Division B
Acceptable Solutions

Part 4 — Flammable and Combustible Liquids

Section 4.7. Bulk Plants

4.7.1. Scope

4.7.1.1. Application
1) Intent StatementThis Section shall apply to that portion of a property where flammable liquids or combustible liquids are received in bulk quantities and are stored or handled for the purpose of being distributed.

4.7.2. Storage

4.7.2.1. Storage
1) Intent StatementFlammable liquids and combustible liquids shall be stored in
a) closed containers, in conformance with Article 4.7.2.4., or
b) storage tanks, in conformance with Section 4.3.
4.7.2.2. Storage Tanks
1) Intent StatementAt bulk plant rail loading and unloading facilities, the minimum distance from a storage tank to a railway line shall be in conformance with TC General Order No. O-32, C.R.C., c1148, “Flammable Liquids Bulk Storage Regulations.”
4.7.2.3. Hydraulic Pressure Shock
1) Intent StatementBulk storage tanks, piping, pumps, valves and associated components shall be designed, installed and maintained to accommodate hydraulic pressure shock on the system.
4.7.2.4. Container Storage
1) Intent StatementContainers for flammable liquids or combustible liquids stored indoors shall be stored in conformance with Subsection 4.2.7.
2) Intent StatementContainers for flammable liquids or combustible liquids stored outdoors shall be stored in conformance with Subsection 4.2.11., except that the distance between the piles and property lines and the distance between piles need not apply when the containers are stored in an area that does not present a hazard to neighbouring property.
4.7.2.5. Spill Control
1) Intent StatementAn outdoor storage area shall be designed to accommodate accidental spillage in conformance with Subsection 4.1.6.
4.7.2.6. Fencing
1) Intent StatementThe outdoor area occupied by aboveground storage tanks, container storage, ancillary equipment and unloading facilities shall be fenced in conformance with Article 3.3.2.6.

4.7.3. Dispensing

4.7.3.1. Interconnection
1) Intent StatementDispensing systems for Class I liquids shall not be interconnected with dispensing systems for Class II and IIIA liquids.
4.7.3.2. Dispensing into Vehicles
1) Intent StatementDispensers used by the general public to dispense flammable liquids or combustible liquids into the fuel tanks of vehicles shall not be located at a bulk plant unless separated by a fence or equivalent barrier from the area in which the bulk storage operations are conducted.
2) Intent StatementWhere a dispenser referred to in Sentence (1) is supplied from an aboveground storage tank
a) an automatically operated valve that is designed to open only when the dispenser is being operated shall be provided at the tank outlet, and
b) an emergency valve shall be provided for the dispenser in conformance with Sentence 4.6.6.3.(1).
4.7.3.3. Dispensing into Metal Containers or Tanks
1) Intent StatementClass I liquids shall not be dispensed into a metal container or storage tank unless it is electrically connected in conformance with Article 4.1.8.2.

4.7.4. Loading and Unloading Facilities

(See Appendix A.)
4.7.4.1. Clearances
1) Intent StatementAt a loading or unloading facility for tank vehicles or tank cars, the horizontal distance from the fill stem to an aboveground storage tank, a building or a property line shall be not less than
a) 7.5 m for Class I liquids, and
b) 4.5 m for Class II and IIIA liquids.
2) Intent StatementAt bulk plant rail loading and unloading facilities, the minimum distance from a loading structure to a railway line shall be in conformance with TC General Order No. O-32, C.R.C., c1148, “Flammable Liquids Bulk Storage Regulations.”
3) Intent StatementBuildings for the shelter of personnel or pumps shall be considered a part of the loading or unloading facility.
4.7.4.2. Multi-purpose Facilities
1) Intent StatementWhen piping and pumping systems have been used for the transfer of either flammable liquids or combustible liquids at loading or unloading facilities, the system shall be cleaned of vapours before the other class of liquid is introduced.
4.7.4.3. Check Valves
1) Intent StatementSystems through which tank cars or tank vehicles discharge into aboveground storage tanks by means of pumps shall be provided with check valves to prevent backflow and the inadvertent mixing of liquids.
2) Intent StatementSystems referred to in Sentence (1) shall be designed, installed and maintained to prevent leakage or spillage.
4.7.4.4. Control Valves
1) Intent StatementValves installed to control the filling of tank vehicles or tank cars shall be of the self-closing type.
2) Intent StatementControl valves referred to in Sentence (1) shall be held open manually, except where automatic devices are provided for shutting off the flow in order to prevent the overfilling of tank vehicle or tank car compartments. (See Appendix A.)
4.7.4.5. Bonding and Grounding
(See Appendix A.)
1) Intent StatementBonding, grounding and isolation components for protection against static charges during the loading or unloading of tank vehicles or tank cars shall be provided when transferring flammable liquids or combustible liquids.
2) Intent StatementWhere flammable liquids or combustible liquids are transferred from or into railway tank cars, the railway tracks shall be bonded throughout their length and permanently grounded in conformance with TC SOR/82-1015, “Railway Prevention of Electric Sparks Regulations.”
3) Intent StatementBonding required in Sentence (1) shall consist of a metallic bond wire connected to the fill stem or to some part of the loading or unloading structure that is in electrical contact with the fill stem in conformance with Subsection 4.1.4.
4) Intent StatementBonding wires for tank vehicles shall be provided with a pull-off connector attached so as to be in electrical contact with the cargo tank of the tank vehicle.
5) Intent StatementThe bonding connection required in Sentence (1) shall be fixed to the tank vehicle or storage tank before dome covers are raised and shall remain in place until filling is completed and all dome covers have been closed and secured.
4.7.4.6. Downspouts
1) Intent StatementExcept as provided in Sentence 4.1.8.2.(3), when tank vehicles or tank cars are filled with Class I or II liquids through the top of the tank, the fill pipe shall terminate within 150 mm of the bottom of the tank.

4.7.5. Fire Protection

4.7.5.1. Portable Extinguishers
1) Intent StatementAt least 2 portable extinguishers, each having a rating of not less than 80-B:C, shall be provided at hazardous locations in bulk storage plants for flammable liquids and combustible liquids.

4.7.6. Spill Control

4.7.6.1. Spill Control
1) Intent StatementFacilities to control possible spills of flammable liquids or combustible liquids shall be provided at loading and unloading points, in conformance with Subsection 4.1.6.