Division B
Acceptable Solutions
Part 9 — Housing and Small Buildings
Section 9.29. Interior Wall and Ceiling Finishes
9.29.1. General
9.29.1.1. Fire Protection and Sound Control
1) 
A wall or ceiling finish shall also conform to the appropriate requirements in
Sections 9.10. and
9.11., in addition to the requirements
in this Section.
9.29.2. Waterproof Wall Finish
9.29.2.1. Where Required
1) 
Waterproof finish shall be provided to a height of not less than
a) 1.8 m above the floor in shower stalls,
b) 1.2 m above the rims of bathtubs equipped with
showers, and
c) 400 mm above the rims of bathtubs not equipped
with showers.
9.29.2.2. Materials
1) 
Waterproof finish shall consist of ceramic, plastic or metal tile, sheet vinyl, tempered hardboard, laminated thermosetting decorative
sheets or linoleum.
9.29.3. Wood Furring
9.29.3.1. Size and Spacing of Furring
1) 
Wood furring for the attachment of wall and ceiling finishes shall conform to
Table 9.29.3.1.
Table 9.29.3.1. Size and Spacing of Furring Forming part of Sentence 9.29.3.1.(1) |
Maximum Spacing of Furring, mm (in.) |
Minimum Size of Furring, mm (in.) |
Maximum Spacing of Furring Supports |
Continuous Supports |
400 mm (in.) (o.c.) |
600 mm (in.) (o.c.) |
300 (12)
|
19 x 38 (¾ x 1½)
|
19 x 38 (¾ x 1½)
|
19 x 64 (¾ x 2½)
|
400 (16)
|
19 x 38 (¾ x 1½)
|
19 x 38 (¾ x 1½)
|
19 x 64 (¾ x 2½)
|
600 (24)
|
19 x 38 (¾ x 1½)
|
19 x 64 (¾ x 2½)
|
19 x 89 (¾ x 3½)
|
9.29.3.2. Fastening
1) 
Furring shall be fastened to the framing or to wood blocks with not less than 51 mm nails.
9.29.4. Plastering
9.29.4.1. Application
9.29.5. Gypsum Board Finish (Taped Joints)
9.29.5.1. Application
1) 
The requirements for application of gypsum board in this Subsection apply to the single layer application of gypsum board to wood furring
or framing using nails or screws.
9.29.5.2. Materials
1) 
Gypsum products shall conform to
b) ASTM C 1178/C 1178M, “Coated Glass Mat Water-Resistant Gypsum Backing Panel,” or
c) ASTM C 1396/C 1396M, “Gypsum Board.”
9.29.5.3. Maximum Spacing of Supports
1) 
Maximum spacing of supports for gypsum board applied as a single layer shall conform to
Table 9.29.5.3.
Table 9.29.5.3. Spacing of Supports for Gypsum Board Forming part of Sentence 9.29.5.3.(1) |
Thickness,
mm |
Orientation
of Board to Framing |
Maximum Spacing of Supports, mm o.c. |
Walls |
Ceilings |
Painted Finish |
Water-Based Texture
Finish |
Gypsum board
conforming to Sentence 9.29.5.2.(1) (except Sections 9 and 12 of ASTM C 1396/C 1396M
|
9.5 |
parallel |
— |
— |
— |
perpendicular |
400 |
400 |
— |
12.7 |
parallel |
600 |
400 |
— |
perpendicular |
600 |
600 |
400 |
15.9 |
parallel |
600 |
400 |
— |
perpendicular |
600 |
600 |
600 |
Gypsum
ceiling board conforming to Clause 9.29.5.2.(1)(c) (only Section 12 of ASTM C 1396/C 1396M
|
12.7
|
parallel
|
600
|
400
|
— |
perpendicular
|
600
|
600
|
600
|
9.29.5.4. Support of Insulation
1) 
Gypsum board supporting insulation shall be not less than 12.7 mm thick.
9.29.5.5. Length of Fasteners
1) 
The length of fasteners for gypsum board shall conform to
Table 9.29.5.5., except that lesser depths of penetration are permitted for assemblies required to have a
fire-resistance rating provided it can be shown, on the basis of fire tests,
that such depths are adequate for the required rating.
Table 9.29.5.5. Fastener Penetration into Wood Supports Forming part of Sentence 9.29.5.5.(1) |
Required Fire-Resistance Rating of Assembly |
Minimum Penetration, mm (in.) |
Walls |
Ceilings |
Nails |
Screws |
Nails |
Screws |
Not required |
20 (13/16)
|
15 (5/8)
|
20 (13/16)
|
15 (5/8)
|
45 min
|
20 (13/16)
|
20 (13/16)
|
30 (1 3/16)
|
30 (1 3/16)
|
1 h
|
20 (13/16)
|
20 (13/16)
|
45 (1 3/4)
|
45 (1 3/4)
|
1.5 h
|
20 (13/16)
|
20 (13/16)
|
60 (2 3/8)
|
60 (2 3/8)
|
9.29.5.6. Nails
1) Nails for fastening gypsum board to wood supports shall conform to
a)

