garage or accessory building is located on the same property as that dwelling unit, and
c) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.
5) Intent StatementExcept as provided in change beginSentence (6)change end, combustible projections on the exterior of a wall that are more than 1 m above ground level and that could expose an adjacent building to fire spread shall not be permitted within
a) 1.2 m of a property line or the centre line of a public way, or
b) 2.4 m of a combustible projection on another building on the same property.
6) Intent Statementchange beginExcept as provided in Sentences (8) to (10), Sentence (5) shall not apply to
a) buildings containing 1 or 2 dwelling units only, and
b) detached garages or accessory buildings, where
i) the detached garage or accessory building serves only one dwelling unit,
ii) the detached garage or accessory building is located on the same property as that dwelling unit, and
iii) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.
(See A-9.10.14.5.(7) in Appendix A.)
7) Where combustible projections on an exposing building face are permitted by Sentence (6), are totally enclosed and constructed with solid faces, such as for fireplaces and chimneys, and extend within 1.2 m of a property line,
a) the construction of the face and sides of the projection shall comply with the corresponding requirements for exposing building faces for limiting distances less than 1.2 m as stated in Sentence (2) or (3), and
b) where the underside of the projection is more than 0.6 m above finished ground level, it shall be protected by
i) not less than 0.38 mm thick noncombustible material,
iii) not less than 12.7 mm thick gypsum soffit board or gypsum ceiling board installed according to CSA A82.31-M, “Gypsum Board Application,”
iv) not less than 11 mm thick plywood,
v) not less than 12.5 mm thick OSB or waferboard, or
vi) not less than 11 mm thick lumber.
(See A-9.10.14.5.(8) in Appendix A.)

contentHistory

8) Intent StatementWhere the exposing building face has a limiting distance of not more than 0.45 m, projecting roof soffits shall not be constructed above the exposing building face. (See A-3.2.3.6.(2) in Appendix A.)
9) Intent StatementWhere the exposing building face has a limiting distance of more than 0.45 m, the face of roof soffits above the exposing building face shall not project to less than 0.45 m from the property line. (See A-3.2.3.6.(2) in Appendix A.)
10) change beginRoof soffits located within 1.2 m of a property line or the centre line of a public way, or located within 1.2 m of an imaginary line between two buildings or two fire compartments on the same property, shallchange end
a) have no openings, and
b) be protected by
i) no less than 0.38 mm thick sheet steel,
iii) no less than 12.7 mm thick gypsum soffit board or gypsum ceiling board installed according to CSA A82.31-M, “Gypsum Board Application,”
iv) no less than 11 mm thick plywood,
v) no less than 12.5 mm thick OSB or waferboard, or
vi) no less than 11 mm thick lumber.
(See A-3.2.3.6.(2) in Appendix A.)

contentHistory

11) For buildings of combustible construction, materials installed to provide the required protection for soffits may be covered with a combustible or noncombustible finish material.change end

contentHistory

12) Intent StatementHeavy timber and steel columns need not conform to the requirements of Sentence (1), provided the limiting distance is not less than 3 m.
13) change beginIf a building is sprinklered, and the maximum percentage of unprotected openings complies with Sentence 9.10.15.4.(7), the exposing building faces may be constructed with a wood stud wall assembly provided
b) the wall assembly is of non-combustible construction throughout excepting structural elements and sheathing, and
c) the wall assembly is clad with non-combustible cladding.change end

contentHistory

9.10.16. Fire change beginBlockschange end

9.10.16.1. Required Fire change beginBlockschange end in Concealed Spaces
1) Intent StatementVertical concealed spaces in interior walls and exterior walls shall be separated by change beginfire blockschange end
a) one from the other, and
b) from horizontal concealed spaces.
2) Intent StatementHorizontal concealed spaces in attics, roof spaces, ceilings, floors, and crawl spaces shall be separated by change beginfire blockschange end
a) one from the other, and
b) from vertical concealed spaces.
3) change beginFire blockschange end shall be provided at all interconnections between concealed vertical and horizontal spaces in interior coved ceilings, drop ceilings and soffits where the exposed construction materials within the concealed spaces have a surface flame-spread rating greater than 25.

contentHistory

4) change beginFire blockschange end shall be provided at the top and bottom of each run of stairs where they pass through a floor containing concealed space in which the exposed construction materials within the space have a surface flame-spread rating greater than 25.

contentHistory

5) In unsprinklered buildings of combustible construction, every concealed space created by a ceiling, roof space or unoccupied attic space shall be separated by change beginfire blockschange end into compartments
a) not more than 60 m in greatest dimension, and
b) where such space contains exposed construction materials having a surface flame-spread rating greater than 25, not more than 300 m2 in area.

contentHistory

6) Intent Statement No dimension of the concealed space  described in Clause (5)(b) shall exceed 20 m.
7) Concealed spaces in mansard or gambrel style roofs, exterior cornices, balconies and canopies of combustible construction in which the exposed construction materials within the space have a surface flame-spread rating exceeding 25 shall have vertical change beginfire blockschange end at intervals of not more than 20 m and at points where such concealed spaces extend across the ends of required vertical fire separations.

contentHistory

9.10.16.2. Required Fire change beginBlockschange end in Wall Assemblies
1) Intent StatementExcept as permitted in Sentence (2), change beginfire blockschange end shall be provided to block off concealed spaces within wall assemblies, including spaces created by furring,
a) at each floor level,
b) at each ceiling level where the ceiling contributes to part of the required fire-resistance rating, and
c) at other locations within the wall, so that the distance between fire blocks does not exceed 20 m horizontally and 3 m vertically.
2) Fire blocks described in Sentence (1) are not required, provided
a) change beginthe insulated wall assembly contains not more than one concealed air space whose horizontal thickness is not more thanchange end 25 mm,
b) the exposed construction materials within the space are noncombustible,
c) the exposed construction materials within the space, including insulation, but not including wiring, piping or similar services, have a flame-spread rating of not more than 25, or
d) the concealed wall space is filled with insulation.

contentHistory

9.10.16.3. Fire change beginBlockchange end Materials
1) Intent Statementchange beginExcept as permitted by Sentences (2) and (3), fire blocks shall be constructed of materials that will remain in place and prevent the passage of flames for not less than 15 min when subjected to the standard fire exposure in CAN/ULC-S101, “Fire Endurance Tests of Building Construction and Materials.”change end
2) Intent Statementchange beginFire blocks are deemed to comply with Sentence (1) if they arechange end constructed of not less than
a) 0.38 mm sheet steel,
b) 12.7 mm gypsum wallboard,
c) 12.5 mm plywood, OSB or waferboard, with joints having continuous supports,
d) 2 layers of 19 mm lumber with joints staggered, or
e) 38 mm lumber.
3) Intent StatementIn a building permitted to be of combustible construction, semi-rigid fibre insulation board produced from glass, rock or slag is permitted to be used to block the vertical space in a double-frame wall assembly formed at the intersection of the floor assembly and the walls, provided the width of the vertical space does not exceed 25 mm and the insulation board
a) has a density not less than 45 kg/m3,
b) is securely fastened to one set of studs,
c) extends from below the bottom of the top plates in the lower storey to above the top of the bottom plate in the upper storey, and
d) completely fills the portion of the vertical space between the headers and between the wall plates.
(See A-3.1.11.7.(7) in Appendix A.)
9.10.16.4. Penetration of Fire change beginBlockschange end
1) Intent StatementWhere change beginfire blockschange end are pierced by pipes, ducts or other elements, the effectiveness of the fire blocks shall be maintained around such elements.

9.10.17. Flame Spread Limits

9.10.17.1. Flame Spread Rating of Interior Surfaces
1) Intent StatementExcept as otherwise provided in this Subsection, the exposed surface of every interior wall and ceiling, including skylights and glazing, shall have a surface flame-spread rating of not more than 150.
2) Intent StatementExcept as permitted in Sentence (3), doors need not conform to Sentence (1) provided they have a surface flame-spread rating of not more than 200.
3) Intent StatementDoors within dwelling units, other than garage doors, need not conform to Sentences (1) and (2).
9.10.17.2. Ceilings in Exits or Public Corridors
1) At least 90 change beginper centchange end of the exposed surface of every ceiling in an exit or unsprinklered ceiling in a public corridor shall have a surface flame-spread rating of not more than 25. (See Article 9.10.17.6.)