ASTM F1667, “Driven Fasteners: Nails, Spikes, and Staples,”

or

NC2010 2010-01-01 R1
1) 
Nails for fastening gypsum board to wood supports shall conform to
CSA B111, “Wire Nails, Spikes and Staples.” a) ASTM F1667, “Driven Fasteners: Nails, Spikes, and Staples,” or
b) CSA B111, “Wire Nails, Spikes and Staples.”
9.29.5.7. Screws
9.29.5.8. Spacing of Nails
1) 
For single-layer application on a ceiling, nails shall be spaced
a) not more than 180 mm o.c. on ceiling supports, or
b) every 300 mm o.c. along ceiling supports, in pairs
about 50 mm apart.
2) 
Where the ceiling sheets are supported by the wall sheets around the perimeter of the ceiling, this support may be considered as equivalent
to nailing at this location.
3) 
Except as required by
Sentence (4), for single-layer application on walls, nails shall be spaced
a) not more than 200 mm o.c. on vertical wall supports, or
b) every 300 mm o.c. along vertical wall supports,
in pairs about 50 mm apart.
4) 
For single-layer application on walls, where gypsum board

provides required bracing in
braced wall panels, lateral support for studs,

or fire protection, nails shall be spaced not more than 200 mm o.c. on
a) vertical wall supports, and
b) top and bottom plates.
(See Article 9.23.10.2. and Section 9.10.) 5) 
The uppermost nails on vertical wall supports shall be not more than 200 mm below the ceiling.
6) 
Nails shall be located not less than 10 mm from the side or edge of the board.
7) 
Nails shall be driven so that the heads do not puncture the paper.
9.29.5.9. Spacing of Screws
1) 
For single-layer application on a ceiling, screws shall be spaced not more than 300 mm o.c. on ceiling supports.
2) 
Where the ceiling sheets are supported by the wall sheets around the perimeter of the ceiling, this support may be considered as equivalent
to screwing at this location.
3) 
Except as required by
Sentence (4), for single-layer application on walls, screws shall be spaced
a) not more than 300 mm o.c. on vertical wall supports where the supports are more than 400 mm o.c., or
b) not more than 400 mm o.c. on vertical wall supports
where the supports are not more than 400 mm o.c.
4) 
Except as provided in
Sentence (5), for single-layer application on walls, where gypsum board

provides required bracing in
braced wall panels, lateral support for studs,

or fire protection, screws shall be spaced not more than 300 mm o.c. on
a) vertical wall supports, and
b) top and bottom plates.
(See Article 9.23.10.2. and Section 9.10.) 6) 
Screws shall be located not less than 10 mm from the edge of the board.
7) 
Screws shall be driven so that the heads do not puncture the paper.
9.29.5.10. Low Temperature Conditions
1) 
In cold weather, heat shall be provided to maintain a temperature not below 10°C for 48 h prior to taping
and finishing and maintained for not less than 48 h thereafter.
9.29.6. Plywood Finish
9.29.6.1. Thickness
Table 9.29.6.1. Thickness of Plywood Interior Finish Forming part of Articles 9.29.6.1. and 9.29.6.2. |
Maximum
Spacing of Supports, mm o.c. |
Minimum Thickness, mm(1) |
On Supports with no Horizontal
Blocking |
On Supports with Blocking
at Vertical Intervals not Exceeding 1.2 m
|
400 |
4.7 |
4.0 |
600 |
8.0 |
4.7 |
2) 
A manufacturing tolerance of −0.4 mm may be applied to the thicknesses listed in
Table 9.29.6.1. 3) 
No minimum thickness is required where plywood is applied over continuous backing.
9.29.6.2. Grooved Plywood
1) 
Except as permitted in
Sentence (2), where plywood for interior finish is grooved, the grooves shall not extend through the face ply and into the plies below the face
ply unless the groove is supported by framing or furring.
2) 
If the grain of the face ply is at right angles to the supporting members, the groove is permitted to extend into plies below the face
ply provided the thickness of the plywood exceeds the value shown
in
Table 9.29.6.1. by an amount equal to not less than the depth of penetration of the grooves into the plies below the face
ply.
9.29.6.3. Nails and Staples
1) 

Except as provided in
Sentence (2)
, nails for attaching plywood finishes shall not be less than 38 mm casing or finishing nails
spaced not more than 150 mm o.c. along edge supports
and 300 mm o.c. along intermediate supports, except that
staples providing equivalent lateral resistance may also be used.
2) 

Where plywood finish provides required bracing in
braced wall panels, the plywood shall be fastened in accordance with the fastening requirements for sheathing
stated in
Sentence 9.23.3.5.(2).