contentHistory

9.10.17.3. Walls in Exits
1) Except as provided in Sentence (2), at least 90 change beginper centchange end of the exposed surfaces of every wall in an exit shall have a surface flame-spread rating of not more than 25. (See Article 9.10.17.6.)

contentHistory

2) At least 75 change beginper centchange end of the wall surface of a lobby used as an exit in Article 9.9.8.5. shall have a surface flame-spread rating of not more than 25. (See Article 9.10.17.6.)

contentHistory

9.10.17.4. Exterior Exit Passageways
1) Where an exterior exit passageway provides the only means of egress from the rooms or suites it serves, the wall and ceiling finishes of that passageway, including the soffit beneath and the guard on the passageway, shall have a surface flame-spread rating of not more than 25, except that up to 10 change beginper centchange end of the total wall area and 10 change beginper centchange end of the total ceiling area is permitted to have a surface flame-spread rating of not more than 150.

contentHistory

9.10.17.5. Walls in Public Corridors
1) At least 90 change beginper centchange end of the total wall surface in any unsprinklered public corridor shall have a surface flame-spread rating of not more than 75, or at least 90 change beginper centchange end of the upper half of such walls shall have a surface flame-spread rating of not more than 25. (See Article 9.10.17.6.)

contentHistory

9.10.17.6. Calculation of Wall and Ceiling Areas
1) Intent StatementSkylights, glazing, combustible doors, and combustible light diffusers and lenses shall not be considered in the calculation of wall and ceiling areas in this Subsection.
9.10.17.7. Corridors Containing an Occupancy
1) Intent StatementWhere a public corridor or a corridor used by the public contains an occupancy, the interior finish materials used on the walls or ceiling of such occupancy, shall have a surface flame-spread rating in conformance with that required for public corridors.
9.10.17.8. Light Diffusers and Lenses
1) Intent StatementLight diffusers and lenses having flame-spread ratings that exceed those permitted for the ceiling finish, shall conform to the requirements of Sentence 3.1.13.4.(1).
9.10.17.9. Combustible Skylights
1) Intent StatementIndividual combustible skylights in corridors required to be separated from the remainder of the building by fire separations shall not exceed 1 m2 in area and shall be spaced not less than 1.2 m apart.
9.10.17.10. Protection of Foamed Plastics
1) Intent StatementExcept as provided in Sentence (2), foamed plastics which form part of a wall or ceiling assembly in combustible construction shall be protected from adjacent space in the building, other than adjacent concealed spaces within attic or roof spaces, crawl spaces, and wall assemblies, by
a) one of the interior finishes described in Subsections 9.29.4. to 9.29.9.,
b) sheet metal mechanically fastened to the supporting assembly independent of the insulation and having a thickness of not less than 0.38 mm and a melting point not below 650°C, provided the building does not contain a Group C major occupancy, or
c) any thermal barrier that meets the requirements of Clause 3.1.5.12.(2)(e).
2) Intent StatementThermosetting foamed plastic insulation having a flame-spread rating of not more than 200 is permitted to be used in factory-assembled doors in storage garages serving single dwelling units provided that
a) the insulation is covered on the interior with a metallic foil,
b) the assembly has a flame-spread rating of not more than 200, and
c) the assembly incorporates no air spaces.
9.10.17.11. Walls and Ceilings in Bathrooms
1) Intent StatementThe interior finish of walls and ceilings in bathrooms within suites of residential occupancy shall have a surface flame-spread rating of not more than 200.
9.10.17.12. Coverings or Linings of Ducts
1) Intent StatementWhere a covering or a lining is used with a duct, such lining or covering shall have a flame-spread rating conforming to Article 3.6.5.4. or 9.33.6.4.

9.10.18. Alarm and Detection Systems

9.10.18.1. Access Provided through a Firewall
1) Intent StatementWhere access is provided through a firewall, the requirements in this Subsection shall apply to the floor areas on both sides of the firewall as if they were in the same building.
9.10.18.2. Fire Alarm System Required
1) change beginExcept as permitted in Sentences (3) , (4) and (5), a fire alarm system shall be installed in buildings in which a sprinkler system is required by this Part. (See Appendix.)change end

contentHistory

2) Intent StatementExcept as provided in Sentence (5), a fire alarm system shall be installed
a) in every building that contains more than 3 storeys, including storeys below the first storey,
b) where the total occupant load exceeds 300, or
c) when the occupant load for any major occupancy in Table 9.10.18.2. is exceeded.
Table 9.10.18.2.
Maximum Occupant Load for Buildings without Fire Alarm Systems
Forming part of Sentence 9.10.18.2.(2)

Major Occupancy Classification

Occupant Load Above which a Fire Alarm System is Required

Residential

10 (sleeping accommodation)

Business and personal services, Mercantile

150 above or below the first storey

Low- or medium-hazard industrial

75 above or below the first storey

3) change beginIn buildings in which a sprinkler system has been installed in accordance with NFPA 13D, “Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes,” a fire alarm system need not be installed.

contentHistory

4) Intent StatementIn buildings that contain fewer than 9 sprinklers conforming to Sentence 3.2.5.12.(4), a fire alarm system need not be installed.change end
5) Intent StatementA fire alarm system is not required in a residential occupancy where an exit or public corridor serves not more than 4 suites or where each suite has direct access to an exterior exit facility leading to ground level.
9.10.18.3. Design and Installation Requirements
1) Intent StatementExcept change beginas stated in Sentence (2) andchange end as required by this Subsection, where fire alarm, fire detection and smoke detection devices and systems are installed, these devices and systems and their installation shall conform to Subsection 3.2.4.
2) Intent Statementchange beginThe following Articles in Subsection 3.2.4. regarding fire alarm systems do not apply to Part 9 buildings: Articles 3.2.4.1., 3.2.4.11., 3.2.4.12., 3.2.4.13., 3.2.4.14., 3.2.4.21., and 3.2.4.22.change end
9.10.18.4. Rooms and Spaces Requiring Heat Detectors or Smoke Detectors
1) Intent StatementWhere a fire alarm system is required, every public corridor in buildings of residential occupancy and every exit stair shaft shall be provided with smoke detectors.
2) Intent Statementchange beginExcept as provided in Sentence (3), if a fire alarm system is required in a building that is not sprinklered, fire detectors shall be installed in the following spaces:
a) storage rooms not within dwelling units,
c) janitors’ rooms
d) rooms in which hazardous substances are to be used or stored (see A-3.3.1.2.(1) in Appendix A),
e) elevator hoistways, chutes and dumbwaiter shafts, and
f) laundry rooms in buildings of residential occupancy, but not those within dwelling units.change end
3) change beginExcept as required in Sentence (4),change end heat detectors and smoke detectors described in Sentence (2) are not required in dwelling units or in sprinklered buildings in which the sprinkler system is electrically supervised and equipped with a water flow alarm.

contentHistory

4) change beginHeat detectors or smoke detectors shall be installed in any elevator hoistway or dumbwaiter shaft which is not equipped with a sprinkler system.change end
9.10.18.5. Smoke Detectors in Recirculating Air-Handling Systems
1) Intent StatementExcept for a recirculating air system serving not more than one dwelling unit, where a fire alarm system is required to be installed, every recirculating air-handling system shall be designed to prevent the circulation of smoke upon a signal from a duct-type smoke detector where such system supplies more than one suite on the same floor or serves more than 1 storey.
9.10.18.6. Portions of Buildings Considered as Separate Buildings
1) Intent StatementExcept as provided in Sentence (2), where a vertical fire separation having a fire-resistance rating of not less than 1 h separates a portion of a building from the remainder of the building and there are no openings through the fire separation other than those for piping, tubing, wiring and conduit, the requirements for fire alarm and detection systems may be applied to each portion so separated as if it were a separate building.
2) Intent StatementThe permission in Sentence (1) to consider separated portions of a building as separate buildings does not apply to service rooms and storage rooms.
9.10.18.7. Central Vacuum Systems
1) Intent StatementCentral vacuum cleaning systems change beginserving more than one suite or storeychange end in buildings equipped with a fire alarm system shall be designed to shut down upon activation of the fire alarm system.
9.10.18.8. Open-Air Storage Garages
1) Intent StatementA fire alarm system is not required in a storage garage conforming to Article 3.2.2.88. provided there are no other occupancies in the building.