9.29.6.4. Edge Support
1) 
All plywood edges shall be supported by furring, blocking or framing.
9.29.7. Hardboard Finish
9.29.7.1. Material Standard
9.29.7.2. Thickness
1) 
Hardboard shall be not less than
a) 3 mm thick where applied over continuous backing,
b) 6 mm thick when applied over supports spaced not more than 400 mm o.c., and
c) 9 mm thick when applied over supports spaced not
more than 600 mm o.c.
9.29.7.3. Nails
1) 
Nails for fastening hardboard shall be casing or finishing nails not less than 38 mm long, spaced not more than 150 mm o.c. along edge supports and 300 mm o.c.
along intermediate supports.
9.29.7.4. Edge Support
1) 
All hardboard edges shall be supported by furring, blocking or framing where the backing is not continuous.
9.29.8. Insulating Fibreboard Finish
9.29.8.1. Material Standard
1) Insulating fibreboard shall conform to

CAN/ULC-S706, “Wood Fibre Insulating Boards for Buildings.”


NC2010 2010-01-01 R1
1) 
Insulating fibreboard shall conform to CAN/ULC-S706, “Wood Fibre Insulating Boards for Buildings.”
9.29.8.2. Thickness
1) 
Insulating fibreboard sheets shall be not less than 11.1 mm thick on supports not more than 400 mm o.c.
2) 
Insulating fibreboard tile shall be not less than 12.7 mm thick on supports spaced not more than 400 mm o.c.
9.29.8.3. Nails
1) 
Nails for fastening fibreboard sheets shall be not less than 2.6 mm shank diameter casing or finishing nails of sufficient length to penetrate not less than 20 mm into the supports.
2) 
Nails shall be spaced not more than 100 mm o.c. along edge supports and 200 mm o.c. along intermediate
supports.
9.29.8.4. Edge Support
1) 
All fibreboard edges shall be supported by blocking, furring or framing.
9.29.9. Particleboard, OSB or Waferboard Finish
9.29.9.1. Material Standard
2) 
OSB or waferboard finish shall conform to
9.29.9.2. Minimum Thickness
2) 
Thicknesses listed in
Table 9.29.6.1. shall permit a manufacturing tolerance of − 0.4 mm.
3) 
No minimum thickness is required where O-2 grade OSB is applied over continuous backing.
4) 
OSB conforming to O-1 grade, waferboard conforming to R-1 grade and particleboard shall be
a) not less than 6.35 mm thick on supports not more
than 400 mm o.c.,
b) not less than 9.5 mm thick on supports not more
than 600 mm o.c., and
c) not less than 6.35 mm thick on supports not more
than 600 mm o.c. in walls where blocking is provided
at midwall height.
5) 
OSB conforming to
CAN/CSA-O325, “Construction Sheathing,” shall meet the minimum panel mark of
a) W16, on supports not more than 400 mm o.c.,
b) W24, on supports not more than 600 mm o.c., and
c) W16, on supports not more than 600 mm o.c. where blocking is provided at mid-wall height.
9.29.9.3. Nails
1) 

Except as provided in
Sentence (2),

nails for fastening particleboard, OSB or waferboard shall be not less than 38 mm casing or
finishing nails spaced not more than 150 mm o.c. along
edge supports and 300 mm o.c. along intermediate supports.
2) 

Where OSB or waferboard provides required bracing in
braced wall panels, the OSB or waferboard shall be fastened in accordance with the fastening requirements for
sheathing stated in
Sentence 9.23.3.5.(2).

9.29.9.4. Edge Support
1) 
All particleboard, OSB or waferboard edges shall be supported by furring, blocking or framing.
9.29.10. Wall Tile Finish
9.29.10.1. Tile Application
1) 
Ceramic tile shall be set in a mortar base or applied with an adhesive.
2) 
Plastic tile shall be applied with an adhesive.
9.29.10.2. Mortar Base
1) 
When ceramic tile is applied to a mortar base the cementitious material shall consist of one part Portland cement to not more than
one-quarter part lime by volume.
2) 
The cementitious material described in
Sentence (1) shall be mixed with not less than 3 nor more than 5 parts of aggregate per part of cementitious material by volume.
3) 
Mortar shall be applied over metal lath or masonry.
4) 
Ceramic tile applied to a mortar base shall be thoroughly soaked and pressed into place forcing the mortar into the joints while the
tile is wet.
9.29.10.3. Adhesives
1) 
Adhesives to attach ceramic and plastic tile shall be applied to the finish coat or brown coat of plaster that has been steel-trowelled
to an even surface or to gypsum board or to masonry provided the masonry
has an even surface.
9.29.10.4. Moisture-Resistant Backing
1) 
Ceramic and plastic tile installed on walls around bathtubs or showers shall be applied over moisture-resistant backing.
9.29.10.5. Joints between Tiles and Bathtub