9.10.19. Smoke Alarms

9.10.19.1. Required Smoke Alarms
1) Smoke alarms conforming to change beginCAN/ULC-S531, “Standard for Smoke Alarms,”change end shall be installed in
a) each dwelling unit, and
b) each sleeping room not within a dwelling unit.

contentHistory

2) change beginAll smoke alarms installed in dwelling units in unsprinklered buildings shall be equipped with a battery powered back up system and a wired in manually operated device which is capable of silencing a smoke alarm signal for a period of not more than 10 minutes and re-sounding the signal if smoke levels in the vicinity trigger the smoke alarm.change end
9.10.19.2. change beginSound Patterns of Smoke Alarms
1) Intent StatementThe sound patterns of smoke alarms shall
a) meet the temporal patterns of alarm signals (see A-3.2.4.19.(2) in Appendix A), or
b) be a combination of temporal pattern and voice relay.change end
9.10.19.3. Location of Smoke Alarms
1) Intent StatementWithin dwelling units, sufficient smoke alarms shall be installed so that
a) there is at least one smoke alarm change begininstalledchange end on each change beginstoreychange end, including basements, and
b) change beginon any storey of a dwelling unit containing sleeping rooms, a smoke alarm is installedchange end
i) change beginin each sleeping room, andchange end
ii) change beginin a location between the sleeping rooms and the remainder of the storey, and if the sleeping rooms are served by a hallway, the smoke alarm shall be located in the hallway.change end
(See Appendix A.)
2) Intent Statementchange beginA smoke alarm required by Sentence (1) shall be installed in conformance with CAN/ULC-S553, “Installation of Smoke-Alarms.”change end
3) Intent StatementSmoke alarms required in Article 9.10.19.1. and Sentence (1) shall be installed on or near the ceiling.
9.10.19.4. Power Supply
1) Intent Statementchange beginExcept as provided in Sentences (2) and (3),change end smoke alarms change begindescribed in Sentence 9.10.19.1.(1)change end shall
a) be installed with permanent connections to an electrical circuit change begin(see A-3.2.4.21.(6)(a) in Appendix A),change end
b) have no disconnect switch between the overcurrent device and the smoke alarm, and
c) change beginin case the regular power supply to the smoke alarm is interrupted, be provided with a battery as an alternative power source that can continue to provide power to the smoke alarm for a period of no less than 7 days in the normal condition, followed by 4 minutes of alarm.change end
2) Intent StatementWhere the building is not supplied with electrical power, smoke alarms are permitted to be battery-operated.
3) change beginSuites of residential occupancy are permitted to be equipped with smoke detectors in lieu of smoke alarms, provided the smoke detectors
a) are capable of independently sounding audible signals within the individual suites,
b) except as permitted in Sentence (4), are installed in conformance with CAN/ULC-S524, “Installation of Fire Alarm Systems,” and
c) form part of the fire alarm system.
(See A-3.2.4.21.(7) in Appendix A.)

contentHistory

4) Intent StatementSmoke detectors permitted to be installed in lieu of smoke alarms as stated in Sentence (3) are permitted to sound localized alarms within individual suites, and need not sound an alarm throughout the rest of the building.change end
9.10.19.5. Interconnection of Smoke Alarms
1) Intent StatementWhere more than one smoke alarm is required in a dwelling unit, the smoke alarms shall be wired so that the activation of one alarm will cause all alarms within the dwelling unit to sound.

contentHistory

9.10.19.6. change beginSilencing of Smoke Alarms
1) Intent StatementExcept as permitted in Sentence (2), a manually operated device shall be incorporated within the circuitry of a smoke alarm installed in a dwelling unit so that the signal emitted by the smoke alarm can be silenced for a period of not more than 10 min, after which the smoke alarm will reset and sound again if the level of smoke in the vicinity is sufficient to re-actuate it.
2) Suites of residential occupancy equipped with smoke detectors installed to CAN/ULC-S524, “Installation of Fire Alarm Systems,” which are part of the fire alarm system in lieu of smoke alarms as permitted in Sentence 9.10.19.4.(3), need not incorporate the manually operated device required in Sentence (1).change end

contentHistory

9.10.19.7. Instructions for Maintenance and Care
1) Intent StatementWhere instructions are necessary to describe the maintenance and care required for smoke alarms to ensure continuing satisfactory performance, they shall be posted in a location where they will be readily available to the occupants for reference.

9.10.20. Firefighting

9.10.20.1. Windows or Access Panels Required
1) Intent StatementExcept as provided in Sentence (3), a window or access panel providing an opening not less than 1 100 mm high and 550 mm wide and having a sill height of not more than 900 mm above the floor shall be provided on the second and third storeys of every building in at least one wall facing on a street if such storeys are not sprinklered.
2) Intent StatementAccess panels required in Sentence (1) shall be readily openable from both inside and outside or be glazed with plain glass.
3) Access panels required in Sentence (1) need not be provided in buildings containing only dwelling units where there is no dwelling unit above another dwelling unit.

contentHistory

9.10.20.2. Access to Basements
1) Except in basements serving not more than one dwelling unit, each unsprinklered basement exceeding 25 m in length or width shall be provided with direct access to the outdoors to at least one street.

contentHistory

2) Intent StatementAccess required in Sentence (1) may be provided by a door, window or other means that provides an opening not less than 1 100 mm high and 550 mm wide, the sill height of which shall not be more than 900 mm above the floor.
3) Intent StatementAccess required in Sentence (1) may also be provided by an interior stair accessible from the outdoors.
9.10.20.3. Fire Department Access to Buildings
1) Access for fire department change beginvehicleschange end shall be provided to each change beginprincipal entrance of a building in accordance with Articles 3.2.5.4., 3.2.5.5. and 3.2.5.6.change end

contentHistory

2) Intent StatementWhere access to a building as required in Sentence (1) is provided by means of a roadway or yard, the design and location of such roadway or yard shall take into account connection with public thoroughfares, weight of firefighting equipment, width of roadway, radius of curves, overhead clearance, location of fire hydrants, location of fire department connections and vehicular parking.
3) change beginDespite the provisions of Sentence (1), an unobstructed path of travel for firefighters shall be provided to an ancillary residential building and the path of travel shall:
a) lead continuously from the street to the lane,
b) have a travel distance of no more than 45 m from the street to the principal entrance of the ancillary residential building,
c) be at least 900 mm wide,
d) have an overhead clearance of at least 2 m, and
e) consist of concrete, asphalt, or similar material.
4) An ancillary residential building shall have a strobe light installed and maintained outside the principal entrance, connected to an internal smoke alarm within the ancillary residential building.
5) Despite Clause 9.10.20.3.(3)(b) the path of travel for firefighters towards not more than one ancillary residential building on a parcel may exceed 45 m to a maximum of 70 m provided the principal entrance to that ancillary residential building is visible from the street.
6) If the principal building and the ancillary residential building are adjacent to a lane, the path of foot travel for firefighters to the ancillary residential building may be through the lane if
a) the travel distance from the street to the principal entrance of the ancillary residential building is no more than 70 m,
b) the path has an overhead clearance of at least 3 m,
c) the path consists of concrete, asphalt, or similar material, and
d) the principal entrance of the ancillary residential building is visible from the street.
7) Two adjacent parcels may have a single shared path of travel for firefighters over the common property line and the adjacent specified area to access both, provided
a) each parcel contains an ancillary residential building,
b) each parcel is subject to a covenant registered on title which prohibits construction upon or obstruction of the common property line and of a specified area adjacent to the property line; and
c) the path of travel meets the requirements of Sentences (3) , (4) and (5).change end

contentHistory

9.10.20.4. Portable Extinguishers
1) Portable extinguishers shall be installed in all buildings, except within dwelling units, in conformance with the change beginFire By-lawchange end.

contentHistory

9.10.20.5. Freeze Protection of Fire Protection Systems
1) Intent StatementEquipment forming part of a fire protection system that may be adversely affected by freezing temperatures and that is located in an unheated area shall be protected from freezing.

9.10.21. Fire Protection for Construction Camps

9.10.21.1. Requirements for Construction Camps
1) Except as provided in Articles 9.10.21.2. to 9.10.21.9., construction camps shall conform to Subsections 9.10.1. to 9.10.20.

contentHistory

9.10.21.2. Separation of Sleeping Rooms
1) Except for sleeping rooms within dwelling units, sleeping rooms in construction camps shall be separated from each other and from the remainder of the building by a fire separation having not less than a 30 min fire-resistance rating.

contentHistory

9.10.21.3. Floor Assemblies between the First and Second Storey
1) Except in a dwelling unit, a floor assembly in a construction camp building separating the first storey and the second storey shall be constructed as a fire separation having not less than a 30 min fire-resistance rating.

contentHistory

9.10.21.4. Walkways Connecting Buildings
1) Intent StatementWalkways of combustible construction connecting buildings shall be separated from each connected building by a fire separation having not less than a 45 min fire-resistance rating.
9.10.21.5. Spatial Separations
1) Construction camp buildings shall be separated from each other by a distance of not less than 10 m except as otherwise permitted in Subsections 9.10.14. and 9.10.15.

contentHistory

9.10.21.6. Flame-Spread Ratings
1) Except in dwelling units and except as provided in Sentence (2), the surface flame-spread rating of wall and ceiling surfaces in corridors and walkways, exclusive of doors, shall not exceed 25 over not less than 90 change beginper centchange end of the exposed surface area and not more than 150 over the remaining surface area.

contentHistory

2) Intent StatementExcept within dwelling units, corridors that provide access to exit from sleeping rooms and that have a fire-resistance rating of not less than 45 min shall have a flame-spread rating conforming to the appropriate requirements in Subsection 9.10.17.
9.10.21.7. Smoke Detectors
1) Except in dwelling units, corridors providing access to exit from sleeping rooms in construction camp buildings with sleeping accommodation for more than 10 persons shall be provided with a smoke detector connected to the building alarm system.

contentHistory

9.10.21.8. Portable Fire Extinguishers
1) Each construction camp building shall be provided with portable fire extinguishers in conformance with the appropriate provincial or territorial regulations or municipal bylaws or, in the absence of such regulations or bylaws, in conformance with the change beginFire By-lawchange end.

contentHistory

9.10.21.9. Hose Stations
1) Every construction camp building providing sleeping accommodation for more than 30 persons shall be provided with a hose station that is protected from freezing and is equipped with a hose of sufficient length so that every portion of the building is within reach of a hose stream.

contentHistory

2) Intent StatementHose stations required in Sentence (1) shall be located near an exit.
3) Intent StatementHoses referred to in Sentence (1) shall be not less than 19 mm inside diam and shall be connected to a central water supply or to a storage tank having a capacity of not less than 4 500 L with a pumping system capable of supplying a flow of not less than 5 L/s at a gauge pressure of 300 kPa.

9.10.22. Fire Protection for Gas, Propane and Electric change beginCooktops and Ovenschange end

(See Appendix A.)
9.10.22.1. Installation of change beginCooktops and Ovenschange end
1) Except as required in Sentence (2), natural gas and propane change begincooktops and ovenschange end shall be installed in accordance with the British Columbia Gas Safety Regulation pursuant to the British Columbia Safety Standards Act. (See also Article 9.34.1.1.)

contentHistory

2) Intent StatementClearances for and protection around gas, propane and electric ranges shall be not less than those provided in Articles 9.10.22.2. and 9.10.22.3.
9.10.22.2. Vertical Clearances above change beginCooktopschange end
1) Intent StatementExcept as provided in Sentence (2), framing, finishes and cabinetry installed directly above the location of the change begincooktopchange end shall be not less than 750 mm above the level of change begincooktopchange end burners or elements.
2) The vertical clearance described in Sentence (1) for framing, finishes and cabinets located directly above the location of the change begincooktopchange end may be reduced to 600 mm above the level of the elements or burners, provided the framing, finishes and cabinets
a) are noncombustible, or
b) are protected by
i) change beginnoncombustible cementitious boardchange end not less than 6 mm thick, covered with sheet metal not less than 0.33 mm thick, or
ii) a metal hood with a 125 mm projection beyond the framing, finishes and cabinets.

contentHistory

9.10.22.3. Protection around change beginCooktopschange end
1) Intent StatementExcept as provided in Sentences (2) and (3), combustible wall framing, finishes or cabinets within 450 mm of the area where the change begincooktopchange end is to be located shall be protected above the level of the heating elements or burners by material providing fire resistance at least equivalent to that provided by a 9.5 mm thickness of gypsum board.
2) Intent StatementCounter-top splash boards or back plates that extend above the level of heating elements or burners need not be protected as described in Sentence (1).
3) Intent StatementExcept for cabinetry described in Article 9.10.22.2., cabinetry located not less than 450 mm above the level of the heating elements or burners need not be protected as described in Sentence (1).